SERVICE
WARNING: When servicing unit, shut off all electri- cal power to unit to avoid shock hazard or injury from rotating parts.
I. CLEANING
Inspect unit interior at the beginning of each cooling season and as operating conditions require.
A. Condenser Coil
Inspect coil monthly. Clean condenser coil annually, and as required by location and
Clean coil as follows:
1.Turn off unit power.
2.Remove and save top panel screws on condensing unit.
3.Remove condenser coil corner post. See Fig. 9. To hold top panel open, place coil corner post between top panel and side panel. See Fig. 10.
4.Remove bracket holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. (75 to 100 mm) from the inner coil sec- tion. See Fig. 11.
5.Use a water hose or other suitable equipment to ¯ush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
6.Reposition the outer coil section, attach the bracket re- moved in Step 4, and remove the coil corner post from between the top panel and side panel. Secure the sec- tions together. Install the coil corner post and replace all screws (removed in Step 2).
II.LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at the factory. Refer to the Oil Charge section on page 10 for ad- ditional information.
B. Fan Motor Bearings
Fan motor bearings are of the
Fig. 9 Ð Cleaning Condenser Coil
Fig. 10 Ð Propping Up Top Panel
Fig. 11 Ð Separating Coil Sections
III.CONDENSER-FAN ADJUSTMENT (Fig. 12)
1.Shut off unit power supply.
2.Remove
3.Loosen fan hub setscrews.
4.Adjust fan height as shown in Fig. 12.
5.Tighten set screws.
6.Replace
NOTE: Fan height adjustments are as follows:
UNIT | in. | mm | |
569C072 | 4.50 | 114 | |
All Units | 6.42 | 163 | |
(except 569C072) | |||
|
|
Fig. 12 Ð Outdoor (Condenser) Fan Adjustment
Ð11Ð