LV850 LEVEL SENSOR

7.Increase the level until the Level Sensor is immersed in the medium.

8.Minimum Sensor:

Turn the potentiometer screw (E) to (-) until the LED (green) extinguishes. Then slowly turn to (+) until the LED indicates. Adjust the screw a further full turn to (+) to compensate for any tolerance.

9. Maximum Sensor:

Turn the potentiometer screw (E) to (+) until the LED (green) extinguishes. Then slowly turn to (-) until the LED indicates. Adjust the screw a further full turn to (-) to compensate for any tolerance.

10.Replace and tighten the cover (C) or the metal coupling (option).

11.Replace and tighten the cable gland nut (PG7).

The Level Sensor is now connected, adjusted and ready for operation.

5 Operating Difficulties

Problem: The Level Sensor fails to operate correctly.

Solution:

-The surface of the sensor probe should be carefully cleaned from inside the container.

5

Image 9
Contents User’sGuide Servicing North America For immediate technical or application assistanceServicing Europe LV850 Level Sensor LV850 Level Sensor Minimum switching Maximum switchingDescription Technical Data Level Sensor may be installed in any attitude Level Sensor InstallationConnection Operating Difficulties SolutionLV850 Level Sensor WARRANTY/DISCLAIMER Temperature