Friedrich CP08E10, CP06E10 manual Troubleshooting Guide

Page 26

www.sylvane.com 1-800-934-9194

 

 

 

Troubleshooting Guide

 

 

 

 

 

 

 

 

COMPLAINT

CAUSE

REMEDY

 

 

 

 

Fan motor noise.

Fan

If cracked, out of balance, or partially missing,

 

 

 

replace it.

 

 

 

 

 

 

Blower

If cracked, out of balance, or partially missing,

 

 

 

replace it.

 

 

 

 

 

 

Loose set screw

Tighten it.

 

 

 

 

 

 

Worn bearings

If knocking sounds continue when running or

 

 

 

loose, replace the motor. If the motor hums or

 

 

 

noise appears to be internal while running,

 

 

 

replace motor.

 

 

 

Compressor will not run,

Voltage

Check voltage. See the limits on the preceding

fan motor runs.

 

page. If not within limits, call an electrician.

 

 

 

 

 

 

Wiring

Check the wire connections; if loose, repair or

 

 

 

replace the terminal. If the wires are discon-

 

 

 

nected, refer to wiring diagram for identification,

 

 

 

and replace the wires. Check the wire connections;

 

 

 

If not according to the wiring diagram, correct

 

 

 

the connections.

 

 

 

 

 

 

Thermistor

Check the TEMP control. If not at the lowest

 

 

 

number, set TEMP control to this setting and

 

 

 

restart the unit.

 

 

 

 

 

 

 

Check the continuity of the thermistor. Replace

 

 

 

the thermistor if the circuit is open.

 

 

 

 

 

 

Rotary

Check for continuity, refer to the wiring diagram

 

 

 

for terminal identification. Replace the switch if

 

 

 

the circuit is open.

 

 

 

 

 

 

Thermostat

Check the position of knob. If not at the coldest

 

 

 

setting, advance the knob to this setting and

 

 

 

restart the unit.

 

 

 

 

 

 

 

Check the continuity of the thermostat. Replace

 

 

 

the thermostat if the circuit is open.

 

 

 

 

 

 

Capacitor (discharge

Check the capacitor.

 

 

capacitor before

Replace if not within ±10% of manufacturer’s

 

 

servicing.)

rating, replace if shorted, open, or damaged.

 

 

 

 

 

 

Compressor

Check the compressor for open circuit or

 

 

 

ground. If open or grounded, replace the

 

 

 

compressor.

 

 

 

 

 

 

Overload

Check the compressor overload if externally mounted.

 

 

 

Replace if open. (If the compressor temperature is

 

 

 

high, remove the overload, cool, and retest.)

 

 

 

 

 

 

 

 

Service Manual 26

Image 26
Contents Room Air Conditioner Service and Parts Manual Table of Contents Safety Precautions Be sure not to doPlug in the power plug properly Do not clean the air conditioner with water Outside Dimensions DimensionsSymbols Used in this Manual Product Specifications 800Operation Location and Function of ControlsAuto Swing Front Grille DisassemblyMechanical Parts CabinetFAN and Shroud Air Handling PartsAIR Guide and Blower Overload Protector Electrical PartsMotor CompressorCapacitor Power CordRefrigerating Cycle CondenserEvaporator Capillary TubePulling Vacuum Circuit Diagram Description QTYElectronic Control Device Components LocationFor Main P.W.B ASM Troubleshooting Guide Piping SystemTroubleshooting Guide Unit runs but poor coolingFails to Start Electric Parts Troubleshooting Guide Possible TroubleIC01M 0V? Is the voltage No.16 Room AIR Conditioner Voltage Limits Troubleshooting Guide Troubleshooting Guide Exploded View RoomAir Conditioner Use Factory Certified Parts
Related manuals
Manual 30 pages 24.51 Kb

CP06E10, CP08E10 specifications

Friedrich CP08E10 and CP06E10 are two high-performance portable air conditioning units designed to deliver effective cooling solutions for residential and commercial spaces. Renowned for their reliability, these models incorporate advanced features and technologies to ensure user comfort and ease of use.

One of the prominent features of both the CP08E10 and CP06E10 is their powerful cooling capacity. The CP08E10 has a cooling capacity of 8,000 BTUs, making it suitable for larger rooms up to 350 square feet, while the CP06E10 offers 6,000 BTUs of cooling, effectively accommodating areas up to 250 square feet. This versatility allows users to choose a model that best fits their specific room size and cooling needs.

Both units are equipped with a range of operating modes, including cooling, fan, and dehumidification. This versatility allows users to customize their environment based on preferences and seasonal conditions. The dehumidification function is particularly beneficial in humid climates, helping to remove excess moisture from the air while maintaining a comfortable temperature.

Energy efficiency is another critical aspect of the Friedrich CP08E10 and CP06E10. Both models possess an Energy Efficiency Ratio (EER) that results in reduced electricity consumption compared to conventional air conditioning systems. This not only saves money on heating and cooling bills but also minimizes the environmental impact, aligning with the growing demand for green technology.

In terms of design, the units feature a sleek and compact profile, making them easy to move and install. They come with caster wheels for portability, and the installation kit simplifies the setup process, ensuring users can quickly enjoy their cooling effects.

Comfort is enhanced through the inclusion of a programmable thermostat and remote control, allowing users to adjust settings from across the room conveniently. The units also feature multiple fan speeds, enabling precise control over airflow and noise levels, making them suitable for both daytime and nighttime use.

Lastly, maintenance is simplified thanks to the accessible filter, which can be easily cleaned and replaced as needed. This feature prolongs the lifespan of the units and ensures they maintain optimal performance throughout their use.

In summary, the Friedrich CP08E10 and CP06E10 combine powerful cooling capacities, energy efficiency, user-friendly features, and a compact design, making them ideal choices for anyone looking to enhance their indoor climate while maintaining convenience and comfort.