Friedrich ZQ05C10 manual Evaporator, Capillary Tube

Page 10

2.4.2 EVAPORATOR

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the upper air guide .(Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections.

5.Remove the evaporator.

6.Re-install by referring to the procedures above.

2.4.3 CAPILLARY TUBE

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the upper air guide . (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube of the capillary tube.

5.Remove the capillary tube.

6.Re-install by referring to the procedures above.

NOTES

Replacement of the refrigeration system.

1.When replacing the refrigeration system, be sure to discharge the refrigerant by using a refrigerant recovery system.

2.After discharging the unit completely, remove the desired components, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with service valves.

5.After completing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.

6.Evacuate as follows:

6-1. Connect the vacuum pump, as illustrated in figure 21A.

6-2. Start the vacuum pump. Slowly open manifold valves A and B with two full turns counter- clockwise and leave the valves closed.

The vacuum pump is now pulling through valves A and B up to valve C by means of manifold and the entire system.

CAUTION : If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclock-

wise. This will keep oil from foaming and being drawn into the vacuum pump.

6-3. Operate the vacuum pump for 20 to 30 min- utes, until 600 micron vacuum is obtained. Close valves A and B and observe vacuum gauge for a few minutes.

A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

6-4. Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 23B. Open valve C.

Discharge the line at the manifold connection. 6-5. The system is now ready for final charging.

7.Recharge as follows:

7-1. Refrigeration cycle systems are charged from the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which is installed as the system is opened.

7-2. Connect the charging cylinder as shown in fig- ure 21B. With valve C open, discharge the hose at the manifold connection.

7-3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.

7-4. If more charge is required, the high-side will not take it. Close valve A.

7-5. With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the low- side.

b.Watch the low-side gauge, allow pressure to rise to 30 lbs.

c.Turn off valve B and allow the pressure to drop.

d.Repeat steps b. and c. until the balance of the charge is in the system.

7-6. When the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on the pinch-off tube. Using a tube cut- ter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit, allow setting for a while and then test the leak- age of the pinch-off connection.

— 10—

Image 10
Contents Page Contents Preface Locations of Controls Front Grille Disassembly InstructionsMechanical Parts CabinetAIR Guide Upper AIR Handling PartsORIFICE, Turbo FAN and FAN AIR Guide Electrical PartsOverload Protector Capacitor Rotary SwitchCompressor ThermostatRefrigeration System Power CordCondenser Evaporator Capillary TubePulling Vacuum Troubleshooting Guide Piping System Condenser CoilsTroubleshooting Guide Unit is running but cooling is ineffectiveFails to Start Room AIR Conditioner Voltage Limits Replace if open. If the compressor temperature is Complaint Cause Remedy Circuit Diagram Model ZQ05C10Exploded View Service Parts List Memo Memo Use Factory Certified Parts

ZQ05C10 specifications

The Friedrich ZQ05C10 is an innovative solution in the world of air conditioning, specifically designed to meet the needs of modern consumers and businesses seeking efficient and effective climate control. This model stands out with its combination of performance, technology, and user-friendly features, making it a popular choice among users.

One of the main features of the ZQ05C10 is its energy efficiency. This model operates with a high SEER (Seasonal Energy Efficiency Ratio) rating, which indicates its ability to provide cooling while consuming less electricity. This not only helps in reducing energy bills but also contributes to a more sustainable environment by lowering the carbon footprint.

The ZQ05C10 is equipped with advanced inverter technology, allowing it to adjust its cooling output according to the ambient temperature. This smart feature enables the unit to run more quietly and efficiently, maintaining a comfortable indoor climate without the noisy fluctuations associated with traditional air conditioning units.

Another standout characteristic of the Friedrich ZQ05C10 is its robust build quality and sleek design. The unit boasts a modern aesthetic that can seamlessly fit into any home or office decor. Available in a range of sizes, it can be installed in various settings, from small bedrooms to larger living spaces.

In terms of technological integration, the ZQ05C10 comes with Wi-Fi connectivity, allowing users to control their air conditioning remotely via a smartphone application. This feature enhances usability, enabling users to adjust settings, monitor energy consumption, and schedule operations from virtually anywhere.

Moreover, the ZQ05C10 incorporates advanced filtration systems that significantly improve indoor air quality. Its multi-stage filters capture dust, allergens, and other airborne particles, ensuring that the air circulated within the space is clean and healthy.

Safety features are also prioritized in the design of the ZQ05C10. It includes built-in protection against power surges and has an auto-restart function in the event of a power failure, ensuring that it resumes operation without any manual intervention.

In summary, the Friedrich ZQ05C10 presents a comprehensive package featuring energy efficiency, advanced technology, robust design, and enhanced air quality. Its combination of these traits makes it an excellent choice for anyone looking to invest in a reliable air conditioning system.