START UP

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil with a dish washing detergent.

CRANKCASE HEATERS

These units are not provided with crankcase heat. These units utilize scroll compressors which do not require crankcase heat in this application.

HIGH PRESSURE SWITCH

The models are supplied with a remote reset high pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR START UP INFORMATION

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.

However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as, substantially reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse rotation for several minutes, the compressor’s internal protector will trip.

All three phase ZR3 compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction.

The direction of rotation of the compressor may be changed by reversing any two line connections to the unit.

SERVICE HINTS

1.Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life as well as increasing operating costs.

2.Switching to heating cycle at 75° F or higher outside temperature may cause a nuisance trip of the remote reset high pressure switch. Turn thermostat off then on to reset the high pressure switch.

3.Check all power fuses or circuit breakers to be sure they are the correct rating.

4.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase of constant air circulation. On all 230 volt units there is a one minute off delay on the blower motor. 460 volt models do not have an off delay.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on the models covered by this manual. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10% of the delay on break setting. When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired.

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Manual 2100-351 Page 15

Image 17
Contents WL4822 WL4823 WL6022 WL6023 WL602N Contents Getting Other Information and Publications Electric Heat Table Wall Mount General InformationAIR Conditioning Wall Mount Model Nomenclature WL602N, WL6023, WL4823 only Unit DimensionsWL6022, WL4822 only Single Circuit Dual Circuit Electrical SpecificationsGeneral Shipping DamageCondensate Drain Duct WorkWall Mounting Information Installation InstructionsMounting the Unit WL4822 and WL6022 onlyMounting Instructions MIS-1444 Electric Heat Clearance See Mounting Instructions Wall Mounting InstructionsCommon Wall Mounting Installations Wiring LOW Voltage Wiring Wiring Main PowerThermostat Wire Size TAP RangeUnit 24V Terminal Board Start UP Pressure Service Ports Phase MonitorRemoval of FAN Shroud TroubleshootingFAN Blade Setting Dimensions Refrigerant Charge Pressure Table Cooling Maximum ESP of Operation Electric Heat onlyOptional Accessories

WL6022, WL6023, WL4823, WL4822, WL602N specifications

Bard's WL6022, WL4822, WL4823, WL602N, and WL6023 represent a series of advanced heating and cooling units tailored for both residential and commercial applications. Each model embodies Bard's commitment to innovation, efficiency, and user-friendly operation, providing sustainable climate control solutions.

The WL6022 stands out with its powerful performance, designed for large spaces needing effective air distribution. With a robust heat capacity, this model can effectively maintain comfortable indoor temperatures even in extreme weather conditions. It incorporates advanced energy-saving technologies, such as a high-efficiency compressor, allowing users to keep operating costs low while ensuring reliable heating and cooling.

The WL4822 and WL4823 are more compact options, ideal for smaller residential or commercial areas. These models feature dual-speed fans, enhancing their efficiency while minimizing noise levels. The WL4823 comes equipped with additional smart control options, enabling users to customize their settings for optimized comfort. Both models benefit from innovative insulation techniques that reduce energy loss, making them environmentally friendly choices.

The WL602N model is a notable addition, designed with energy efficiency at its core. It utilizes a microprocessor-based control system that allows precise temperature management, further optimizing energy usage. Additionally, the WL602N supports advanced diagnostics, making maintenance easier and reducing downtime.

Finally, the WL6023 model is engineered for versatility, accommodating various installation demands. Its flexible design allows it to be used in diverse environments, ensuring it meets the cooling and heating needs of any space. The WL6023 is recognized for its airflow control features, which ensure even temperature distribution throughout the room.

In conclusion, Bard's WL6022, WL4822, WL4822, WL602N, and WL6023 models exemplify modern engineering in climate control technology. Their blend of efficiency, performance, and smart features positions them as reliable choices for effective heating and cooling. Whether used in homes or industrial settings, these models are designed to deliver superior comfort while minimizing energy consumption. Bard continues to lead the way in crafting innovative climate solutions, ensuring customer satisfaction and environmental responsibility.