Automatic overload and thermal (overheating) shutoff
Front panel remote control connector enables remote off/on switching (APSRM4 sold separately)
Load sensing control dial enables adjustable load threshold required to automatically turn the inverter on and off in DC mode as load conditions change
Automatic Generator Starter jack enables user configuration of automatic generator
Remote battery temperature sensing connection function prolongs battery life by adjusting the charge float voltage level based on battery temperature
DB9 communication port for SNMPWEBSOLOHV management.
Specifications
OVERVIEW
Intended Application
OUTPUT
Emergency Power, Remote Power, Alternative Power
Frequency compatibility
Output watts
Continuous output capacity (watts)
Peak output capacity (watts)
Output nominal voltage
Output voltage regulation
Output frequency regulation
Outlet quantity / type
INPUT
50 / 60 Hz
6000
6000
12000
208/230V
LINE POWER (AC): Maintains 208/230V nominal sine wave output from line power source. INVERTER POWER (AC): Maintains sine wave output voltage of 208/230 VAC
50/60 Hz (+/- 0.3 Hz)
Hardwire
Nominal Input
Voltage(s)
Supported
208V AC; 230V AC
Recommended Electrical Service
Maximum input amps / watts
Input connection type
Voltage compatibility (VAC)
Voltage compatibility (VDC)
BATTERY
DC INPUT: Requires 48VDC input source capable of delivering 138A for the required duration (when used at full continuous capacity - DC requirements increase during OverPower and DoubleBoost operation). For automotive applications, professional hardwire installation with 250A minimum battery system fusing is recommended.
DC INPUT: Full continuous load - 145A at 48VDC. AC INPUT: 30 amps at 208/230VAC with full inverter and charger load
DC INPUT: Set of DC
208; 230
48
Expandable battery runtime
Runtime is expandable with any number of user supplied wet or gel type batteries