Bryant 591B Accessory Usage, Outdoor Unit Connected to FACTORY- Approved Indoor Unit

Page 4

TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

UNIT SIZE

LIQUID

 

VAPOR

 

VAPOR (LONG LINE)

Connection Diameter

 

Tube Diameter

Connection Diameter

 

Tube Diameter

Connection Diameter

Tube Diameter

 

 

 

018, 024

3/8

 

3/8

5/8

 

5/8

5/8

3/4

030, 036

3/8

 

3/8

3/4

 

3/4

3/4

7/8

042, 048

3/8

 

3/8

7/8

 

7/8

7/8

1-1/8

060

3/8

 

3/8

7/8

 

1-1/8

7/8

1-1/8

 

 

 

 

 

 

 

 

 

NOTES:

1.Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual—Air Conditio ners and Heat Pumps Using Puron®.

2.Do not apply capillary tube indoor coils to these units.

TABLE 2—ACCESSORY USAGE

 

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

ACCESSORY

LOW-AMBIENT

LONG-LINE

SEA COAST

APPLICATIONS

APPLICATIONS*

APPLICATIONS

 

 

(BELOW 55°F)

(OVER 50 FT)

(WITHIN 2 MILES)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Yes

Yes

No

Capacitor and Relay

 

 

 

MotorMaster® Control,

 

 

 

or

Yes

No

No

Low-Ambient Pressure Switch

 

 

 

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

 

 

 

or

No

See Long-Line Application Guideline

No

Hard Shutoff TXV

 

 

 

Ball Bearing Fan Motor

Yes‡

No

No

*For Tubing Sets between 50 and 175 ft horizontal or 20 ft vertical differential, refer to the Application Guideline and Service Manual—Air Condition ers and Heat Pumps Using Puron®.

† Only when low-pressure switch is used.

‡ Required for low-ambient controller (full modulation feature) and MotorMaster® Control only.

CAUTION: To prevent improper performance and/or unit component failures, do not leave system open to atmosphere any longer than minimum required for instal- lation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.

CAUTION: To prevent improper performance or equip- ment failure this caution must be followed. If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. Do not bury lines over 36 in. in length.

CAUTION: To prevent damage to unit or service valves observe the following:

• Use a brazing shield.

Wrap service valves with wet cloth or use a heat sink material.

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft, substan- tial capacity and performance losses can occur. Following the recommendations in the Application Guideline and Service

—4—

Manual—Air Conditioners and Heat Pumps Using Puron® Refrig- erant will reduce these losses. Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.

There are no buried-line applications greater than 36 in.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

A. OUTDOOR UNIT CONNECTED TO FACTORY- APPROVED INDOOR UNIT

Factory refrigerant charge is for a 15 ft line set. Outdoor unit contains correct system refrigerant charge for operation with ARI rated indoor unit. Check refrigerant charge for maximum effi- ciency. The charge must be adjusted based on the actual line set length. Add or subtract 0.6 oz/ft for line sets longer or shorter than 15 ft.

B. INSTALL LIQUID-LINE FILTER DRIER

CAUTION: To avoid performance loss and compressor failure, installation of filter drier in liquid line is required.

Refer to Fig. 6 and install filter drier as follows:

1.Braze 5-in. connector tube to liquid service valve. Wrap filter drier with damp cloth.

2.Braze filter drier between connector tube and liquid tube to indoor coil. Flow arrow must point towards indoor coil.

Image 4
Contents Installation Recommendations Safety ConsiderationsInstallation II. Install on a SOLID, Level Mounting PAD Dimensions→ VI. Install TXV Check Equipment and JOB Site Unpack UnitReplacing TXV on R-22 Indoor Coil Installing TXV in Place of PistonVII. Make Piping Connections Install LIQUID-LINE Filter Drier Accessory UsageOutdoor Unit Connected to FACTORY- Approved Indoor Unit Refrigerant Tubing Sweat ConnectionEvacuate Refrigerant Tubing and Indoor Coil VIII. Make Electrical ConnectionsRoute Ground and Power Wires Connect Ground and Power WiresConnect Control Wiring Install Electrical AccessoriesRequired LIQUID-LINE Temperature F Cooling only ProcedureUnits with Cooling Mode Puron TXV Units with Indoor PistonsCare and Maintenance Required SUCTION-LINE TemperatureSuperheat Charging XIII. Final ChecksTypical 24v Circuit Connections J1 Jumper Puron R-410A Quick Reference Guide

591B specifications

The Bryant 591B is a high-efficiency gas furnace designed to deliver comfort, reliability, and energy savings to homeowners. It stands out in the market for its advanced features and innovative technologies, making it a preferred choice for many.

One of the key features of the Bryant 591B is its two-stage heating capability. This technology allows the furnace to operate at a lower capacity during milder conditions, leading to improved fuel efficiency and consistent comfort levels. When the temperature drops significantly, the furnace shifts to its higher capacity, ensuring your home remains warm and cozy even in extreme weather.

The furnace is equipped with a variable-speed blower motor. This advanced motor allows for quieter operation and enhanced airflow throughout the home. With the ability to adjust speed based on the heating requirements, it not only contributes to better temperature consistency but also improves indoor air quality by facilitating increased filtration cycles.

In terms of energy efficiency, the Bryant 591B has impressive AFUE (Annual Fuel Utilization Efficiency) ratings, which can reach up to 95%. This translates to substantial savings on energy bills, making it an eco-friendly choice as well. The higher the AFUE rating, the more efficient the furnace is at converting fuel into heat, and Bryant has engineered this unit to perform at the top of its class.

Another significant characteristic is the furnace's compatibility with the Bryant Housewise thermostat. This smart thermostat provides users with enhanced control over their home heating, allowing for customized scheduling and remote access. This technology helps optimize energy usage while maintaining comfort, ensuring that you only heat your space when needed.

Additionally, the 591B is designed with a durable cabinet that minimizes noise and enhances performance. Insulated for sound, this furnace operates quietly in the background without disrupting daily life. Furthermore, its compact design allows for ease of installation in tight spaces, making it suitable for various home configurations.

Overall, the Bryant 591B offers a blend of efficiency, technology, and innovative features. Its two-stage heating, variable-speed blower motor, high AFUE ratings, and compatibility with smart thermostats provide both homeowners and contractors with an advanced heating solution that prioritizes comfort, efficiency, and user convenience. With the Bryant 591B, you can expect reliable warmth throughout the winter months while enjoying lower energy costs and a decreased environmental footprint.