Bryant 591B Installing TXV in Place of Piston, Replacing TXV on R-22 Indoor Coil

Page 3

INSTALLING TXV IN PLACE OF PISTON

1.Pump system down to 2 psig and recover refrigerant.

2.Remove hex nut from piston body. Use backup wrench on fan coils.

3.Remove and discard factory-installed piston. Be sure teflon seal is in place.

4.Reinstall hex nut. Finger tighten nut plus 1/2 turn.

NOTE: If the piston is not removed from the body, TXV will not function properly.

CAUTION: To prevent damage to the unit, use a brazing shield and wrap TXV with wet cloth or use heat sink

10 O'CLOCK

2 O'CLOCK

STRAP

SUCTION TUBE

8 O'CLOCK

78 IN. OD & SMALLER

SENSING BULB

4O'CLOCK

LARGER THAN 78 IN. OD

material.

5.Install TXV on indoor coil liquid line. Sweat swivel adapter to inlet of indoor coil and attach to TXV outlet. Use backup wrench to avoid damage to tubing or valve. Sweat inlet of TXV, marked “IN” to liquid line. Avoid excessive heat which could damage valve.

6.Install vapor elbow with equalizer adapter to suction tube of line set and suction connection to indoor coil. Adapter has a 1/4-in. male connector for attaching equalizer tube.

7.Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor line adapter.

8.Attach TXV bulb to horizontal section of suction line using clamps provided. Insulate bulb with field-supplied insula- tion tape. See Fig. 5 for correct positioning of sensing bulb.

9.Proceed with remainder of unit installation.

REPLACING TXV ON R-22 INDOOR COIL

1.Pump system down to 2 psig and recover refrigerant.

2.Remove coil access panel and fitting panel from front of cabinet.

PISTON

RETAINER

PISTON

RING

PISTON

PISTON

BODY

FIELD

CONNECTION

STRAINER

FLARE

ADAPTER

LIQUID LINE STRAINER

APPROX 2” LONG

STRAINER LABEL

(AFFIX TO LIQ. LINE

NEAR STRAINER LOCATION

A01019

Fig. 4—Check-Flo-Rater® Components (550A, 552A, 591B Only)

—3—

A81032

Fig. 5—Position of Sensing Bulb

3.Remove TXV support clamp using a 5/16-in. nut driver. Save the clamp.

4.Remove R-22 TXV using a backup wrench on flare connections to prevent damage to tubing.

5.Using wire cutters, cut equalizer tube off flush with vapor tube inside cabinet.

6.Remove bulb from vapor tube inside cabinet.

7.Braze equalizer stub-tube closed. Use protective barrier as necessary to prevent damage to drain pan.

IMPORTANT: Route the equalizer tube of Puron® TXV through suction line connection opening in fitting panel prior to replacing fitting panel around tubing.

8.Install TXV with 3/8-in. copper tubing through small hole in service panel. Use wrench and backup wrench, to avoid damage to tubing or valve, to attach TXV to distributor.

9.Reinstall TXV support clamp (removed in item 3).

10.Attach TXV bulb to vapor tube inside cabinet, in same location as original was when removed, using supplied bulb clamps (nylon or copper). See Fig. 5 for correct positioning of sensing bulb.

11.Route equalizer tube through suction connection opening (large hole) in fitting panel and install fitting panel in place.

12.Sweat inlet of TXV, marked “IN” to liquid line. Avoid excessive heat which could damage valve.

13.Install vapor elbow with equalizer adapter to vapor line of line set and vapor connection to indoor coil. Adapter has a 1/4-in. male connector for attaching equalizer tube.

14.Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor line adapter. Use backup wrench to prevent damage to equalizer fitting.

15.Proceed with remainder of unit installation.

CAUTION: To avoid improper performance and pos- sible equipment failure, remove indoor coil piston if unit is to be installed on system with a TXV metering device.

VII. MAKE PIPING CONNECTIONS

WARNING: Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.

Image 3
Contents Safety Considerations Installation RecommendationsInstallation Check Equipment and JOB Site Unpack Unit II. Install on a SOLID, Level Mounting PADDimensions → VI. Install TXVInstalling TXV in Place of Piston Replacing TXV on R-22 Indoor CoilVII. Make Piping Connections Accessory Usage Install LIQUID-LINE Filter DrierOutdoor Unit Connected to FACTORY- Approved Indoor Unit VIII. Make Electrical Connections Refrigerant TubingSweat Connection Evacuate Refrigerant Tubing and Indoor CoilInstall Electrical Accessories Route Ground and Power WiresConnect Ground and Power Wires Connect Control WiringUnits with Indoor Pistons Required LIQUID-LINE Temperature FCooling only Procedure Units with Cooling Mode Puron TXVXIII. Final Checks Care and MaintenanceRequired SUCTION-LINE Temperature Superheat ChargingTypical 24v Circuit Connections J1 Jumper Puron R-410A Quick Reference Guide

591B specifications

The Bryant 591B is a high-efficiency gas furnace designed to deliver comfort, reliability, and energy savings to homeowners. It stands out in the market for its advanced features and innovative technologies, making it a preferred choice for many.

One of the key features of the Bryant 591B is its two-stage heating capability. This technology allows the furnace to operate at a lower capacity during milder conditions, leading to improved fuel efficiency and consistent comfort levels. When the temperature drops significantly, the furnace shifts to its higher capacity, ensuring your home remains warm and cozy even in extreme weather.

The furnace is equipped with a variable-speed blower motor. This advanced motor allows for quieter operation and enhanced airflow throughout the home. With the ability to adjust speed based on the heating requirements, it not only contributes to better temperature consistency but also improves indoor air quality by facilitating increased filtration cycles.

In terms of energy efficiency, the Bryant 591B has impressive AFUE (Annual Fuel Utilization Efficiency) ratings, which can reach up to 95%. This translates to substantial savings on energy bills, making it an eco-friendly choice as well. The higher the AFUE rating, the more efficient the furnace is at converting fuel into heat, and Bryant has engineered this unit to perform at the top of its class.

Another significant characteristic is the furnace's compatibility with the Bryant Housewise thermostat. This smart thermostat provides users with enhanced control over their home heating, allowing for customized scheduling and remote access. This technology helps optimize energy usage while maintaining comfort, ensuring that you only heat your space when needed.

Additionally, the 591B is designed with a durable cabinet that minimizes noise and enhances performance. Insulated for sound, this furnace operates quietly in the background without disrupting daily life. Furthermore, its compact design allows for ease of installation in tight spaces, making it suitable for various home configurations.

Overall, the Bryant 591B offers a blend of efficiency, technology, and innovative features. Its two-stage heating, variable-speed blower motor, high AFUE ratings, and compatibility with smart thermostats provide both homeowners and contractors with an advanced heating solution that prioritizes comfort, efficiency, and user convenience. With the Bryant 591B, you can expect reliable warmth throughout the winter months while enjoying lower energy costs and a decreased environmental footprint.