Studer Innotec XPC 2200-48 user manual Remote Control, Multifunctional Contact, Temperature sensor

Page 17

STUDER Innotec

XP-COMPACT

 

 

4.10 The Multifunctional Contact

In the XP-COMPACT there is a built-in power relay. The potential-free change-over contact (NO – NC) of this power relay is connected to the screw terminal AUX CONTACT.

Maximum Contact load: 230Vac /12Vdc/24Vdc/16Amp 60Vdc/3 Amp. !

The contact is activated when the XP-COMPACT is halted or by a fault condition, or by a normal manual stop done by pushing push-button 19.

This auxiliary contact can be freely programmed for any displayed functional status through the remote control (refer to chap.5)

4.11 The Temperature sensor

Operating voltage of lead-acid batteries change depending on the tempera- ture. To correct the operating voltages according to the actual temperatures, a temperature sensor can be connected to the COMPACT.

The compensation through the sensor is –3mV/°C/Cell.

Order Number: CT-35

Dimensions: H x B x T / 58 x 51.5 x 22mm

5 The Remote Control

As an option a Remote Control can be connected to the XP- COMPACT through a standard supplied 20m long cable. It can be extended to 40m.

The Remote Control is suitable for surface mounting on the wall or on to a switch board. It is fixed with 4 screws.

All operating controls and displays except from level adjustment are available on the Remote Control. Several extra features are implemented in the remote control:

A charging current monitor (25) Output power monitor (25) The battery status monitor Auxiliary contact programming Battery voltage level adjustment Remote Alarm contact and command

5.1Remote control plug-in

The remote is delivered with a 20m long cable and can be connected or discon- nected at any time while the main unit is running (hot plug).

The remote control can be mounted with the frame or directly on a board. The screws are not supplied.

5.2Power monitor

The instantaneous power of the inverter in % off Pnom or the charging current is continuously displayed on LED lines (25).

INVERTER - CHARGER

COMPACT

1

 

TRANSFER

8

 

A

%

AC IN

 

 

 

AC OUT

100

160

 

2

7

9

 

90

160

CHARGER

 

 

 

INVERTER

80

130

 

 

 

 

RESET

70

100

SOLAR CHARGE

 

 

20

60

80

 

 

ALARM

3

 

 

 

 

 

 

 

(Select)

50

60

EQUALIZE

14

10

Over Temp.

40

40

30

20

 

 

 

 

 

4 Program

 

15

11

Overload

20

10

 

12

Battery

10

5

 

 

 

5 Contact active

 

16

Low/High

Charger

Inverter

 

 

6 Contact manual

 

17

13

OFF

 

 

18

 

 

 

25

AUXILIARY CONTACT

 

 

ON/OFF

 

 

 

 

 

 

 

(Program)

 

 

 

(Change status)

 

21

 

 

19

 

 

 

RCC-01

User manual

XP-COMPACT V5.1 E

16

Image 17
Contents XP-COMPACT V5.1 E XP-COMPACT XPCControl SummaryMaintenance CE Compliance Technical Data Warranty Disclaimer Quality and WarrantyGeneral Information Operating instructionsSpecial Precautions PrecautionsIntroduction Principle schematicDescription of main functions InverterBattery connections Installation place Mounting and installingFixing Protection cover IP23Solar + Connecting panel / Front sideProtection cover for the terminals con- nections Pre-installation settings Cabling/wiringConnection to battery Connecting the 230Vac-Consumer Appliance AC OutputConnection to Temperature Sensor Temp Connection to Remote controlControl Display and control parametersMarking LED lit LED blinks Light Emitting Diodes LEDInverter Push buttonsTurning Knobs Battery Condition Battery chargerOverheating Over Temp Cycle of chargeCharging current Transfer systemEqualization charging Delayed mode of the Transfer System Fast UPS- Mode for the Transfer SwitchSolar charge controller option Set the transfer voltage thresholdTemperature sensor Remote ControlRemote control plug-in Power monitorFault indicator Battery ConditionRemote alarm contact and on/off control ProgrammingBattery voltages and absorption time Standard settingReset value default settings Principle Program the auxiliary contactExample Diagram of the different modeDisabling some of the XP-COMPACT functions CE Compliance MaintenanceModel Technical Data