ERROR CONTENTS
Model : MW18Y3F / MR18Y3F
* Detailed Trouble Display (secondary level) can be indicated by pressing Test Operation button.
Trouble Display (primary) | Detailed Trouble Display (by Test Button) |
| Detailed Error Item | ||||
Error | Operation | Timer | Error | Operation | Timer |
| |
|
| ||||||
Serial signal | Normal | 1 sec | Serial reverse signal error | 0.1sec | 0.5sec |
| When a signal is not read continuously for 10 secs |
error |
| blinking | at operation start up | blinking | 2 times |
| from power relay ON immediately after operation starts |
|
|
|
|
|
|
| >>Cooling 0 code transmission, automatic reset |
|
|
|
|
|
|
| When a signal is not read for 20 secs thereafter |
|
|
|
|
|
|
| >>Trouble display continues and power relay OFF |
|
|
|
|
|
|
| >>Permanent stop |
|
|
| Signal reverse signal error | 0.1sec | 0.5sec |
| When a signal is not read continuously for 10 secs |
|
|
| during operation | blinking | 2 times |
| from power relay ON immediately after operation starts |
|
|
|
|
|
|
| >>Cooling 0 code transmission, automatic reset |
|
|
|
|
|
|
| When a signal is not read for 20 secs thereafter |
|
|
|
|
|
|
| >>Trouble display continues and power relay OFF |
|
|
|
|
|
|
| >>Permanent stop |
|
|
|
|
|
|
|
|
|
|
| Serial forward signal error | 0.1sec | 0.5 sec |
| Normal Serial Forward Signal can not be |
|
|
| at operation start up | blinking | 4 times |
| received more than 10 secs |
|
|
|
|
|
|
| >>Releases when it becomes normal |
|
|
|
|
|
|
|
|
|
|
| Serial forward signal error | 0.1sec | 0.5sec |
| Normal Serial Forward Signal can not be |
|
|
| during operation | blinking | 5 times |
| received more than 10 secs ( after receiving |
|
|
|
|
|
|
| effective forward transfer signal) |
|
|
|
|
|
|
| >>Releases when it becomes normal |
Indoor unit | 0.5sec | 0.1sec | Indoor temperature | 0.1sec | 0.5sec | Indoor | Thermistor detection value is open when |
thermistor | 2 times | blinking | thermistor open | blinking | 2 times | AC plug is inserted | |
error |
|
|
|
|
|
| |
|
|
|
|
|
| >>Releases when value becomes normal | |
|
|
|
|
|
|
| |
|
|
| Pipe thermistor | 0.1sec | 0.5sec | Indoor | Thermistor detection value is open or short |
|
|
| open or short | blinking | 3 times | when AC plug is inserted | |
|
|
|
|
|
| >>Releases when value becomes normal | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
Outdoor unit | 0.5sec | 0.1sec | Discharge thermistor | 0.1sec | 0.5sec | Outdoor | Thermistor detection value is open or short |
thermistor | 3 times | blinking | open or short | blinking | 2 times |
| |
error |
|
|
|
|
|
| |
|
|
|
|
|
| >>Outdoor unit stops | |
|
|
|
|
|
|
| Releases when it becomes normal |
|
|
|
|
|
|
|
|
|
|
| Heat exchanger | 0.1sec | 0.5sec | Outdoor | Thermistor detection value is open |
|
|
| thermistor open | blinking | 3 times |
| |
|
|
|
|
|
| >>Outdoor unit stops | |
|
|
|
|
|
|
| Releases when it becomes normal |
|
|
| Outdoor temperature | 0.1sec | 0.5sec | Outdoor | Thermistor detection value is open or short |
|
|
| thermistor open or short | blinking | 4 times |
| |
|
|
|
|
|
| >>Outdoor unit stops | |
|
|
|
|
|
|
| Releases when it becomes normal |
Indoor unit | 0.5sec | 0.1sec | Forced automatic SW | 0.1sec | 0.5sec |
| Forced Auto SW is ON for more than |
control error | 4 times | blinking | welded | blinking | 2 times | Indoor | 10 secs continuously |
|
|
|
|
|
| >>Error is indicated while it is ON | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| Normal Operation other than error indication |
|
|
|
|
|
|
|
|
|
|
| Main relay welded | 0.1sec | 0.5sec |
| Serial Reverse Signal is received 1 min. |
|
|
|
| blinking | 3 times |
| after Main relay becomes OFF |
|
|
|
|
|
| Indoor | >>Error is indicated while serial reverse |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| signal is input on normal operation |
|
|
|
|
|
|
| Normal operation except error indication |
|
|
|
|
|
|
|
|
|
|
| Power interruption error | 0.1sec | 0.5sec | Indoor | 50/60Hz is not detected after 4 secs of |
|
|
|
| blinking | 4 times | power ON. | |
|
|
|
|
|
| >>Error is indicated and unit is stopped | |
|
|
|
|
|
|
|
2006.02.20 | 10 |