Bryant 552A warranty Low-Ambient Pressure Switch, Sound

Page 7

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued

10.Low-Ambient Pressure Switch

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F (–17.8°C) when properly installed.

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

11.MotorMaster® Control

A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ± 10°F (37.8°C ± 5.6°C).

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

All commercial installations.

12.Outdoor Air Temperature Sensor

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.

SUGGESTED USE: All Bryant programmable thermostats.

13.Piston Body

This piston body is to be used as a replacement for the FK4C Fan Coil R-22 thermostatic expansion valve when used with Puron® (R-410A) air conditioner

units. Use piston and piston ring shipped with outdoor unit for installations under 50 ft. SUGGESTED USE: All Puron® air conditioner installations matched with FK4C Fan Coils.

14.Support Feet

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion.

SUGGESTED USE: For improved sound ratings.

Coastal installations.

Windy areas or where debris is normally circulating.

Rooftop installations.

15.Thermostatic Expansion Valve (TXV)

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve and adapter tubes.

SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. Required for use on all zoning systems.

16.Time-Delay Relay

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.

SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. Required for use on all zoning systems.

17.Winter Start Control

An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load

conditions.

SUGGESTED USE: All air conditioners where Low-Ambient Controller has been added.

SOUND POWER (A-wtd., non-pure tone corrected.)

 

SOUND

 

 

OCTAVE BAND CENTER FREQUENCY (Hz)

 

 

UNIT

LEVEL

 

 

 

 

 

 

 

 

 

 

 

SIZE-SERIES

(dBA)

125

250

500

1000

2000

4000

8000

018-F

72

67.0

69.0

69.0

67.0

63.0

55.5

49.5

024-F

69

54.0

60.5

63.5

63.0

59.0

55.5

48.5

 

 

 

 

 

 

 

 

 

024-G

74

57.0

66.0

68.0

67.0

65.0

62.0

51.5

 

 

 

 

 

 

 

 

 

030-F

70

57.0

61.5

64.5

65.0

63.0

59.5

53.0

036-F, G

73

60.0

64.0

66.5

68.5

66.0

62.0

53.5

 

 

 

 

 

 

 

 

 

042-F

73

57.5

63.5

67.0

68.0

65.5

62.0

55.0

 

 

 

 

 

 

 

 

 

048-F

76

63.0

66.0

67.0

70.5

67.0

62.5

55.0

060-F

78

63.0

67.5

69.5

72.5

68.5

64.5

58.5

NOTE: Tested in accordance with ARI Standard 270.95. (Not listed with ARI.)

—7—

Image 7
Contents 552A 60 Hz Unit Dimensions Minimum Mounting Size DimensionsUnit SIZE-SERIES Required Subcooling F UnitPiston Identification noElectrical SpecificationsSpecifications Required for LOW-AMBIENT LONG-LINE SEA Coast Accessory Usage GuidelineSound Low-Ambient Pressure SwitchCombination Ratings Combination Ratings Coils + 315A,JAV060110 VARIABLE-SPEED Furnace Coils + 315A,JAV060120 VARIABLE-SPEED Furnace 030-F Coils + 315A,JAV066110 VARIABLE-SPEED Furnace CC5A/CD5AC048 CK5PA042 39,000 CC5A/CD5AA060 CK5A/CK5BA060 CK5PX060 46,000 Tested combination Detailed Cooling Capacities Evap Condenser Entering AIR Temperatures FCFM EWB Coils + 315A,JAV036070 Variable Speed Furnace Coils + 355MAV042040 Variable Speed FurnaceCoils + 355MAV042060 Variable Speed Furnace Coils + 355MAV042080 Variable Speed FurnaceCoils + 315A,JAV066155 Variable Speed Furnace Coils + 315A,JAV048090 Variable Speed FurnaceCoils + 315A,JAV060110 Variable Speed Furnace Coils + 315A,JAV066135 Variable Speed FurnaceCoils + 355MAV060120 Variable Speed Furnace Coils +Variable Speed Furnace Coils + 355MAV060100 Variable Speed Furnace552AN030-F Outdoor Section With CK5A/CK5BA036 Indoor Section 105 115 125 Capacity Total Coils + 315A,JAV066110 Variable Speed Furnace 29.4 26.423.1 26.5 21.6 552AN042-F Outdoor Section With CK5A/CK5BA048 Indoor Section CD5AA 552AN048-F Outdoor Section With CK5A/CK5BA060 Indoor Section 32.3 39.5 31.1 34.7 29.2 552AN060-F Outdoor Section With CK5A/CK5BA060 Indoor Section Condenser only Ratings SST Condenser Entering AIR Temperatures FCondenser only Ratings System Design Summary General Guide Specifications
Related manuals
Manual 12 pages 37.09 Kb