SERVICE

WARNING: When servicing unit, shut off all electri- cal power to unit to avoid shock hazard or injury from rotating parts.

I. CLEANING

Inspect unit interior at the beginning of each cooling season and as operating conditions require.

A. Condenser Coil

Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor-air conditions.

Clean coil as follows:

1.Turn off unit power.

2.Remove and save top panel screws on condensing unit.

3.Remove condenser coil corner post. See Fig. 9. To hold top panel open, place coil corner post between top panel and side panel. See Fig. 10.

4.Remove bracket holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. (75 to 100 mm) from the inner coil sec- tion. See Fig. 11.

5.Use a water hose or other suitable equipment to ¯ush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.

6.Reposition the outer coil section, attach the bracket re- moved in Step 4, and remove the coil corner post from between the top panel and side panel. Secure the sec- tions together. Install the coil corner post and replace all screws (removed in Step 2).

II.LUBRICATION

A. Compressors

Each compressor is charged with the correct amount of oil at the factory. Refer to the Oil Charge section on page 10 for ad- ditional information.

B. Fan Motor Bearings

Fan motor bearings are of the permanently-lubricated type. No further lubrication is required.

Fig. 9 Ð Cleaning Condenser Coil

Fig. 10 Ð Propping Up Top Panel

Fig. 11 Ð Separating Coil Sections

III.CONDENSER-FAN ADJUSTMENT (Fig. 12)

1.Shut off unit power supply.

2.Remove condenser-fan assembly (grille, motor, motor cover, and fan).

3.Loosen fan hub setscrews.

4.Adjust fan height as shown in Fig. 12.

5.Tighten set screws.

6.Replace condenser-fan assembly.

NOTE: Fan height adjustments are as follows:

UNIT

in.

mm

569C072

4.50

114

All Units

6.42

163

(except 569C072)

 

 

Fig. 12 Ð Outdoor (Condenser) Fan Adjustment

Ð11Ð

Image 11
Contents Installation Important Ðread Before InstallingContents Safety ConsiderationsIV. Unit Refrigerant Piping Connections Locate the UnitII. RIG and Place Unit III. Compressor MountingÐ3Ð Ð Specications EnglishÐ4Ð Ð Specications SIÐ5Ð Base Unit DimensionsElectrical Connections Field Power Supply FigRefrigerant Piping Sizes Liquid Line DataÐ7Ð Ð8Ð Electrical DataÐ9Ð VI. Accessory InstallationAccessory List PRE-START-UPCare and Maintenance START-UP START-UP and AdjustmentsCompressors Service CleaningCondenser Coil II. LubricationVII. Refrigerant Charge VIII. Refrigerant Service PortsCompressor Removal Cooling Charging Chart Ð 569C072 Symptom Cause Remedy Troubleshooting GuideComp CAPOFC CLOPage Page Copyright 1999 Bryant Heating & Cooling Systems Catalog no Piping Outdoor UnitControls Indoor UnitÐCL-2Ð III. START-UP