DETAILED COOLING CAPACITIES* Continued

EVAPORATOR

 

 

 

 

 

 

 

 

 

CONDENSER ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

 

AIR

 

 

75

 

 

 

 

85

 

 

 

 

95

 

 

 

 

105

 

 

 

 

115

 

 

 

 

125

 

 

 

 

 

Capacity

 

Total

 

Capacity

Total

 

Capacity

Total

 

Capacity

Total

Capacity

 

Total

 

Capacity

 

Total

 

 

 

MBtuh†

 

 

MBtuh†

 

MBtuh†

 

MBtuh†

 

MBtuh†

 

 

MBtuh†

 

 

 

 

 

Sys

 

Sys

 

Sys

 

Sys

 

 

Sys

 

 

Sys

CFM

 

EWB

Total

Sens‡

 

KW**

 

Total

Sens‡

KW**

Total

 

Sens‡

KW**

Total

 

Sens‡

KW**

Total Sens‡

 

KW**Total Sens‡

 

KW**

 

 

 

 

 

561C060-A, B, E Outdoor Section With CC5A/CD5AW060 Indoor Section

 

 

 

 

 

 

 

72

66.3

32.0

5.14

 

63.7

31.0

 

5.64

 

61.0

 

30.0

6.20

 

58.1

 

28.9

6.82

55.0

27.8

 

7.50

51.7

26.6

 

8.24

1750

 

67

60.6

40.0

4.96

 

58.1

38.9

 

5.46

 

55.6

 

37.9

6.01

 

52.9

 

36.7

6.63

50.0

35.6

 

7.30

47.1

34.4

 

8.02

 

62

55.2

47.8

4.81

 

52.9

46.7

 

5.30

 

50.6

 

45.5

5.85

 

48.1

 

44.3

6.46

45.4

42.9

 

7.12

42.8

41.5

 

7.80

 

 

 

 

 

 

 

 

 

 

 

 

57

51.8

51.8

4.72

 

50.0

50.0

 

5.22

 

48.2

 

48.2

5.78

 

46.3

 

46.3

6.40

44.2

44.2

 

7.07

42.1

42.1

 

7.77

 

 

72

66.6

32.3

5.17

 

64.0

31.3

 

5.67

 

61.2

 

30.3

6.23

 

58.3

 

29.2

6.85

55.2

28.1

 

7.53

51.9

26.9

 

8.27

1800

 

67

60.8

40.4

4.99

 

58.4

39.4

 

5.48

 

55.8

 

38.3

6.04

 

53.1

 

37.2

6.65

50.2

36.0

 

7.33

47.2

34.8

 

8.05

 

62

55.5

48.4

4.83

 

53.2

47.3

 

5.33

 

50.8

 

46.1

5.88

 

48.2

 

44.8

6.49

45.6

43.5

 

7.14

42.9

42.0

 

7.83

 

 

 

 

 

 

 

 

 

 

 

 

57

52.2

52.2

4.75

 

50.4

50.4

 

5.25

 

48.6

 

48.6

5.81

 

46.6

 

46.6

6.43

44.5

44.5

 

7.11

42.4

42.4

 

7.81

 

 

72

68.1

33.9

5.34

 

65.3

32.9

 

5.83

 

62.4

 

31.8

6.39

 

59.4

 

30.7

7.01

56.1

29.6

 

7.69

52.8

28.4

 

8.43

2100

 

67

62.2

43.1

5.14

 

59.7

42.1

 

5.64

 

57.0

 

41.0

6.20

 

54.2

 

39.8

6.81

51.2

38.6

 

7.48

48.0

37.4

 

8.21

 

62

56.7

52.0

4.98

 

54.4

50.8

 

5.48

 

51.9

 

49.5

6.03

 

49.3

 

48.0

6.64

46.6

46.3

 

7.30

44.1

44.1

 

8.01

 

 

 

 

 

 

 

 

 

 

 

 

57

54.6

54.6

4.93

 

52.7

52.7

 

5.43

 

50.7

 

50.7

5.99

 

48.6

 

48.6

6.62

46.4

46.4

 

7.29

44.1

44.1

 

8.01

 

 

72

68.7

34.6

5.41

 

65.9

33.6

 

5.91

 

62.9

 

32.6

6.47

 

59.8

 

31.4

7.09

56.5

30.3

 

7.77

53.1

29.1

 

8.51

2250

 

67

62.8

44.4

5.22

 

60.2

43.4

 

5.71

 

57.5

 

42.3

6.27

 

