| Product Specifications | |
Specifications |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
Capacities |
|
|
|
|
|
|
Nominal Cooling (BTU/h) | 33,000 | 35,000 | 48,000 | 53,000 | 57,000 |
|
EER¹ | 9.0 | 9.0 | 9.0 | 9.0 | 9.0 |
|
Nominal Heating (BTU/h) | 32,000 | 32,000 | 48,000 | 54,000 | 61,000 |
|
Decibels | 78 | 78 | 78 | 80 | 80 |
|
|
|
|
|
|
|
|
Compressor |
|
|
|
|
|
|
RLA | 15.9 | 5.7 | 8.2 | 9.0 | 10.9 |
|
LRA | 104 | 42 | 64 | 74 | 101 |
|
Volts |
| |||||
|
|
|
|
|
|
|
Condenser Fan Motor |
|
|
|
|
|
|
Horsepower | ¼ | ⅓ | ⅓ | ⅓ | ⅓ | |
FLA | 0.9 | 1.2 | 1.2 | 1.2 | 1.2 |
|
Volts | 380 | 380 | 380 | 380 |
| |
|
|
|
|
|
|
|
Refrigeration System |
|
|
|
|
|
|
Liquid Valve Size (“O.D.) | ⅜" | ⅜" | ⅜" | ⅜" | ⅜" | |
Suction Valve Size (“O.D.) | ¾" | ¾" | ⅞" | ⅞" | ⅞" | |
Valve Type | Sweat | Sweat | Sweat | Sweat | Sweat | |
Refrigerant Charge (oz.) | 110 | 110 | 137 | 138 | 167 |
|
Shipped with Orifice Size (in.) | 0.073 | 0.073 | 0.084 | 0.093 | 0.093 |
|
|
|
|
|
|
|
|
Condenser Fan / Coil |
|
|
|
|
|
|
Horsepower - RPM | ¼ - 950 | ⅓ - 1,075 | ⅓ - 1,075 | ⅓ - 1,075 | ⅓ - 1,075 | |
Fan Diameter/ # Fan Blades | 20/3 | 20/3 | 22/3 | 22/3 | 22/3 |
|
Outdoor Nominal CFM | 1,800 | 1,800 | 2,600 | 2,600 | 3,200 |
|
Face Area (ft²) | 14.58 | 14.58 | 17 | 17 | 17 |
|
Rows Deep/ Fins per Inch | 1/19 | 1/19 | 1/19 | 1/22 | 1/22 |
|
Fin Type | Ripple | Ripple | Ripple | Ripple | Ripple | |
Coil No. of Tubes | 24 | 24 | 24 | 36 | 36 |
|
Coil Tube Diameter (in.) | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 |
|
|
|
|
|
|
|
|
Electrical Data |
|
|
|
|
|
|
| ||||||
Min. Circuit Ampacity² | 20.8 | 8.3 | 11.5 | 12.5 | 14.8 |
|
Max. Overcurrent Protection | 35 | 15 | 15 | 20 | 25 |
|
(amps)³ |
| |||||
|
|
|
|
|
| |
Min / Max Volts | 198/264 | 342/456 | 342/456 | 342/456 | 342/456 |
|
Power Supply Conduit Size | ½ or ¾ | ½ or ¾ | ½ or ¾ | ½ or ¾ | ½ or ¾ | |
|
|
|
|
|
|
|
Ship Weight | 206 [94] | 206 [94] | 216 [98] | 248 [113] | 249 [113] |
|
|
|
|
|
|
|
|
¹ Energy Efficiency Ratio
²Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ³ Must use
Note: Always check the S&R plate for electrical data on the unit being installed.
www.goodmanmfg.com | 3 |