Bard WL602N, WL4822 Wiring Main Power, Wiring LOW Voltage Wiring, TAP Range, Thermostat Wire Size

Page 15

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring muse conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab locate in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut a padlock may be placed through the hole in the tab preventing entry.

See “Start Up” section for important information on three phase scroll compressor start ups.

WIRING – LOW VOLTAGE WIRING

230 / 208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 9:

TABLE 3

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

 

 

VA

FLA

Wire Gauge

In Feet

 

 

 

 

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 guage

160

 

 

12 guage

250

 

 

 

 

TABLE 4

WALL THERMOSTAT AND SUBBASE COMBINATIONS

Thermostat

Subbase

Predominate Features

 

 

 

8403-002

8404-003

1 stage heat, 1 stage cool

T87F3111

Q539A1220

System: heat-off-cool Fan: auto-on

 

 

 

8403-041

---

1 stage heat, 1 stage cool

T8034C

 

System: heat-off-cool Fan: auto-on

 

 

 

8403-019

8404-012

1 stage cool, 2 stage heat

T874C1760

Q674A1001

System: heat-auto-cool Fan: auto-on

 

 

 

8403-021

8404-012

2 stage cool, 2 stage heat

T874D1934

Q674A1001

System: heat-auto-cool Fan: auto-on

 

 

 

8403-035

---

2 stage cool, 2 stage heat

1F95-80

 

Electronic 7 day programming

 

 

 

8403-043

---

1 stage heat, 1 stage cool

CM-200

System: heat-off-cool Fan: auto-on

 

 

 

 

Manual 2100-351 Page 13

Image 15
Contents WL4822 WL4823 WL6022 WL6023 WL602N Contents Getting Other Information and Publications Wall Mount General Information AIR Conditioning Wall Mount Model NomenclatureElectric Heat Table WL602N, WL6023, WL4823 only Unit DimensionsWL6022, WL4822 only Single Circuit Dual Circuit Electrical SpecificationsDuct Work Shipping DamageGeneral Condensate DrainWL4822 and WL6022 only Installation InstructionsWall Mounting Information Mounting the UnitMounting Instructions MIS-1444 Electric Heat Clearance See Mounting Instructions Wall Mounting InstructionsCommon Wall Mounting Installations TAP Range Wiring Main PowerWiring LOW Voltage Wiring Thermostat Wire SizeUnit 24V Terminal Board Start UP Pressure Service Ports Phase MonitorTroubleshooting FAN Blade Setting Dimensions Refrigerant ChargeRemoval of FAN Shroud Pressure Table Cooling Maximum ESP of Operation Electric Heat onlyOptional Accessories

WL6022, WL6023, WL4823, WL4822, WL602N specifications

Bard's WL6022, WL4822, WL4823, WL602N, and WL6023 represent a series of advanced heating and cooling units tailored for both residential and commercial applications. Each model embodies Bard's commitment to innovation, efficiency, and user-friendly operation, providing sustainable climate control solutions.

The WL6022 stands out with its powerful performance, designed for large spaces needing effective air distribution. With a robust heat capacity, this model can effectively maintain comfortable indoor temperatures even in extreme weather conditions. It incorporates advanced energy-saving technologies, such as a high-efficiency compressor, allowing users to keep operating costs low while ensuring reliable heating and cooling.

The WL4822 and WL4823 are more compact options, ideal for smaller residential or commercial areas. These models feature dual-speed fans, enhancing their efficiency while minimizing noise levels. The WL4823 comes equipped with additional smart control options, enabling users to customize their settings for optimized comfort. Both models benefit from innovative insulation techniques that reduce energy loss, making them environmentally friendly choices.

The WL602N model is a notable addition, designed with energy efficiency at its core. It utilizes a microprocessor-based control system that allows precise temperature management, further optimizing energy usage. Additionally, the WL602N supports advanced diagnostics, making maintenance easier and reducing downtime.

Finally, the WL6023 model is engineered for versatility, accommodating various installation demands. Its flexible design allows it to be used in diverse environments, ensuring it meets the cooling and heating needs of any space. The WL6023 is recognized for its airflow control features, which ensure even temperature distribution throughout the room.

In conclusion, Bard's WL6022, WL4822, WL4822, WL602N, and WL6023 models exemplify modern engineering in climate control technology. Their blend of efficiency, performance, and smart features positions them as reliable choices for effective heating and cooling. Whether used in homes or industrial settings, these models are designed to deliver superior comfort while minimizing energy consumption. Bard continues to lead the way in crafting innovative climate solutions, ensuring customer satisfaction and environmental responsibility.