Bard MC Series Controller Manual and Setup Guide for MC4000

Page 15

USER PAGE

1.The designated Admin person can assign up to 9 additional users and set-up as Admin, Write or Read authority.

2.User Name and password must be assigned, each must be at least 3 characters long, and are case sensitive.

3.Only “Admin” can add, change or delete users and has access to all controller pages.

4.“Write” can make changes to the controller settings and operating characteristics, and has access to only Log In, System Status, Setpoints, and Log Out pages.

5.“Read” can only view Status and Setpoints pages and cannot make any changes.

SYSTEM STATUS PAGE

1.This page shows the overall HVAC status of:

a.Active cooling or heating stages or dehumidification mode (requires humidity sensor)

b.Active controller outputs (blower, cooling Stage 1 or 2, heating) to each air conditioner

c.Which unit is the Lead unit

d.Power loss or refrigerant lock-out for each air conditioner

e.If economizers are used if on or off (Note: older style EIFM economizers require a simple relay kit for this feature to work, Bard Part Number 8620-221)

2.General status of:

a.Dehumidification Active or not

b.Backup Generator Active or not (if tied to generator run controls to inhibit lag unit operation during generator run)

c.Alarm board connected or not

d.Controller system Locked or Unlocked

e.Comfort mode Active or not

3.Temperatures:

a.Average temperature (if more than ones sensor used, if not will read same as Local sensor)

b.Local sensor at controller

c.Remote 1 or Remote 2 if connected

4.General Alarm Status:

a.Fire/Smoke, Clear or Alarm

b.Low Temp, Clear or Alarm

c.High Temp #1, Clear or Alarm

d.High Temp #2, Clear or Alarm

e.Controller Failure, Clear or Alarm

SETPOINTS PAGE (Note: “Read” level authority can view this screen but cannot make any changes. “Admin” and “Write” authority can make changes)

1.General Setpoints

a.On initial installation and start-up all selectable characteristics are set to factory default settings.

b.Each of these points has a drop-down menu for ease of use.

2.Alarm Board Setpoints

a.Low temperature alarm setpoint

b.High temperature alarm #1 setpoint

c.High temperature alarm #2 setpoint

3.System Overrides

a.System 1 Cooling Override

b.System 1 Heating Override

c.System 2 Cooling Override

d.System 2 Heating Override

e.Turn Power On to the System (Note: Cannot remotely turn the controller system Off)

f.Lock/Unlock Controller

g.Advance Lead to Lag Unit

h.Comfort Mode

i.Restore System Defaults

j.Reset Controller. There are built-in routines to prevent the controller system from getting “locked up”, but this also allows a manual remote reset as a backup before having a service call to the site.

LOG OUT BUTTON

1.Clicking this button will automatically log you off the controller remote access.

2.To log back in will require entering assigned IP address into your browser and entering valid User Name and Password.

CONNECT TO NETWORK

CB4000 COMMUNICATION BOARD

RESET BUTTON TO RETURN TO DEFAULT CONTROLLER SETTINGS

￿

1.After initial set-up using laptop computer, disconnect computer cable from the Ethernet port and connect the CAT 5 or CAT 6 network cable.

2.Remote access is now available using the assigned IP address and valid User Name and Password (case sensitive).

￿

￿

PHONE JACK CONNECTION TO MAIN CONTROLLER BOARD

￿

 

ETHERNET PORT

IP DEFAULT ADDRESS RESET

Manual

2100-563C

Page

15 of 40

Image 15
Contents Installation Instructions & Replacement Parts List Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsController Certifications Shipping DamageGeneral Theory of OperationMounting the Controller SPECIFICATIONS/FEATURES for Basic ControllerTemperature Sensors Temperature Sensor LogicLocated on Main Controller Board SPECIFICATIONS/FEATURES for Alarm BoardsAdvance Swap LEAD/LAG Unit Feature LOW Voltage Field WiringController POWER-UP Staging Delay PeriodsGeneral Programming Overview Controller Programmable Features and Default SettingsHumidity Control Option Manual Manual Manual Heating Sequence of Operation CB4000 Communication Board Specifications for Optional Remote Communication BoardCB4000 Communication Board Backup DC Power Connection Controller WiringSecurity Locking Feature Generator RUN FeatureHOOK-UP Diagram Selection Table Reference Shown Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Controllerconnections Heat Pumps no Economizer Manual Emergency Ventilation Sequence Alarm Wiring2ND Stage Cooling Alarm Refrigerant Pressure AlarmsManual Manual Programming Instructions MC4000Series MIS-2954 Parts List This page intentionally left blank This page intentionally left blank This page intentionally left blank

MC4000 specifications

The Bard MC4000 is a state-of-the-art multi-channel wireless communication system, designed primarily for the needs of professionals in various industries. Known for its robust performance and exceptional reliability, the MC4000 is an ideal solution for events, concerts, large venues, and critical communications in diverse environments.

One of the main features of the MC4000 is its multi-channel capability, allowing it to support a range of frequencies simultaneously. This feature prevents interference from other devices and ensures clear, uninterrupted communication. The system supports multiple transmitters and receivers, enabling large teams to communicate effectively without the need for cumbersome cables.

The Bard MC4000 utilizes advanced digital signal processing technology, offering enhanced audio quality. This technology minimizes background noise and provides crisp, clear audio transmission even in challenging environments. The system also features automatic frequency selection, which scans for the best available frequencies, ensuring optimum performance at all times.

The MC4000 is designed with user-friendliness in mind, featuring an intuitive interface that allows for quick setup and operation. The clearly labeled controls and bright display make it easy for users to monitor audio levels and battery life, ensuring seamless operation during critical moments. Furthermore, the system is compatible with a variety of microphones and headsets, providing users with the flexibility to choose the equipment that best suits their needs.

Durability is another key characteristic of the Bard MC4000. Its rugged construction can withstand demanding usage in various environments, from outdoor events to industrial applications. The system also includes weather-resistant features, making it suitable for operations in adverse weather conditions without compromising functionality.

In terms of connectivity, the MC4000 supports both wired and wireless options. This versatility enables users to switch between modes depending on their needs or specific venue requirements. The built-in rechargeable battery ensures extended usage, eliminating the hassle of frequent battery replacements.

Overall, the Bard MC4000 is a versatile, high-performance wireless communication system that meets the demanding needs of modern professionals. Its combination of multi-channel support, advanced audio technology, and user-friendly design makes it an essential tool for anyone needing reliable communication in their operations. With the MC4000, users can expect clarity, durability, and performance that can keep pace with their dynamic work environments.