54.6

 

41.1

6.89

51.5

39.9

 

7.56

48.3

38.6

 

8.28

 

62

57.3

53.7

5.05

 

54.9

52.4

 

5.55

 

52.4

 

51.0

6.10

 

49.8

 

49.3

6.71

47.2

47.2

 

7.38

44.8

44.8

 

8.11

 

 

 

 

 

 

 

 

 

 

 

 

57

55.6

55.6

5.01

 

53.7

53.7

 

5.51

 

51.6

 

51.6

6.08

 

49.5

 

49.5

6.70

47.2

47.2

 

7.38

44.8

44.8

 

8.11

 

 

 

 

 

 

 

 

 

Multipliers for Determining the Performance With Other Indoor Sections

 

 

 

 

 

 

 

 

 

Indoor

 

 

Unit

 

 

 

 

Cooling

 

 

 

 

 

Indoor

 

 

 

Unit

 

 

 

 

Cooling

 

 

 

 

Section

 

 

Size

 

 

Capacity

 

 

Power

 

 

 

Section

 

 

 

Size

 

 

Capacity

 

 

Power

 

CC5A/CD5AW

 

 

060

 

 

1.00

 

 

 

1.00

 

 

 

FG3AAA

 

 

 

060

 

 

0.99

 

 

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC5A/CD5AA

 

 

060

 

 

0.96

 

 

 

0.97

 

 

 

FK4CNB

 

 

 

006

 

 

1.02

 

 

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CE3AA

 

 

060

 

 

1.01

 

 

 

0.99

 

 

 

 

COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE

 

 

CK3BA

 

 

060

 

 

0.96

 

 

 

1.00

 

 

 

CK3BA

 

 

 

060

 

 

0.96

 

 

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CK5A/CK5BA

 

 

060

 

 

0.96

 

 

 

0.97

 

 

 

CK5A/CK5BA

 

060

 

 

0.96

 

 

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CK5A/CK5BN

 

 

060

 

 

0.96

 

 

 

0.98

 

 

 

CK5A/CK5BX

 

060

 

 

1.00

 

 

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CK5A/CK5BX

 

 

060

 

 

1.00

 

 

 

1.00

 

 

 

 

COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE

 

F(A,B)4AN(F,B)

 

 

060

 

 

1.01

 

 

 

1.05

 

 

 

CK3BA

 

 

 

060

 

 

0.96

 

 

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FB4ANB

 

 

070

 

 

1.02

 

 

 

1.03

 

 

 

CK5A/CK5BA

 

060

 

 

0.96

 

 

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BN(F,B)

 

 

060

 

 

1.00

 

 

 

1.04

 

 

 

CK5A/CK5BX

 

060

 

 

0.96

 

 

 

0.96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC4BNB

 

 

070

 

 

1.02

 

 

 

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.

‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed.

**Unit kw is total of indoor and outdoor unit kilowatts. EWB—Entering Wet Bulb

—24—

Image 24
Contents 561C 60 Hz Dimensions DIMENSIONS-561CUnit Dimensions Minimum Mounting Size CHECK-FLO-RATER Piston Chart Recommended Tube DiametersSpecifications ElectricalSpecifications 561C048-A, B 561C048-B, C 561C060-A, B 561C060-B, E Accessory Usage Guideline Required for LOW-AMBIENT LONG-LINE SEA CoastApplications High-Pressure Switch Low-Pressure SwitchOutdoor Air Temperature Sensor Time-Delay RelayCombination Ratings Combination Ratings Coils + 333B,JAV060120 VARIABLE-SPEED Furnace 10.00 10.10 Enhance Standard Accessory Furnace or Unit IndoorBtuh Ment Rating TDR† Coils +11.50 10.00 Evaporator Condenser Entering AIR Temperatures F CFM EWBCoils + 333B,JAV036060 VARIABLE-SPEED Furnace Detailed Cooling Capacities Coils + 333B,JAV048080 VARIABLE-SPEED Furnace Size Capacity Power Total Sens‡ KW**Total Sens‡Detailed Cooling Capacities CD5AA Coils + 355MAV060080 VARIABLE-SPEED Furnace Indoor Unit Cooling Unit Cooling Section SizeMBtuh† Sys Indoor Unit Cooling Section SizeSection Size Section Size Capacity Power Sens‡ TotalCoils + 333B,JAV060100 VARIABLE-SPEED Furnace SST Condenser Entering AIR Temperatures F Condenser only Ratings561C042-A, B, C System Design General Products