Sanyo manual WCHDXseries, Way ECOi VRF Heat Pumps combined units, Wchdx Chdx, Chdx Wchdx

Page 14

WCHDXseries

W 2-Way ECOi VRF Heat Pumps combined units

SANYO’s Combined ECOi outdoor units offer superior heating and cooling coupled with cost effective installation. Providing a single refrigerant pipe network means there’s only one penetration into the building and ultimately less piping material required, saving you time and money. A smart conditioning solution for large capacity jobs.

WCHDX Combined Series.

WCHDX 14463 / WCHDX 16863 / WCHDX 19263

WCHDX 21663 / WCHDX 24063

WCHDX 26463 / WCHDX 28863

Key Features:

*Heat Pump

*Combine 3 outdoor units up to 24 tons

*Combined Series Allows Up to 40 Indoor Units (50%-130% ratio of indoor to outdoor capacity)

*“ECO Friendly” R410A Refrigerant

*208/230V, 3 Phase, 60Hz

*Multiple Compressors For Precise and Efficient Operation

*Operating Range (Outdoor Ambient) -Cooling 14 FDB to 113 FDB

-Heating -4 FWB to 59 FWB

*Ultra Quiet Operation As Low As 51.5dB(a)

*Variable Speed DC Fan Motors

*Flexible Piping Design:

-984 Feet - Maximum Total Liquid Line

-492 Feet - Maximum Outdoor To Most Distant Indoor Unit

-164 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Above Indoor)

-131 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Below Indoor)

System

Outdoor Unit

Cooling & Heating

Power input

Control Range

 

 

 

208/230

 

 

 

 

 

 

WCHDX 14463

CHDX 07263 (quantity of 2)

144,000 & 162,000 BTU/H

10.56/11.58 kW

6 - 100%

 

 

 

 

 

WCHDX 16863

CHDX 07263

168,000 & 189,000 BTU/H

12.97/ 14.39 kW

6 - 100%

 

CHDX 09663

 

 

 

 

 

 

 

 

WCHDX 19263

CHDX 09663 (quantity of 2)

192,000 & 216,000 BTU/H

15.38/ 17.2 kW

6 - 100%

 

 

 

 

 

WCHDX 21663

CHDX 07263 (quantity of 3)

216,000 & 243,000 BTU/H

15.84/ 17.37 kW

6 - 100%

 

 

 

 

 

WCHDX 24063

CHDX 07263 (quantity of 2)

240,000 & 270,000 BTU/H

18.25/ 20.18 kW

6 - 100%

 

CHDX 09663

 

 

 

 

 

 

 

 

WCHDX 26463

CHDX 09663 (quantity of 2)

264,000 & 297,000 BTU/H

20.66/ 22.99 kW

6 - 100%

 

CHDX 07263

 

 

 

 

 

 

 

 

WCHDX 28863

CHDX 09663 (quantity of 3)

288,000 & 324,000 BTU/H

23.07/ 25.8 kW

6 - 100%

 

 

 

 

 

(R)indicates with salt protection - Special Order

*NOTE: *460 Volt Step Down Transformers (460-230) available for 6 and 8 ton condensers

14

Image 14
Contents ECOiTM Sanyo Control System ECOi Building ECOi Your Building Life Tool Way ECOiTM VRF Heat Recovery CHDZseries CHDXseriesWay ECOi VRF Heat Recovery CHDZseriesFan device Chdz RPerformance Wchdz Way ECOi VRF Heat Recovery Combined UnitsWCHDZseries Wchdz ChdzWay ECOi VRF Heat Recovery Combined Units WCHDZseries Wchdz21663 24063 26463 28863 Refrigerant tube diameter CHXseriesCHX R Chdx CHDXseriesWay ECOi VRF Heat Pump Chdx RDescription Chdx RWchdx WCHDXseriesWay ECOi VRF Heat Pumps combined units Wchdx ChdxWchdx Wchdx KHX 1962 / KHX 2452 / ATK-SVRK56BA KHXseriesKHX THX THXseriesCeiling Suspended Unit THX 1252 / THX 1852 / THXAHX 52 / 09 AHX 52/ 12 AHX Drainpipe DimensionAHXseries AHXXmhx XMHXseriesXmhx 52 / 18 Xmhx XHX 52 / 36 XHX XMXUmhx 0762 / Umhx 0962 / Umhx 1262 Umhx 1562 / Umhx UMHXseriesUmhx UHXseries UHXDHX DHXseriesConcealed Ducted Medium-High Static DHX 3652 / DHXFloor Mounted FHX/FMHXseries Floor Mounted With Decorative PanelControl systems Simple System Control Network S-NetKey Features Standard Remote/7 Day Timer Key Features Simple RemoteSimple System Control Network Key Features System ControlKey Features Intelligent Control Building Management Integration Control systems SHA-LN16UABAccessories Services Safety Precautions