Bard WL702-A, WL701-C Installation Instructions, Wall Mounting Information, Mounting the Unit

Page 8

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1.Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3.

2.On wood-frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. See Figures 5 and 6.

WARNING

Fire hazard can result if 1/4 inch clearance to combustible materials for supply air duct is not maintained. See Figure 3.

3.Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installing unit. See Figure 5.

MOUNTING THE UNIT

1.These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation.

2.The unit itself is suitable for “0” inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material. If a combustible wall, use a minimum of 30-1/2" x 10-1/2" dimensions for sizing. However, it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material. The supply air opening would then be 32" x 12". See Figures 3, 4 and 5 for details.

WARNING

Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire.

3.Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 5.

4.Mount bottom mounting bracket.

5.Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.

6.Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.

7.Secure rain flashing to wall and caulk across entire length of top. See Figure 3.

8.For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.

9.On side by side installations, maintain a minimum of 20 inches clearance on left side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.

TYPICAL INSTALLATIONS

See Figure 6 for common ways to install the wall-mount unit.

WIRING — MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR" type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75ºC copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR" type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

Manual 2100-426 Page 6

Image 8
Contents Wall Mounted Packaged Bryan, OhioContents Getting Other Information and Publications For More INFORMATION, Contact These PublishersAIR Conditioner Wall Mount Model Nomenclature Electrical SpecificationsWall Mount General Information Unit Dimensions Electric Heat TableDuct Work Shipping DamageGeneral Blower Damper Assembly FiltersFresh AIR Intake Condensate DrainInstallation Instructions Typical InstallationsWiring Main Power Wall Mounting InformationMounting Instructions Wiring LOW Voltage WiringOperating Voltage Range Electric Heat Clearance Thermostat Wire SizeWall Thermostat and Subbase Combinations WALL-MOUNTING Instructions Common WALL-MOUNTING Installations LOW Voltage Wiring Important Installer Note High Pressure SwitchThree Phase Scroll Compressor Start UP Information Start UPCompressor Control Module Service HintsSequence of Operation Phase Monitor Pressure Service PortsAdjustable Delay on Make and Delay on Break Timer Typical Settings for Dual Unit InstallationTroubleshooting FAN Blade Setting DimensionsRemoval of FAN Shroud Refrigerant ChargeCooling Pressure ALL Temperatures F Optional AccessoriesPage

WL702-A, WL701-B, WL701-C specifications

The Bard WL702-A, WL701-B, and WL701-C are advanced heating and cooling units designed for efficient and reliable climate control in various applications. These models showcase Bard's commitment to innovation, energy efficiency, and user-friendly features, making them ideal for residential, commercial, and industrial use.

The Bard WL702-A model is a versatile unit, emphasizing energy efficiency with a high Seasonal Energy Efficiency Ratio (SEER). This model employs a variable speed compressor, allowing it to adjust its output based on the current outdoor and indoor temperatures. This flexibility not only enhances comfort but also significantly reduces energy consumption. Additionally, the WL702-A is designed with a robust cabinet construction, ensuring longevity and resistance to harsh weather conditions.

On the other hand, the Bard WL701-B is engineered with a focus on providing reliable heating solutions. It features advanced heat pump technology, utilizing environmentally friendly refrigerants that comply with current environmental standards. The WL701-B is equipped with an integrated defrost control, which minimizes frost buildup and maintains optimal performance in colder climates. Its compact design allows for convenient installation in tight spaces, making it a perfect choice for urban settings.

The Bard WL701-C model takes comfort to the next level with its state-of-the-art smart controls. These controls allow users to set schedules, monitor usage, and adjust settings remotely via a smartphone or tablet application. This model also includes zoning capabilities, enabling customized temperature settings in different areas of a building, leading to enhanced comfort and efficiency. Furthermore, the WL701-C’s quiet operation ensures that occupants can enjoy a peaceful environment, free from disruptive noise.

In summary, the Bard WL702-A, WL701-B, and WL701-C units each bring distinct features and technologies to the table. From the energy-efficient variable speed compressor of the WL702-A to the heat pump technology of the WL701-B and the smart control capabilities of the WL701-C, these models reflect Bard's dedication to providing high-quality climate control solutions that cater to a variety of needs. With their combination of performance, reliability, and ease of use, these units stand out as some of the best options available in the market for effective heating and cooling.