Hitachi RAC-35YH6, RAS-35YH6 installation manual Direct Mounting On The Wall

Page 1

FOR SERVICE PERSONNEL ONLY

THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation.)

WARNING

WARNING

SAFETY PRECAUTION

• Read the safety precautions carefully before operating the unit.

The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.

UNIT

 

CAUTION

• No nearby heat source and no obstruction near the air

 

outlet is allowed.

INDOOR

The clearance distances from top, right and left are

 

specified in figure below.

 

 

• The location must be convenient for water drainage and pipe connection with the Outdoor unit.

• To avoid interference from noise, please place the unit and its remote controller at least 1m from the radio and television.

• To avoid any error in signal transmission from the remote controller, please put the controller far away from high- frequency machines and high-power wireless systems.

The Outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.

 

CAUTION

UNIT

• Do not expose the unit under direct sunshine or rain.

• The air blown out of the unit should not point directly to

 

Besides, ventilation must be good and clear of obstruction.

OUTDOOR

animals or plants.

from the floor.

 

• The clearances of the unit from top, left, right and front are

specified in figure below. At least two of the above sides must be open air.

• The installation height should be at least 2,300 mm or more

• Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.

• Do not install at a location where there is flammable gas, steam, oil and smoke.

• The location must be convenient for water drainage.

• The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

WARNING

Incorrect methods of installation may cause death or serious injury.

CAUTION

Improper installation may result in serious consequence.

Make sure to connect earth line.

This sign in the figures indicates prohibition.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.

WARNING

• Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the

installation work yourself.

• Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause

water leakage, electric shock and fire.

• Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may

collapse and impose danger.

• Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing

with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and

fire may occur due to the use of low quality wire or improper work.

• Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the

conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the

terminal base. Improper insertion and loose contact may cause over-heating and fire.

• Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or

Names of Indoor Components

No.

Item

Qty

 

Hanger

 

1

 

1

 

Screw for Hanger

6

2

 

 

(4.1 x 32)

 

 

Holder for Remote

 

3

Controller

1

 

AAA size Battery

2

4

 

 

Screw for holder of

 

5

Remote Controller

2

 

(3.1 x 16)

 

The Length of Indoor Unit

Connecting Cord

above

 

 

 

 

 

above

0.9 m

 

 

 

 

 

1.6 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the power is supplied from the indoor unit, pull the power cable from the cable drawer at the right or left side of the indoor unit.

Cable drawer (right side)

Direction of Piping

Backward piping from left

Connection

• Place the Outdoor unit and its connecting cord at least 1 m away from the antenna or signal line of television, radio or telephone. This is to avoid noise interference.

Figure showing the Installation of Indoor and Outdoor Unit.

 

 

 

 

above

 

 

 

 

50mm

 

 

 

1

2

 

 

 

 

 

above 50mm

above 50mm

Be sure to

 

 

 

 

completely

 

 

 

 

seal any gap

 

0.45m

 

 

with putty.

 

 

 

bendnotmust

 

 

 

300mmabout

about

6 Used in

2,300 mm or more

 

 

 

 

horizontal piping

stronger vibration may occur.

• Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.

• When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)

does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally

which could result in a rupture and injury.

• Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may

occur.

• After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the

room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

• Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner

technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.

• Be sure to connect the earth line from the power supply wire to the outdoor unit and between

the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the

telephone unit. Improper earthing may cause electric shocks.

• When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.

If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a

pressure in the freezing cycle system will build up steeply, causing an explosion or injury.

• When installing the unit, be sure to install the refrigerant pipe before starting the compressor.

If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the

pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.

CAUTION

A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.

Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire

if flammable gas leaks around it.

Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your funiture.

An IEC approved power cord should be used. Power cord type: NYM.

 

Holder

6

1

 

Remote Controller

7

1

 

Insulation sheet

8

1

 

Bush

9

1

 

Drain Pipe

0

1

 

Switch Cover

A

1

 

Purifying Filter

B

1

The components of 9 & 0 are included in the package of the outdoor unit.

