Sanyo manual Way ECOi VRF Heat Recovery Combined Units WCHDZseries, Wchdz

Page 9

3-Way ECOi VRF Heat Recovery Combined Units WCHDZseries

DESCRIPTION

WCHDZ 14463

WCHDZ 16863

WCHDZ 19263

 

includes (1) CHDZ07263

includes (1)CHDZ07263 and

includes (1) CHDZ09663

 

and (1) CHDZ07263

(1) CHDZ09663

and (1) CHDZ09663

Performance

 

 

 

Cooling capacity: BTU/H

144,000

168,000

192,000

Power input: kW

10.56

12.97

15.38

Heating capacity: BTU/H

162,000

189,000

216,000

Power input: kW

11.58

14.39

17.2

 

 

 

 

Cooling Mode Nominal Conditions

 

 

 

Indoor: °F WB/ °F DB

80/67

80/67

80/67

Outdoor: °F DB

95

95

95

Pipe Length: Feet

25

25

25

Level Difference: Feet

0

0

0

 

 

 

 

Heating Mode Nominal Conditions

 

 

 

Indoor: °F DB

70

70

70

Outdoor: °F DB/ °F WB

47/43

47/43

47/43

Pipe Length: Feet

25

25

25

Level Difference: Feet

0

0

0

 

 

 

 

Operating Range

 

 

 

Cooling: °F DB

14 to 113

14 to 113

14 to 113

Heating: °F WB

-4 to 59

-4 to 59

-4 to 59

 

 

 

 

Compressor

 

 

 

Type/Quantity

2 Inverter driven Rotary

2 Inverter driven Rotary

2 Inverter driven Rotary

 

 

& 1 fixed speed scroll

& 2 fixed speed scroll

Capacity Control Range: %

6 - 100%

6 - 100%

6- 100%

 

 

 

 

Fan

 

 

 

Type/Quantity

1 Propeller (ea)

1 Propeller (ea)

1 Propeller (ea)

Fan Motor Output: (kW)

0.7 kW (ea)

0.7 kW (ea)

0.7 kW (ea)

External Static Pressure

.04 / .25

.04 / .25

.04 / .25

 

 

 

 

Power Supply

 

 

 

V/PH/Hz

208 - 230/ 3/ 60

208 - 230/ 3/ 60

208 - 230/ 3/ 60

Minimum Circuits Amps (MCA): (A)

52

60

68

Max. Overcurrent Protection (MOCP): (A)

80

85

90

 

 

 

 

Weight: (lbs)

1168

1267

1366

 

 

 

 

Coil:

 

 

 

Coil Face Area:(sq. Ft.)

29.5(ea)

29.5(ea)

29.5(ea)

Number of Rows:

4(ea)

4(ea)

4(ea)

 

 

 

 

Protection Devices

 

 

 

High Pressure Switch/Overcurrent

Yes

Yes

Yes

(CT Method)

25 + 25

25 + 25 + 32

25 + 32 X 2

Crankcase Heaters:(W)

 

 

 

 

 

 

 

Each outdoor unit requires a separate electrical FUSED DISconnect, see individual outdoor requirements.

(R)indicates with salt protection - Special Order

*NOTE: *460 Volt Step Down Transformers (460-230) available for 6 and 8 ton condensers

SANYO OUTDOOR

09

Image 9
Contents ECOiTM Sanyo Control System ECOi Building ECOi Your Building Life Tool CHDXseries Way ECOiTM VRF Heat Recovery CHDZseriesCHDZseries Way ECOi VRF Heat RecoveryChdz R PerformanceFan device WCHDZseries Way ECOi VRF Heat Recovery Combined UnitsWchdz Wchdz ChdzWchdz Way ECOi VRF Heat Recovery Combined Units WCHDZseries21663 24063 26463 28863 CHXseries CHX RRefrigerant tube diameter Way ECOi VRF Heat Pump CHDXseriesChdx Chdx RChdx R DescriptionWay ECOi VRF Heat Pumps combined units WCHDXseriesWchdx Wchdx ChdxWchdx Wchdx KHXseries KHXKHX 1962 / KHX 2452 / ATK-SVRK56BA Ceiling Suspended Unit THXseriesTHX THX 1252 / THX 1852 / THXAHXseries Drainpipe DimensionAHX 52 / 09 AHX 52/ 12 AHX AHXXMHXseries Xmhx 52 / 18 XmhxXmhx XMX XHX 52 / 36 XHXUMHXseries UmhxUmhx 0762 / Umhx 0962 / Umhx 1262 Umhx 1562 / Umhx UHX UHXseriesConcealed Ducted Medium-High Static DHXseriesDHX DHX 3652 / DHXFloor Mounted With Decorative Panel Floor Mounted FHX/FMHXseriesSimple System Control Network S-Net Control systemsKey Features Simple Remote Key Features Standard Remote/7 Day TimerKey Features System Control Key Features Intelligent ControlSimple System Control Network SHA-LN16UAB Building Management Integration Control systemsAccessories Services Safety Precautions