Tripp Lite APSX6048VRNET owner manual Specifications, Overview, Output, Input, Battery

Page 2

Automatic overload and thermal (overheating) shutoff

Front panel remote control connector enables remote off/on switching (APSRM4 sold separately)

Load sensing control dial enables adjustable load threshold required to automatically turn the inverter on and off in DC mode as load conditions change

Automatic Generator Starter jack enables user configuration of automatic generator start-up as inverter batteries drop to 23.0 VDC and generator shutoff as inverter batteries are recharged to 28.2 VDC.

Remote battery temperature sensing connection function prolongs battery life by adjusting the charge float voltage level based on battery temperature

DB9 communication port for SNMPWEBSOLOHV management.

Specifications

OVERVIEW

Intended Application

OUTPUT

Emergency Power, Remote Power, Alternative Power

Frequency compatibility

Output watts

Continuous output capacity (watts)

Peak output capacity (watts)

Output nominal voltage

Output voltage regulation

Output frequency regulation

Outlet quantity / type

INPUT

50 / 60 Hz

6000

6000

12000

208/230V

LINE POWER (AC): Maintains 208/230V nominal sine wave output from line power source. INVERTER POWER (AC): Maintains sine wave output voltage of 208/230 VAC (+/-5%).

50/60 Hz (+/- 0.3 Hz)

Hardwire

Nominal Input

Voltage(s)

Supported

208V AC; 230V AC

Recommended Electrical Service

Maximum input amps / watts

Input connection type

Voltage compatibility (VAC)

Voltage compatibility (VDC)

BATTERY

DC INPUT: Requires 48VDC input source capable of delivering 138A for the required duration (when used at full continuous capacity - DC requirements increase during OverPower and DoubleBoost operation). For automotive applications, professional hardwire installation with 250A minimum battery system fusing is recommended.

DC INPUT: Full continuous load - 145A at 48VDC. AC INPUT: 30 amps at 208/230VAC with full inverter and charger load

DC INPUT: Set of DC bolt-down terminals. AC INPUT: Hardwire via built in terminal strip with cover plate

208; 230

48

Expandable battery runtime

Runtime is expandable with any number of user supplied wet or gel type batteries

Image 2
Contents Description FeaturesHighlights Overview SpecificationsBattery OutputVoltage Regulation Leds Alarms & SwitchesLine / Battery Transfer PhysicalRelated Items Special FeaturesWarranty Certifications