DRAIN CONNECTIONS

All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection.

The drain pan connections are designed to ASTM Standard D 2466 Schedule 40. 3/4" PVC is preferred. Since the drains are not subject to any pressure it is not necessary to use Schedule 40 pipe for drain lines.

It is recommended that all drain connections be sealed with teflon tape or equivalent.

Threaded drain connection should be hand-tightened, plus no more than one turn.

Horizontal drain cutout in the center access panel should be removed by using a utility knife. DO NOT TRY TO KNOCK OUT.

Route the drain line so that it does not interfere with accessibility to the coil, air handling system or filter and will not be exposed to freezing temperatures. See Figures 2, 3 and 4.

NOTE: When the coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil as is specified by most local building codes.

Coils should be installed level or pitched slightly toward the drain end. Suggested pitch should not exceed 1/4 inch per foot of coil.

The coil is provided with a secondary drain that should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain is not used it must be capped.

MAINTENANCE

Filters must be cleaned or replaced when they become dirty. Inspect at least once per month. The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions. Clean filters keep unit efficiency high.

COIL CLEANING

If the coil needs to be cleaned or replaced, it should be washed with Calgon CalClean (mix one part CalClean to ten parts water). Allow solu- tion to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted sur- faces.

LUBRICATION

The bearings of the blower motor are permanently lubricated.

CONDENSATE DRAINS

During the cooling season check the condensate drain lines to be sure that condensate is flowing from the primary drain but not from the sec- ondary drain. If condensate ever flows from the secondary drain the unit should be promptly shut off and the condensate pan and drains cleaned to insure a free flowing primary drain.

 

 

TROUBLESHOOTING GUIDE

 

 

 

PROBLEM

 

POSSIBLE CAUSE

 

 

 

 

1.

No heat units do not have 6-pin connector installed.

 

2.

Limit open or not connected.

Blower Runs all of the time

3. Variable speed break-out tab broken out.

 

4.

Blower OFF delay (approx. 1 min).

 

5.

Thermostat fan switch in “ON” position.

 

 

Blown Fuse

1. Low voltage short to C or ground from R, Y, G, W, or O.

 

1.

4-pin connector loose.

No 24V

2. Loose wire from control to transformer (24V and 230V).

 

3.

Blown fuse on control board.

 

 

 

No 2nd stage heat

1.

Check 6-pin connector and connections to panel mount relays.

2.

Verify that both W1 & W2 are connected at the terminal strip.

 

 

 

 

 

1.

Check filter.

 

2.

Closed registers.

No Heat or Limited Heating

3. Restricted airflow (supply registers or return registers)

 

4.

Check blower motor operation.

 

5.

If the safety limit opens 4 times, the control will not permit the heating element to operate for 1 hour.

 

 

 

Subject to change without notice. Printed in U.S.A.

292043-UIM-B-0707

Copyright © by York International Corp. 2007. All rights reserved.

Supersedes: 292043-UIM-A-0507

Unitary

5005

Norman

Product

York

OK

Group

Drive

73069

Image 16
Contents Installation Manual Specific Safety Rules and Precautions Safety RequirementsGeneral Information InspectionHorizontal Drain PAN Conversion Models F*FP Duct Connections AIR FiltersSuspension Kits Coil Metering DevicesRefrigerant Line Connection UIM-B-0707 Unitary Products Group LOW Voltage Control Connection Line Power ConnectionsBlower Speed Connections KW & MBH Conversions for Total Power Input Requirement Models F*FP036 040 048 060Min. CFM Max. Static Total Heat2W1 Only W2 Only W1 + W2 75C Wire Size AWG Min. Circuit AmpacityHeater ModelMax. Static Total Heat W1 OnlyStatic Tap 208 240 208V 240VAirflow Data for 230 Volt Heat Pump Models1 High 950 910835 775 730 590 502 400 F4FP024H06T2 Med 845 815Blower Motor Volt Series Maintenance Coil CleaningTroubleshooting Guide Drain Connections

F*FP specifications

The Coleman F*FP, an innovative product from the renowned outdoor gear manufacturer Coleman, represents a significant leap forward in portable lighting solutions. Designed for outdoor enthusiasts, campers, and emergency preparedness, this compact device merges functionality with cutting-edge technology.

One of the standout features of the Coleman F*FP is its impressive brightness, which can easily illuminate small campsites or provide adequate light for activities such as cooking or reading after sunset. With adjustable brightness settings, users can customize the light output according to their specific needs, effectively conserving battery life when full brightness isn’t necessary.

The Coleman F*FP incorporates advanced LED technology, ensuring longevity and efficiency. Unlike traditional incandescent bulbs, the LEDs offer a much longer lifespan and consume significantly less power, making them an ideal choice for outdoor use where access to electricity may be limited. This energy-efficient design makes the F*FP not only cost-effective but also environmentally friendly.

Portability is another key characteristic of the Coleman F*FP. The device is lightweight and compact, making it easy to pack and transport, whether you're heading on a weekend camping trip or preparing for an emergency situation. It typically features a built-in handle or a hook for easy hanging, allowing for versatile placement in tents, trees, or outdoor structures.

Durability is paramount when it comes to outdoor equipment, and the Coleman F*FP does not disappoint. Constructed with weather-resistant materials, it can withstand various environmental conditions, from rain to dust, ensuring reliable performance and longevity. This rugged construction makes it a trustworthy companion for any outdoor adventure.

The F*FP also includes user-friendly features such as easy-to-navigate controls and battery indicators. Some models may offer rechargeable options, reducing the need for disposable batteries and enhancing sustainability.

In summary, the Coleman F*FP stands out in the realm of outdoor lighting solutions. Its impressive brightness, energy-efficient LED technology, portability, and durable construction make it an essential tool for adventurers and a sensible choice for emergency preparedness. With the Coleman F*FP in tow, users can enjoy peace of mind and a well-lit experience in the great outdoors.