Omega Vehicle Security LDP1XX-21 manual Power SUPPLY, Recommended Wiring, Protection Fuses

Page 9

8.- WIRING

8.1.- POWER SUPPLY, RECOMMENDED WIRING

POWER SUPPLY

115 Vac (230 Vac Optional).

Power switch

FUSE and spare fuse.

8.2.- PROTECTION FUSES

The unit has a protection fuse located on the power supply socket.

If this fuse must be replaced or changed because the power supply is changed, use the time-lag fuse according to IEC 127/2 with the values indicated on the table.

8.3.- SENSOR CONNECTIONS FOR MODEL: MX.

Power

Fuse

Supply

value

 

 

230 Vac

0.2 A

115 Vac

0.4 A

 

 

D

Signal input C connector. B

A

PT-100

PT-100

3-wires connection.

2-wires connection.

Do not forget to link

 

 

terminal A

 

to

 

terminal C.

8.4.- SENSOR CONNECTIONS FOR MODELS: J1,J2,K1,K2,T1,T2,E1,E2,S1,S2,R1,R2 & L1.

D

Signal C input

connector. B

A

+

Thermocouple

_

Page : 8

Image 9
Contents Users Guide LDP-124 and LDP-144 Series For TemperatureUSA Contents Important Safety Considerations Unpacking and Inspection ENGINEERING´S customer service departmentLDP Reference KEYMechanical Main FeaturesConnections Sensor Break DetectionLDP-1X4-MX ModelsDisplay General SpecificationsANALOG-TO-DIGITAL Conversion EnvironmentalPower SUPPLY, Recommended Wiring WiringProtection Fuses Sensor Connections for Model MXSignal Conditioners Temperature RangesSignal Conditioner for RTD Sensor Signal Conditioners for Thermocouple SensorsAdjustment and Calibration Procedure RTD ModelsThermocouple Models Mechanical Dimensions mm inches InstallationReturn REQUESTS/INQUIRIES WARRANTY/DISCLAIMERPRESSURE, Strain and Force TemperatureFLOW/LEVEL Data Acquisition