There are 6 directions allowed, namely, backward piping, backward piping from left, horizontally piping from right, horizontally piping from left, vertically down from right, vertically down from left.

Dimension of Mounting Stand of the Outdoor unit

(unit : mm)

 

(10)

 

50

Mounting

 

 

 

 

330

310

 

 

Stand

 

 

 

 

10

35

12

 

 

500

 

 

 

 

 

 

 

 

 

125

 

above 50 mm when installed on the ceiling of balcony

above 100mm

above 300mm

Maximum pipe length 20m

above 200mm

above 50mm

give clearance

as wide as

possible

above

200mm

7

5 4 3

Plug (Procure locally)

The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commercial products.)

The refrigerating machine oil is easily affected by moisture. Use caution to prevent water from entering the cycle.

The difference in height between the indoor and outdoor unit should be kept below 10m.

The connecting pipe, no matter big or small, should all be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape).

The connection of insulated drain hose.

Inner diameter 16mm

Please use insulated drain hose for the indoor piping (commercial product)

UNIT

1 Installation of Hanger, Wall Penetration and Installation of Protection Pipe

CAUTION

The draining of the water container inside the Indoor unit can be done from the left. Therefore the hanger must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.

Direct Mounting On The Wall

• Please use hidden beams in the wall to hold the hanger.

Visible outline of the

450mm

 

 

outdoor unit

 

 

400mm

 

 

125mm

316mm

20mm

125mm

 

 

41mm

 

 

44mm

280mm

199mm

 

 

Wall hole

80mm

 

42mm

 

 

 

45mm

 

45mm

ø65mm

65mm

390mm

10mm

ø65mm

Drain Hose

 

530mm

 

Drain Hose

 

Level

780mm

 

 

 

2 Screw for Hanger

 

 

 

 

1 Hanger

 

Screw the hanger at the

 

positions possibly near the

 

upper and lower hooks where

 

the indoor unit is hung. Use 4 or

Line

more screws to fix the hanger.

Weight

Wall hole

 

Procedures of Installation and Precautions

• Procedures to fix the hanger.

2 Installation Of The Indoor Unit

Cutting Low Cover bush

• While installing the pipe from the right, left or bottom side, use a knife to cut openings as shown in figure. Then smoothen the edges of openings with a file.

Openings

¡PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL) Openings

Preparation

Connect connecting cord.

Pull out the pipe, connecting cord and drain hose.

Installation

 

• Insert the pipe through the wall hole.

Connecting cords, pipe and

¡ The upper part of the Indoor unit is hanged on the

drain hose must be laid

together with Vinyl tape.

hanger.

 

 

 

Wall hole

The projection at the lower part of the Indoor unit is

 

 

 

hooked onto the hanger.

 

 

Pipe

 

 

 

 

1 Hanger

¡ 1 Hanger

Cable

Drain hose

 

 

 

 

Lift the body

Drain layout of

 

Refrigerating

backward piping

 

of the unit

 

 

 

 

Pipe

upwards and

 

 

 

 

then force it

 

 

 

 

downwards.

 

 

Protection

 

 

 

Drain Hose Connecting Cord

 

 

Pipe

 

 

 

 

Projection

 

 

INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES

The refrigerating pipe should be adjusted to fit into

Drain hose

 

the hole on the wall and then ready for further

 

 

 

connection.

 

• The terminals of 2 connected pipes must be covered

 

 

with insulator used for terminal connection. Then the

Connecting

 

pipes are wrapped with insulation pipe.

cord

Connect the connecting cord after removing low

Pipe

 

cover.

 

 

 

(Refer to "CONNECTION OF POWER CORD")

 

After adjustment, fit the connecting cord and pipes

 

 

into the space available under the unit. Use holder to

 

 

hold them tight.

 

Holder can be attached at the either of 2 places. Insulation pipe (must be wrapped with Holder

 

Please select the easier position.

vinyl tape at every 120 mm)

THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT

Preparation To Install Refrigerating Pipes

The end of the refrigerating pipes are at

locations marked with “” symbol.

The refrigerating pipes and connecting cord transform and are attached.

