Bard Comprehensive Guide to Lead Lag Controllers and MC Series Functionality

Page 13

5.2-Stage Compressor Units with Newer ECONWMT Economizers (See Note A)

1st stage cooling set point is the setting (SP) input into the controller. Factory default is 77F (25C). On a call for cooling the blower of the lead unit will come on immediately (if not already on – See Blower Operation), and the Stage 1 LED will blink for 10-seconds before going solid, at which time the lead unit Y1 cooling output turns on. If the outdoor temperature and humidity conditions are below the set point of the economizer control the lead unit economizer will operate instead of the compressor. If outdoor conditions are not acceptable for free cooling the compressor will automatically operate on compressor Stage 1 partial capacity instead of the economizer.

2nd cooling set point is 4F (default setting, user selectable 2-6F) warmer than Stage 1. On a call for 2nd stage cooling the lead unit Y2 cooling output turns on. If the outdoor temperature and humidity conditions are below the set point of the economizer control the lead unit economizer will continue to operate, and the compressor will operate on compressor Stage 1 partial capacity. If the compressor is already operating on Stage 1 partial capacity because outside free cooling range the compressor will switch to compressor Stage 2 full capacity.

3rd cooling set point is 2F (default setting, user selectable 2-3F) warmer than Stage 2. On a call for 3rd Stage cooling the blower of the lag unit will come on immediately (if not already on – See Blower Operation), and the Stage 3 LED will blink for 10-seconds before going solid, at which time the lag unit Y1 cooling output turns on. The lag unit economizer will operate if the outdoor temperature and humidity conditions are below the set point of the economizer control. If outdoor conditions are not acceptable for free cooling the compressor will automatically operate on compressor Stage 1 partial capacity instead of the economizer.

4th cooling set point is 2F (default setting, user selectable 2-3F) warmer than Stage 3. On a call for 4th Stage cooling the lag unit Y2 cooling output turns on activating the compressor. If the outdoor temperature and humidity conditions are below the set point of the economizer control the lag unit economizer will continue to operate, and the compressor will operate on compressor Stage 2 full capacity. If the compressor is already operating on Stage 1 partial capacity because outside free cooling range the compressor will switch to compressor Stage 2 full capacity.

Note A: Economizers in ECONWMT-Series are available with either “T” temperature only outdoor sensor or “E” enthalpy (temperature and humidity) outdoor sensor. The “T” versions will have a fixed (but selectable) outdoor temperature decision whereas on the “E” versions the outdoor temperature decision will float based on outdoor humidity and the selected Enthalpy curve in the economizer control module.

HEATING SEQUENCE OF OPERATION

Note: All heating sequences for air conditioners with electric heat or heat pumps will automatically operate in Alternating Lead/Lag/Lead/Lag sequence even if controller is set to Non-Alternating for cooling with or without economizers.

1.Air Conditioners with Electric Heat

1st stage heating set point is the dead-band (db) below the 1st stage cooling set point (the SP entered into the program). The dead-band is adjustable from 2-40F, and factory default is 17F.

2nd stage heating set point will operate at same inter- stage differential as set for cooling mode.

2.Heat Pumps with Electric Heat

When the MC4000 controller is configured for heat pump installations the 2nd-stage (Y2) outputs for both units 1 and 2 are redefined and used to control the reversing valves, and which are energized in heating mode.

1st stage heating set point is the dead-band (db) below the 1st stage cooling set point (the SP entered into the program). The dead-band is adjustable from 2-40F, and factory default is 17F.

1st-stage heating consists of lead unit blower coming on (if not already on – See Blower Operation), and reversing valve being energized. The Stage 1 heating LED will blink for 10-seconds, at which time the compressor turns on.

2nd heating set point is 4F (default setting, user selectable 2-6F) cooler than Stage 1. On a call for 2nd Stage heating the blower of the lag unit is turned on (if not already on

See Blower Operation), the reversing valve is energized, and the Stage 2 LED will blink for 10- seconds before going solid, at which time the compressor will start.

3rd-stage heating will be the electric heater, if so equipped, in the lead unit. Stage 3 heating LED comes on solid with no blinking.

4th-stage heating will be the electric heater, if so equipped, in the lag unit. Stage 4 heating LED comes on solid with no blinking.

Manual

2100-563C

Page

13 of 40

Image 13
Contents Installation Instructions & Replacement Parts List Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Shipping DamageTheory of Operation Controller CertificationsTemperature Sensors SPECIFICATIONS/FEATURES for Basic ControllerTemperature Sensor Logic Mounting the ControllerLocated on Main Controller Board SPECIFICATIONS/FEATURES for Alarm BoardsController POWER-UP LOW Voltage Field WiringStaging Delay Periods Advance Swap LEAD/LAG Unit FeatureGeneral Programming Overview Controller Programmable Features and Default SettingsHumidity Control Option Manual Manual Manual Heating Sequence of Operation CB4000 Communication Board Specifications for Optional Remote Communication BoardCB4000 Communication Board Security Locking Feature Controller WiringGenerator RUN Feature Backup DC Power ConnectionHOOK-UP Diagram Selection Table Reference Shown Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Manual Controllerconnections Heat Pumps no Economizer Manual 2ND Stage Cooling Alarm Alarm WiringRefrigerant Pressure Alarms Emergency Ventilation SequenceManual Manual Programming Instructions MC4000Series MIS-2954 Parts List This page intentionally left blank This page intentionally left blank This page intentionally left blank

MC4000 specifications

The Bard MC4000 is a state-of-the-art multi-channel wireless communication system, designed primarily for the needs of professionals in various industries. Known for its robust performance and exceptional reliability, the MC4000 is an ideal solution for events, concerts, large venues, and critical communications in diverse environments.

One of the main features of the MC4000 is its multi-channel capability, allowing it to support a range of frequencies simultaneously. This feature prevents interference from other devices and ensures clear, uninterrupted communication. The system supports multiple transmitters and receivers, enabling large teams to communicate effectively without the need for cumbersome cables.

The Bard MC4000 utilizes advanced digital signal processing technology, offering enhanced audio quality. This technology minimizes background noise and provides crisp, clear audio transmission even in challenging environments. The system also features automatic frequency selection, which scans for the best available frequencies, ensuring optimum performance at all times.

The MC4000 is designed with user-friendliness in mind, featuring an intuitive interface that allows for quick setup and operation. The clearly labeled controls and bright display make it easy for users to monitor audio levels and battery life, ensuring seamless operation during critical moments. Furthermore, the system is compatible with a variety of microphones and headsets, providing users with the flexibility to choose the equipment that best suits their needs.

Durability is another key characteristic of the Bard MC4000. Its rugged construction can withstand demanding usage in various environments, from outdoor events to industrial applications. The system also includes weather-resistant features, making it suitable for operations in adverse weather conditions without compromising functionality.

In terms of connectivity, the MC4000 supports both wired and wireless options. This versatility enables users to switch between modes depending on their needs or specific venue requirements. The built-in rechargeable battery ensures extended usage, eliminating the hassle of frequent battery replacements.

Overall, the Bard MC4000 is a versatile, high-performance wireless communication system that meets the demanding needs of modern professionals. Its combination of multi-channel support, advanced audio technology, and user-friendly design makes it an essential tool for anyone needing reliable communication in their operations. With the MC4000, users can expect clarity, durability, and performance that can keep pace with their dynamic work environments.