TROUBLESHOOTING (Continued)
PROBLEM | POSSIBLE CAUSE | TO CORRECT | |
| Defective switch | Check continuity across terminals 2 and 3. | |
| Fan capacitor open. | Check by substituting a known good capacitor of the same | |
| rating. | ||
|
| ||
FAN MOTOR DOES | Inoperative fan motor. | Direct test fan motor. | |
NOT RUN. | Incorrect wiring of fan circuit. | Connect per wiring diagram. | |
| Relay open. | Replace Relay. | |
| Check for seized motor bearings. | Rotate by hand, add oil, if noisy, replace. | |
| Bound fan blade or blower wheel. | Adjust for proper clearance. | |
|
|
| |
SWITCH |
|
| |
DOES NOT CUT | Selector Switch Relay | Replace selector switch. Replace relay. | |
FAN MOTOR OFF. |
|
| |
|
|
| |
| Poor installation. | Refer to Installation Instructions for proper installation. | |
| Fan blade striking chassis. | Adjust motor mount to attain proper fan blade and blower | |
| wheel clearance. | ||
|
| ||
NOISY AND/OR | Compressor vibrating. | Check for deteriorated compressor grommets, or missing | |
VIBRATION. | mounting parts. | ||
| |||
| Loose cabinet parts, improperly |
| |
| mounted components, tubing | Adjust and tighten as required. | |
| rubbing. |
| |
|
|
| |
| Evaporator drain pan overflowing. | Clean obstructed drain trough. | |
WATER LEAKS | Condensation forming on bottom | Evaporator drain pan broken or cracked. Reseal or | |
of base pan. | replace. | ||
INTO ROOM. | |||
Water dripping from discharge air | Dirty evaporator coil, or extremely high humidity conditions. | ||
| |||
| grilles. | Clean coil with steam or detergent. | |
|
|
| |
| Evaporator drain pan cracked or | Repair and clean, or replace as required. | |
| obstructed. | ||
|
| ||
| Water in center section of base | Remove condenser shroud, Clean and remove old sealer | |
OUTSIDE WATER | from base pan and shroud. Apply new sealer, reinstall and | ||
pan (compressor area). | |||
LEAKS. | check. | ||
| |||
| Dirty Condenser coil. | Clean with steam or detergent. | |
| Fan blade and slinger ring | Adjust fan blade to 1/2" clearance from condenser coil. | |
| improperly positioned. | ||
|
|