0.85m

 

Please bend at a small

below

radius to form an arc

5mm

Installation

 

Hang the indoor unit onto the hanger. Use the temporary stand Projection

 

at the back of the Indoor unit to push its lower part 15cm

Hook

forwards.

 

• Place the drain hose through the hole on the wall.

 

INDOOR

1. Drill holes on wall.

2. Push plug into the holes.

3. Fix the hanger on wall with

PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

(As shown below)

(As shown below)

4.1 x 32 screw.

Preparation

 

 

(As shown in figure below)

 

 

 

Wall

1 Hanger

Plug

Ceiling

Changed of Drain Hose and Installation Procedures.

 

.8mm

(Procure

Exchange the location of drain hose and drain cap while installing the pipe from the left side as

 

 

2 Screw

locally)

 

 

shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.

 

above 50mm

 

 

ø4

 

 

 

 

• Please use pliers to pull out the drain cap.

CAUTION

 

 

 

 

 

32mm

Wall

 

 

 

(This is an easier way to remove the drain

Insufficient insert may

 

 

 

cap).

 

 

 

 

 

result in water leakage.

 

 

 

 

 

 

• Procedures to fix the holder of remote control.

 

4.1 x 32 screw

 

 

1. Drill holes on wall.

2. Push plug into the holes.

 

 

 

 

 

(As shown below)

(As shown below)

 

 

 

Rib at the Indoor unit

 

 

 

 

 

Wall

 

 

 

 

 

ø4.4mm

Control

 

 

 

drain hose end

 

 

 

Drain cap

Drain Hose

Insulating

 

3 Remote

 

section of the

 

 

 

 

 

Holder

5 Screw

 

• Remove low cover

• Push the pipe deeply until the insulating

 

Plug

 

• Insert drain cap up to the

20mm

 

 

section of the drain hose end gets over the

(Procure locally)

 

location securely till the

 

 

rib at the indoor unit side.

 

 

 

 

cap stops.

 

 

 

 

 

Wrap the refrigerating pipes with insulation pipe after connecting refrigerating pipe.

Connect the connecting cord after removing low cover.

 

 

about 15cm

 

(Refer to "Connection of Power Cord")

 

 

 

 

 

 

• After adjustment, the connecting cord and refrigerating pipes

 

 

are placed into the space available under the Indoor unit.

Protection

 

The projection of Indoor unit must hook to the hanger.

 

 

 

pipe

 

 

 

Wall hole

 

 

 

Drain hose

 

Pipe

 

Connecting

Refrigerating

Pull this to the front during the

 

 

cord

pipe

 

 

 

Drain hose

connection of refrigerating

 

 

 

Cable

 

Heat

 

 

 

 

pipe to ease task.

 

 

 

 

 

 

 

Connecting cord

Drain layout of backward piping from left

 

insulation pipe

 

 

 

 

 

Holder Connected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

section

 

3 Heat Insulation and Finish of the Piping

 

 

 

• The connected terminals should be completed sealed

Insulation material for pipe

 

with heat insulator and then tied up with rubber strap.

connection

 

Do not tie the terminals with the tape too tight.

 

 

 

 

If any clearance or over-tightening may cause

 

 

 

 

condensation.

 

 

 

 

 

 

Please tie the pipe and power line together with vinyl

 

Sleeve of

 

 

tape as shown in the figure showing the installation of

 

 

 

 

protection pipe

Putty

 

Indoor and Outdoor units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall Penetration and Installation of Protection Pipe

Drill a ø65mm hole on wall which is

 

Indoor

 

 

 

 

 

Outdoor

 

WARNING

 

slightly tilted towards the outdoor side.

 

 

 

 

 

 

 

2-5mm

 

 

 

 

 

 

 

 

Be sure that the wire is not

 

Drill the wall at a small angle.

Seal with

 

 

 

Seal with

 

 

 

 

Cut the protection pipe according to the

 

 

 

in contact with any metal in

putty

 

 

 

putty

 

 

 

the wall. Please use the

 

wall thickness.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

protection pipe as wire

Empty gap in the sleeve of protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

passing through the hollow

 

pipe should be completely sealed with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

part of the wall so as to

 

putty to avoid dripping of rain water into

Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

prevent the possibility of

 

 

WALL

 

 

 

 

 

 

the room.

pipe

 

 

 

 

 

 

damaged by mouse.

