Bard WA4823, WA6023, WA602N, WA6022, WA4822 Phase Monitor, Pressure Service Ports

Page 18

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout Sequence

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute

(30 seconds)

DOB = 123 second DOM

1.0 minute

(60 seconds)

DOB = 126 second DOM

2.0minute (120 seconds) DOB = 132 second DOM

3.0minute (180 seconds) DOB = 138 second DOM

4.0minute (240 seconds) DOB = 144 second DOM

5.0minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds.

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds.

PHASE MONITOR

All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.

Manual 2100-348 Page 16

Image 18
Contents WA4822 WA4823 WA6022 WA6023 WA602N Contents Getting Other Information and Publications AIR Conditioning Wall Mount Model Nomenclature Wall Mount General InformationX a Electric Heat TableUnit Dimensions WA602N, WA6023, WA4823 onlyWA6022, WA4822 only Electrical Specifications Single Circuit Dual CircuitCondensate Drain Shipping DamageGeneral Duct WorkMounting the Unit Installation InstructionsWall Mounting Information WA4822 and WA6022 onlyMounting Instructions MIS-1444 Electric Heat Clearance Wall Mounting Instructions See Mounting InstructionsCommon Wall Mounting Installations Thermostat Wire Size Wiring Main PowerWiring LOW Voltage Wiring TAP RangeUnit 24V Terminal Board Start UP Phase Monitor Pressure Service PortsTroubleshooting FAN Blade Setting Dimensions Refrigerant ChargeRemoval of FAN Shroud Maximum ESP of Operation Electric Heat only Pressure Table CoolingOptional Accessories

WA4822, WA4823, WA6022, WA602N, WA6023 specifications

Bard is a renowned name in the HVAC industry, and their models WA4823, WA4822, WA602N, WA6022, and WA6023 reflect a commitment to providing efficient and reliable heating and cooling solutions. Each model is designed with specific features and technologies that cater to varying needs, making them suitable for residential and commercial applications.

The WA4823 and WA4822 are part of Bard's high-efficiency wall-mounted air conditioning units, engineered to maximize comfort while minimizing energy consumption. The WA4823 offers a cooling capacity of 23,000 BTUs, making it ideal for larger spaces. Its unique design includes a high-efficiency scroll compressor and a multi-speed fan that adjusts airflow according to the needs of the environment. This model also features a built-in thermostat and an easy-access filter, ensuring optimal air quality and minimal maintenance.

The WA4822, slightly smaller with a cooling capacity of 22,000 BTUs, shares many features with the WA4823. Both units are equipped with a robust insulation system that significantly reduces sound levels, providing a quiet and comfortable indoor environment. Additionally, they utilize eco-friendly refrigerants, contributing to lower greenhouse gas emissions.

The WA602N, WA6022, and WA6023 models are designed for larger applications, offering advanced cooling solutions. The WA602N is particularly noteworthy for its patented technology that enhances energy efficiency while delivering powerful cooling performance. With a cooling capacity of 6,000 BTUs, it features a durable exterior designed to withstand outdoor elements, making it suitable for external installations.

The WA6022 and WA6023 offer slightly higher capacities, catering to larger spaces with demands for cooling. Both models come equipped with advanced climate control technologies, including programmable thermostats and energy-saving modes that adjust the system's operation based on occupancy. These features not only optimize comfort but also provide significant savings on energy bills.

In summary, Bard's WA4823, WA4822, WA602N, WA6022, and WA6023 models stand out for their efficiency, advanced technology, and user-friendly features. Their design emphasizes quiet operation, eco-friendly refrigerants, and robust construction, making them reliable choices for both residential and commercial environments. With a strong focus on energy conservation and comfort, Bard's units are shaping the future of HVAC solutions.