Bard PA13241-A Wiring Main Power, Wiring 24V LOW Voltage Control Circuit, Transformer Taps

Page 13

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required. The heater rating plate located adjacent to the basic unit rating plate will show the appropriate circuit ampacity fuse size, etc. (Also see “Electrical Specifications” on pages 5 & 7.) All models are suitable for connection with copper wire only. These instructions must be adhered to. Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material.

The electrical specifications list fuse and wire sizes (75°F copper) for all models including the most commonly used heater sizes.

The unit rating plate lists a “Maximum Time Delay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor.

WIRING – 24V LOW VOLTAGE CONTROL CIRCUIT

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 6.

TABLE 6

THERMOSTAT WIRE SIZE

 

 

 

Maximum

 

 

 

Distance

Transformer VA

FLA

Wire Gauge

In Feet

 

 

 

 

 

 

20

45

 

 

18

60

55

2.3

16

100

 

 

14

160

 

 

12

250

 

 

 

 

TRANSFORMER TAPS

230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

THERMOSTATS

See specific wiring information for the different models, heater KWs, and voltages on unit and heating wiring diagrams.

 

TABLE 7

 

WALL THERMOSTATS

 

 

Thermostat

Predominant Features

 

 

8403-057

1 stage Cool; 1 stage Heat

heat-off-cool Fan: on-auto

(TH3110D1040)

Electronic Non-Programmable

 

 

8403-058

2 stage Cool; 2 stage Heat

Electronic Non-Programmable

(TH5220D1151)

 

Auto or Manual changeover

 

3 stage Cool; 3 stage Heat

8403-060

Programmable/Non-Programmable Electronic

(1120-445)

HP or Conventional

 

Auto or Manual changeover

 

 

IMPORTANT NOTE: Only the thermostats as shown above will work with this equipment. The thermostats and correct operation can be assured only by proper selection and application of these parts.

Manual

2100-467D

Page

13 of 25

Image 13
Contents Installation Instructions Single Package AIR Conditioners Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Instructions Field Installed Heater Packages OptionalShipping Damage GeneralHz Circuit a Electrical SpecificationsVolts Optional Field Installed Electric Heater Table Dimensions of Units Unit Dimension ChartTypical Installations InstallationLocation GeneralSlab Mounting AT Ground Level Airflow and Service Access ClearancesAS Required Elevated Mounting PlatformAIR Filters Condensate Drain TrapFilter Requirements & Sizes Condensate Drain TrapWiring 24V LOW Voltage Control Circuit Wiring Main PowerTransformer Taps ThermostatsLOW Voltage Wiring Low Voltage WiringStart UP Safety PracticesTopping OFF System Charge Start UP NotesStart UP and Operation Three Phase Scroll Compressor Start UP InformationSequence of Operation Indoor Blower MotorLOW Ambient Control AdjustmentsService Hints Service and TroubleshootingPressure Service Ports FAN Blade SettingsReturn Air Pressure Pressure Table115 120 Model563 120 125 ModelSuction and Discharge Tube Brazing Brazing DiagramTroubleshooting GE ECM 2.3 Motors Troubleshooting GE ECM2.3 Motors CONT’D Troubleshooting GE X13-SERIES ECM2.3 Motors Troubleshooting GE X13-SERIES ECM2.3 Motors CONT’D

PA13361-B, PA13301-A, PA13241-A, PA13361-A specifications

The Bard PA13361-B, PA13361-A, PA13241-A, and PA13301-A are high-efficiency packaged air conditioning units known for their exceptional performance in residential and commercial settings. These models are designed to provide effective cooling solutions while maximizing energy efficiency and comfort.

One of the standout features of these models is their robust construction, made to withstand varying environmental conditions. The units are engineered with corrosion-resistant materials, making them ideal for both indoor and outdoor applications. This durability ensures that they can operate effectively in diverse climates, providing consistent cooling performance year-round.

The PA13361-B and PA13361-A models are equipped with advanced thermostatic control systems that allow for precise temperature adjustments. This technology enhances user comfort and contributes to energy savings by ensuring the system operates only when needed. Users can easily manage their indoor environment through intuitive controls, making it straightforward to tailor the cooling output to their preferences.

In terms of energy efficiency, these Bard units are designed to operate at low energy consumption levels while delivering powerful cooling capabilities. The integration of high-efficiency compressors and refrigerants contributes substantially to reducing energy costs, making these models an environmentally friendly choice for consumers. With a high Seasonal Energy Efficiency Ratio (SEER), these air conditioning units not only comply with but often exceed industry standards.

The PA13241-A and PA13301-A models introduce enhanced airflow technology, which allows for better air distribution throughout the space. This feature ensures that every corner of the room receives adequate cooling, eliminating hot spots and ensuring comfort for occupants.

Furthermore, the simplicity of installation and maintenance adds to the appeal of these models. Bard units are designed with serviceability in mind, allowing technicians to perform routine maintenance with ease. This accessibility can lead to reduced downtime and enhanced longevity of the equipment.

In summary, the Bard PA13361-B, PA13361-A, PA13241-A, and PA13301-A packaged air conditioning units are robust, efficient, and user-friendly systems. Their advanced features, energy-efficient operation, and durable construction make them a top choice for those seeking reliable cooling solutions in various settings. Whether for residential or commercial use, these models offer performance and comfort that users can depend on.