Please ensure smooth flow of water

 

 

 

 

Sleeve of

 

 

 

 

 

 

 

protection

Unless it seals completely,

 

when installing the drain hose. Improper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pipe

any air with high humidity

 

installing may wet your funiture.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain cap

CAUTION

The rubber strap used for fixing the insulator

 

 

 

should not be tied with great force. Otherwise,

 

 

 

this will damage heat insulation and causes

Pipe

Rubber strap tied

 

water condensation.

 

 

with great force

Please pull the lower part of the Indoor unit

 

 

 

 

outwards to check if the unit is hooked onto

 

 

 

the hanger. Improper installation may cause

 

 

 

vibration and noise.

 

 

Transform the piping while holding down the

Pipe

 

 

lower portion of pipe-support by hand.

Transform after

 

support

To enhance the heat insulation and to prevent water

 

 

condensation, please cover the outdoor part of the

 

 

drain hose and pipe with insulation pipe.

 

Completely seal any gap with putty.

Putty

 

 

4 Installation of Drain Hose

 

 

CAUTION

Ditch

Be sure that the drain hose is

Condensed

not loosely connected bend or

water pond

Bending upwards Condensed water

proper condition like left figure.

pond

 

You are free to choose the side (left or right) for the installation of drain

• An IEC approved power cord should be

flows from outdoor and any

bending downward.

hose. Please ensure the smooth flow of condensed water of the Indoor

CAUTION

used. Power cord type: NYM.

dew may drop.

unit during installation. (Careless may result in water leakage.)

06K108_RAS-35_YH6_English.p65

1

11/13/06, 3:02 PM

Image 1
Contents Wall Penetration and Installation of Protection Pipe Procedures of Installation and PrecautionsDirect Mounting On The Wall Wiring of The Indoor Unit Procedures of WiringWiring of the Outdoor Unit Power Source

RAC-35YH6, RAS-35YH6 specifications

The Hitachi RAS-35YH6 and RAC-35YH6 air conditioning units represent a remarkable blend of advanced technology and energy efficiency, making them ideal for both residential and commercial settings. These models are known for their effective cooling and heating capabilities, ensuring optimum comfort throughout the year.

One of the main features of the RAS-35YH6 and RAC-35YH6 is their inverter technology. This innovative feature allows the units to adjust the compressor speed according to the temperature requirements of the environment. As a result, energy consumption is significantly reduced, leading to lower utility bills. The inverter system also contributes to quieter operation, creating a serene environment in homes and offices.

Another noteworthy characteristic of these models is the use of high-energy efficiency ratings. The RAS-35YH6 and RAC-35YH6 achieve impressive seasonal energy efficiency ratios, ensuring that users can enjoy a comfortable interior without the guilt of high energy consumption. This not only benefits the environment but also aligns with the increasing demand for sustainable energy solutions.

The air conditioning units are equipped with a powerful air purification system. This technology effectively filters out dust, allergens, and pollutants, ensuring that the indoor air quality remains fresh and clean. The inclusion of a humidification function also helps to maintain an optimal humidity level, further enhancing the comfort of the space.

Ease of use is another highlight of these models. With a user-friendly remote control and an intuitive interface, adjusting settings and monitoring performance is effortless. The programmable timer function allows users to set specific operating times, ensuring that the system runs only when needed.

In terms of design, the RAS-35YH6 and RAC-35YH6 feature a sleek and modern aesthetic that seamlessly complements various interior designs. The compact size allows for flexible installation options, making it suitable for a range of room layouts.

Lastly, the durability and reliability of Hitachi products are well recognized. These models are designed for long-term performance, incorporating robust components that can withstand diverse weather conditions.

In summary, the Hitachi RAS-35YH6 and RAC-35YH6 offer a perfect combination of efficiency, technology, and user convenience, making them an excellent choice for those seeking a reliable air conditioning solution.