Charger Location and Connection

The charger must be mounted inside. This device is not weather-proof. Free air flow is required from below and out the top of the unit.

Do not operate charger in a closed-in area or restrict ventilation in any way.

Never place charger directly above battery being charged as gases from battery will corrode and damage charger.

Never allow battery acid to drip on charger when reading specific gravity or filling battery.

The battery charger should be connected to a grounded, metal, permanent wiring system.

Connections to battery charger should comply with all local codes and ordinances.

AC wiring should be run separately from the output of the charger and the alarm wiring. Use two runs of 12 gauge or heavier wire from the charger to the battery. Use 12 gauge or larger wire for input and ground connections.

NOTE: Follow all national and local wiring codes and best practices.

Section 75

00-02-0615

02-29-08

- 3 -

Image 7
Contents Guardian Battery Charger Series Before Beginning Installation of this Murphy Product Table of Contents Page General Safety Instructions Safety InstructionsPrior to Installation / Commissioning Personal PrecautionsCharger Location and Connection Auto Boost Equalizing Operation Temperature CompensationCharge Fail and Alarms General Product InformationDimensions Battery Charged ConditionCurrent Limiting Mounting hole dimensions Installation and Mounting InstructionsTerminal Connection Information Operating InstructionsDisconnection of Batteries Automatic Battery ChargerConnection to Power Supply Connection to BatteriesFuses Over Voltage, Under Voltage, and Charge Fail ConnectionTroubleshooting Output Voltage Current Flow from Charger to BatteryVoltage Rise at Battery Terminals Measuring Charging Voltage and CurrentBattery Life Using Correct Size Battery ChargerFactors Contributing to Electrolyte Loss Charge Specific Gravity Voltage DC on 12V battery Charge Fail Output SpecificationsPower Supply DC Charge OutputSection 00-02-0615 02-29-08