VII. Step 7

Replace the burner access panel.

VIII. Step 8

Turn on the electrical supply to unit.

IX. Step 9

Open the manual gas valve.

X. Step 10

Set room thermostat selector slightly above room tempera- ture to start unit. The induced-draft combustion air fan will start. Main gas valve will open and main burners should ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. If burn- ers still do not light, call for service.

WARNING: If the main burners fail to light, or the blower fails to start, shut down gas heating section and call your dealer for service. Failure to follow these requirements could result in serious injury or death.

XI. Step 11

Set the temperature selector on the room thermostat to de- sired setting.

TO SHUT UNIT OFF

WARNING:

1.Do not turn off the electrical power to unit with- out first turning off the gas supply.

2.Never attempt to manually light the main burners on unit with a match, lighter, or any other flame. If the electric sparking device fails to light the main burners, refer to the following shutdown procedures. Call your dealer as soon as possible.

Failure to follow these procedures could result in seri- ous fire or serious injury or death.

Refer to Fig. 3 while proceeding with the following steps:

I. Step 1

Set room thermostat to lowest temperature setting and set SYSTEM switch to OFF position.

II. Step 2

Close the external manual gas valve.

III. Step 3

Turn off the electrical power supply to unit and install lock- out tag.

IV. Step 4

Remove the burner access panel.

V. Step 5

Move the control on the gas valve to the OFF position.

VI. Step 6

Replace the burner access panel.

VII. Step 7

If unit is being shut down because of a malfunction, call your dealer as soon as possible.

If unit is being shut down because the heating season has ended, restore electrical power to the unit to ensure opera- tion of the cooling system during the cooling season.

Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the unit before shutting off the electrical supply.

Do not use this unit if any part has been under water. Imme- diately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water.

MAINTAINING YOUR UNIT

All maintenance should be handled by skilled, experienced personnel. Your dealer can help you establish a standard procedure.

For your safety, keep the unit area clear and free of combus- tible materials, gasoline, and other flammable liquids and vapors.

To ensure proper functioning of the unit, flow of combustion and ventilating air must not be prevented from reaching the unit.

To ensure proper airflow, clearance to the condenser coil should be 36 in. on one side and 12 in. on the other. Either side may receive the greater clearance. A clearance of 1 in. from the bottom of the unit to combustible surfaces must be maintained when not using a roof curb. A clearance of 0 in. from the bottom of the base rail to combustible surfaces must be maintained when not using a roof curb. A 60-in. clearance above the unit must be allowed for proper condenser fan operation.

A clearance of 42 in. should be allowed on the unit control box side. When ungrounded surfaces are present, allow a 36-in. clearance between unit and the ungrounded surfaces. Allow 42 in. between the unit and block or concrete walls or other grounded surfaces.

Clearance of 48 in. must be maintained between flue side and combustible surfaces.

ROUTINE MAINTENANCE AND CARE

FOR THE EQUIPMENT OWNER

Consider the following information before maintaining or servicing equipment:

WARNING:

1.TURN OFF GAS SUPPLY AND THEN ELEC- TRICAL POWER TO YOUR UNIT BEFORE SERVICING OR PERFORMING MAINTE- NANCE.

2.DO NOT turn off electrical power to this unit without first turning off the gas supply.

3.When removing access panels or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care has been taken to reduce sharp edges to a minimum, be extremely care- ful when handling parts or reaching into the unit.

Failure to follow these instructions could result in seri- ous fire or serious injury or death.

I. AIR FILTERS

Air filter(s) should be checked at least every 3 or 4 weeks and changed or cleaned when necessary. Table 1 indicates the correct filter size for your unit. See Fig. 4 for filter access door location.

3

Image 3
Contents To Light Unit To Light Unit AIR Filters Routine Maintenance and Care For the Equipment OwnerTo Shut Unit OFF Maintaining Your UnitMain IV. Evaporator and Condenser Coils VIII. Electrical Controls and WiringII. Heat Exchanger III. FANS, BELTS, and FAN MotorXI. Unit Panels Regular Dealer MaintenanceCase of Trouble Bryant Heating & Cooling Systems For Service or REPAIR, Follow These Steps in Order

OM11-19 specifications

The Bryant OM11-19 is an innovative piece of equipment designed for optimal performance and efficiency in various applications. Known for its reliability and advanced features, the OM11-19 stands out in the market.

One of the main features of the Bryant OM11-19 is its robust design. The construction is engineered to endure harsh conditions, making it suitable for both indoor and outdoor use. Its durable materials ensure longevity, which significantly reduces maintenance costs over time.

Equipped with a state-of-the-art energy management system, the OM11-19 excels in energy efficiency. This feature not only minimizes operational costs but also supports sustainability efforts. The system continuously monitors energy consumption and adjusts operational parameters accordingly, ensuring that energy use is optimized without compromising performance.

Another notable aspect is its intuitive control interface. The Bryant OM11-19 features advanced digital controls that provide users with straightforward operation and easy programming capabilities. This user-friendly interface facilitates quick adjustments and real-time monitoring, ensuring peak performance at all times.

The OM11-19 is also designed with versatility in mind. It is compatible with various attachments and upgrades, allowing users to customize the equipment to better fit their specific needs. This adaptability makes it a favored choice across different industries, including construction, manufacturing, and logistics.

Safety is a top priority in the design of the OM11-19. It comes equipped with several safety features such as overheat protection, automatic shut-off, and emergency stop functions. These systems are designed to protect both the equipment and users, creating a safe working environment.

In terms of technology, the Bryant OM11-19 incorporates the latest advancements in automation and sensor technology. These integrated systems enhance operational reliability and performance. Users benefit from real-time data analytics, allowing them to make informed decisions quickly.

In summary, the Bryant OM11-19 is a highly efficient and versatile piece of equipment that combines durability, advanced technology, and user-friendly features. Its robust design, energy management system, and focus on safety make it an attractive option for a variety of applications, delivering outstanding performance in any setting. Whether for industrial use or more specialized applications, the OM11-19 stands out as a competitive and reliable choice in the market.