Goodman Mfg Condensing Units, CKF50Hz service manual Condensing Unit Specifications

Page 6

CONDENSING UNIT SPECIFICATIONS

 

 

 

 

 

 

 

 

CKF24- 2*

CKF36-2*

CKF36-5 *

CKF48-5*

CKF6 0-5*

CKF70- 5*

 

 

 

 

 

 

 

Cooling Capacity, BTUH/kW

24600/7.2

34000/10.0

34000/10.0

44000/12.9

55000/16.1

64000/18.8

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

R.L. Amps

12.50

17.9

5.3

7.4

9

10.9

L.R. Amps

61.0

97.4

42.0

50.0

74.0

101.0

High Pressure Switch-Open / Close

410/275

410/275

410/275

410/275

410/275

410/275

Condenser Fan Motor

1/4

1/4

1/4

1/4

1/4

1/3

Horsepower

F.L. Amps

0.9

0.9

0.8

0.8

0.8

1.2

Liquid Line, Inches [mm] O.D.*

3/8 [9.6]

3/8 [9.6]

3/8 [9.6]

3/8 [9.6]

3/8 [9.6]

3/8 [9.6]

Suction Line, Inches [mm] O.D.*

3/4 [19.1]

3/4 [19.1]

7/8 [22.3]

7/8 [22.3]

7/8 [22.3]

7/8 [22.3]

Refrigerant Charge

88

89

89

113

121

153

Power Supply

 

 

 

 

 

 

Minimum Circuit Ampacity(1)

16.6

23.3

7.5

10

12

14.8

Maximum Overcurrent Device(2)

25

40

15

15

20

20

Electrical Conduit Size

 

 

 

 

 

 

Power Supply (Inches)

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

(mm)

[13 or 20]

[13 or 20]

[13 or 20]

[13 or 20]

[13 or 20]

[13 or 20]

Approximate Shipping Weight (lbs-[kg])

180 [82]

184 [84]

184 [84]

191 [87]

210 [96]

228 [104]

 

 

 

 

 

 

 

[ ] Designates metric equivalents

1Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

2May use fuses or HACR-type circuit breakers of the same size as noted.

NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.

CKF**-*P* models are shipped with a nitrogen holding charge only.

6

Image 6
Contents Technical Manual 036 Product IdentificationDo not connect or use any device Product Design Me asurements in inches. Desi gnates metric equi valentsDimensions Condensing Unit Specifications CKF24 CKF36-2 CKF36-5 CKF48-5 CKF6 CKF7012.4 Entering Indoor Wet Bulb Temperature22.2 24412.9 Airflow24.0 26030.6 18.9253 19.7 Outdoor Ambient Temperature 105 115 118F 125F33.0 270Outdoor Ambient Temperature 254105 115 118F 125F 27140.8 11.2246 44.0 11.6271 51.0 11.1Cooling Performance Data 55.011.5 56.5 13.6264 61.0 14.1282 Performance Data Performance TestWiring DiagramsWiring Diagrams CKF48-70M/N/P