GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a her- metic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of ARI Standard 210.

Unit will be certified for capacity and efficiency, and listed in the lastest ARI directory.

Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have c-UL approval.

Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test.

Air-cooled condenser coils will be leak tested at 150 psig and pressure tested at 450 psig.

Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled air conditioner unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge Puron® (R-410A), and special features required prior to field start-up.

Refrigerant

Refrigerant will be Puron (R-410A) HFC Refrigerant with zero ozone depletion potential. R-410A is approved under the EPA’s Significant New Alternatives Program (SNAP).

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Air-Cooled, Split-System Air Conditioner 552A

1-1/2 to 5 Tons Nominal

Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.

Fan blades will be statically and dynamically balanced.

Condenser fan openings will be equipped with PVC-coated steel wire safety guards.

Compressor

Compressor will be hermetically sealed.

Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.

Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed.

Refrigeration Components

Refrigeration circuit components will include liquid-line shutoff valve with sweat connections, vapor-line shutoff valve with sweat connections, system charge of Puron® (R-410A) refrigerant, and compressor oil.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a

suction temperature of _____ °F. The power consumption at full

load will not exceed _____ kW.

Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh or greater at

conditions of _____ CFM entering air temperature at the

evaporator at _____ °F wet bulb and _____ °F dry bulb, and air

entering the unit at _____ °F.

The system will have an SEER of _____ Btuh/watt or greater at

DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, single

phase, 60 hz. The unit will be capable of satisfactory operation within voltage limits of _____ v to _____ v.

Unit electrical power will be single point connection. Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS

Cancels: PDS 552A.18.2

New: PDS 552A.18.3

© 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231

—36—

PRINTED IN U.S.A. Catalog No. 5255-206 10-03

Image 36
Contents 552A 60 Hz Dimensions Unit Dimensions Minimum Mounting SizeUnit PistonIdentification no Unit SIZE-SERIES Required Subcooling FSpecifications ElectricalSpecifications Accessory Usage Guideline Required for LOW-AMBIENT LONG-LINE SEA CoastLow-Ambient Pressure Switch SoundCombination Ratings Combination Ratings Coils + 315A,JAV060110 VARIABLE-SPEED Furnace Coils + 315A,JAV060120 VARIABLE-SPEED Furnace 030-F Coils + 315A,JAV066110 VARIABLE-SPEED Furnace CC5A/CD5AC048 CK5PA042 39,000 CC5A/CD5AA060 CK5A/CK5BA060 CK5PX060 46,000 Tested combination Evap Condenser Entering AIR Temperatures F Detailed Cooling CapacitiesCFM EWB Coils + 355MAV042040 Variable Speed Furnace Coils + 355MAV042060 Variable Speed FurnaceCoils + 355MAV042080 Variable Speed Furnace Coils + 315A,JAV036070 Variable Speed FurnaceCoils + 315A,JAV048090 Variable Speed Furnace Coils + 315A,JAV060110 Variable Speed FurnaceCoils + 315A,JAV066135 Variable Speed Furnace Coils + 315A,JAV066155 Variable Speed FurnaceCoils + Variable Speed FurnaceCoils + 355MAV060100 Variable Speed Furnace Coils + 355MAV060120 Variable Speed Furnace552AN030-F Outdoor Section With CK5A/CK5BA036 Indoor Section 105 115 125 Capacity Total 29.4 26.4 Coils + 315A,JAV066110 Variable Speed Furnace23.1 26.5 21.6 552AN042-F Outdoor Section With CK5A/CK5BA048 Indoor Section CD5AA 552AN048-F Outdoor Section With CK5A/CK5BA060 Indoor Section 32.3 39.5 31.1 34.7 29.2 552AN060-F Outdoor Section With CK5A/CK5BA060 Indoor Section SST Condenser Entering AIR Temperatures F Condenser only RatingsCondenser only Ratings System Design Summary Guide Specifications General