Bryant 569C installation instructions Electrical Data, Ð8Ð

Page 8

Table 4 Ð Electrical Data

UNIT

NOMINAL VOLTAGE

VOLTAGE RANGE

COMPRESSOR

OFM

POWER SUPPLY

(V-Ph-Hz)

Min

Max

RLA

LRA

FLA

MCA

MOCP

 

 

208/230-3-60

187

254

21.8

142

1.9

25.6

35

569C072

460-3-60

414

508

9.6

72

1.0

12.9

15

575-3-60

518

632

7.6

58

1.9

11.4

15

 

220-3-50

198

242

19.0

142

1.0

25.6

35

 

400-3-50

360

440

9.5

72

1.0

12.9

15

 

208/230-3-60

187

254

28.8

195

3.8

39.8

45

569C090

460-3-60

414

508

14.7

95

1.9

20.3

20

575-3-60

518

632

10.8

80

1.9

15.4

15

 

220-3-50

198

242

28.8

195

1.5

37.5

45

 

400-3-50

360

440

14.7

90

1.5

19.9

20

 

208/230-3-60

187

254

37.8

239

3.1

46.2

60

569C120

460-3-60

414

508

17.2

125

1.4

22.7

30

575-3-60

518

632

12.3

80

1.4

19.3

25

 

220-3-50

198

242

37.8

239

1.4

46.2

60

 

400-3-50

360

440

17.2

114

1.4

22.7

30

 

208/230-3-60

187

254

31.5

160

3.1

42.5

50

 

380-3-60

342

418

19.0

75

2.2

26.0

35

576B090

460-3-60

414

508

15.7

80

1.4

21.0

25

575-3-60

518

632

12.6

64

1.4

17.2

20

 

 

220-3-50

198

253

31.5

160

1.4

42.5

50

 

400-3-50

342

460

15.7

80

1.4

21.0

25

 

208/230-3-60

187

254

39.7

198

3.1

52.7

70

 

380-3-60

342

418

24.0

93

2.2

32.2

40

576B102

460-3-60

414

508

19.9

99

1.4

26.3

35

575-3-60

518

632

15.9

79

1.4

21.3

25

 

 

220-3-50

198

253

39.7

198

1.4

52.7

70

 

400-3-50

342

460

19.9

99

1.4

26.3

35

 

208/230-3-60

187

254

39.7

198

3.1

52.7

70

 

380-3-60

342

418

24.0

93

2.2

32.2

40

576B120

460-3-60

414

508

19.9

99

1.4

26.3

35

575-3-60

518

632

15.9

79

1.4

21.3

25

 

 

220-3-50

198

253

39.7

198

1.4

52.7

70

 

400-3-50

342

460

19.9

99

1.4

26.3

35

LEGEND

Example: Supply voltage is 460-3-60.

CSA

Ð Canadian Standards Association

FLA

Ð Full Load Amps

HACR

Ð Heating, Air Conditioning and Refrigeration

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

NEC

Ð National Electrical Code (U.S.A. Standard)

OFM

Ð Outdoor (Condenser) Fan Motor

RLA

Ð Rated Load Amps

=

1371

3

UL

Ð Underwriters' Laboratories

= 457

(AB) 457 - 452 = 5 v (BC) 464 - 457 = 7 v

(AC) 457 - 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance

% Voltage Imbalance = 100 x

7

NOTES:

1.In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the over- current protective device for the unit shall be fuse or HACR breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance.

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maxi- mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

3.The 575-v units are CSA only.

4.The 380-v units are not UL or CSA listed.

= 100 x

max voltage deviation from average voltage

average voltage

Ð8Ð

Image 8
Contents Important Ðread Before Installing ContentsSafety Considerations InstallationLocate the Unit II. RIG and Place UnitIII. Compressor Mounting IV. Unit Refrigerant Piping ConnectionsÐ Specications English Ð3ÐÐ Specications SI Ð4ÐBase Unit Dimensions Ð5ÐField Power Supply Fig Refrigerant Piping SizesLiquid Line Data Electrical ConnectionsÐ7Ð Electrical Data Ð8ÐVI. Accessory Installation Accessory ListPRE-START-UP Ð9ÐSTART-UP START-UP and Adjustments Care and MaintenanceService Cleaning Condenser CoilII. Lubrication CompressorsVII. Refrigerant Charge VIII. Refrigerant Service PortsCompressor Removal Cooling Charging Chart Ð 569C072 Troubleshooting Guide Symptom Cause RemedyCAP OFCCLO CompPage Page Copyright 1999 Bryant Heating & Cooling Systems Catalog no Outdoor Unit ControlsIndoor Unit PipingIII. START-UP ÐCL-2Ð