Friedrich MW18Y3F, MR18Y3F Active Filter voltage error operated 3 times Permanent stop

Page 12

Trouble Display (primary)

Detailed Trouble Display (by Test Button)

Error

Operation

Timer

Error

Operation

Timer

Outdoor unit

0.5sec

1 sec

Current trip

0.1sec

0.5sec

control error

5 times

blinking

 

blinking

2 times

 

 

 

CT abnormal

0.1sec

0.5sec

 

 

 

 

blinking

3 times

 

 

 

Compressor rotation

0.1sec

0.5 sec

 

 

 

error

blinking

5 times

 

 

 

Outdoor unit fan drive

0.1sec

0.5sec

 

 

 

system abnormal

blinking

6 times

Indoor fan

0.5sec

0.1sec

Abnormal lock

0.1sec

0.5sec

motor error

6 times

blinking

 

blinking

2 times

 

 

 

Abnormal rotation

0.1sec

0.5sec

 

 

 

 

blinking

3 times

Refrigerant

0.5sec

0.1sec

Discharge temperature

0.1sec

0.5sec

cycle error

7 times

blinking

abnormal

blinking

2 times

 

 

 

Cooling high pressure

0.1sec

0.5sec

 

 

 

abnormal rise

blinking

3 times

Optional

0.5sec

0.1sec

Active filter voltage

0.1sec

0.5sec

function

8 times

blinking

abnormal (3rd time)

blinking

2 times

error

 

 

 

 

 

 

 

 

Active filter foltage

0.1sec

0.5sec

 

 

 

abnormal (1st time)

blinking

3 times

 

 

 

 

 

 

Outdoor Outdoor Outdoor Outdoor Indoor Indoor Outdoor Outdoor Outdoor Outdoor

Detailed Error Item

Current trip error is 2nd time within start up

>>Permanent stop

Current detection value is 0A for more than 1 sec when compressor is operated at more than 56rps

>>Automatic release after 3 min. ST

Compressor location detection error (incl. failed start up) for 3 times

>>Permanent stop

When outdoor fan abnormal fan motor duty abnormal operated 5 times

>>Permanent stop

Detected rotation is 0 r.p.m. at start up or at 56 secs after Fan mode is selected

>>Permanent stop

Detected rotation is 1/3 of target r.p.m. at start up or at 56 secs after Fan mode is selected

>>Permanent stop

Discharge Temperature protection (Discharge temperature is 110degC) operated 2 times

>>Permanent stop

High pressure rise protection (Outdoor heat exchanger temperature is 65degC) operated

>>Comp. OFF (releases after 3min.ST) Error is indicated while 3 min.ST

Active Filter voltage error operated 3 times

>>Permanent stop

Active Filter Module error or open detection protection operated

>>Automatic release after 3 min. ST

2006.02.20

11

Image 12
Contents Wall Mounted type Specifications Electrical DataDimensions Refrigerant System Diagram Circuit Diagram Indoor UnitIndoor PCB Circuit Diagram Model MW18Y3FController PCB Assembly Indicator PCB Assy Outdoor PCB Circuit Diagram Inverter Assembly EZ-005SHUE60Hz Error Contents Active Filter voltage error operated 3 times Permanent stop Disassembly Illustration 61-2 61-1 2006.02 Parts List MW18Y3FMR18Y3F Standard Accessories 0511G2952