Variable Speed Two-Stage
Thermidistat |
| Fan Coil | Air Conditioner |
|
|
| |
|
| O |
|
RVS/Heat Stage 2 | O/W2/B | Y1 | Y1 |
|
| ||
Heat Stage 1 | W/W1 | W1 | REMOVE J2 |
|
|
| |
Compressor Low | Y1 | W2 | JUMPER FOR |
HEAT STAGING | |||
Compressor High | Y/Y2 | Y/Y2 | Y2 |
Fan | G | G |
|
24VAC Hot Heating | Rh | R | R |
24VAC Hot Cooling | Rc |
| REMOVE J1 FOR |
| DEHUMIDIFY | ||
|
| DH | |
|
| MODES | |
Dry Contact 1 | D1 |
| |
|
| ||
Dry Contact 2 | D2 | C | C |
|
| ||
24VAC Common | C |
|
|
Humidify | HUM | Humidifier Solenoid | |
|
| ||
Outdoor Air Temp | OAT | Valve |
|
Remote Room Sensor | RRS | Outdoor Sensor |
|
|
|
| |
OAT/RRS Return | SRTN | Remote Room |
|
SRTN |
| Sensor |
|
Thermidistat |
| Variable Speed | |
|
| Furnace | |
Heat Stage 2 | O/B W2 | W2 | |
Heat Stage 1 | W/W1 | W1 | |
Cool Stage 1 | Y1 / W2 |
| |
Cool Stage 2 | Y/Y2 | Y/Y2 | |
Fan | G | G | |
24VAC Hot Heating | Rh | R | |
24VAC Hot Cooling | Rc |
| |
Dry Contact 1 | D1 |
| |
Dry Contact 2 | D2 | DHUM | |
24VAC Common | C | COM | |
Humidify | HUM | Humidifier Solenoid | |
Outdoor Air Temp | OAT | ||
Valve * | |||
Remote Room Sensor | RRS | Outdoor Sensor * | |
OAT/RRS Com | SRTN | Remote Room | |
|
| Sensor * |
Air Conditioner
Y1 |
Y/Y2 |
R |
C |
180A / 187A
A08060
Edge Thermidistat Models
w/ Fan Coil &
* Indicates connection may not be required / available.
A09338
Thermidistat Model
w/ VS Furnace &
THERMIDISTAT |
| VARIABLE SPEED |
|
| FURNACE |
RVS/Heat Stage 2 | O/W2/B | W2 |
Heat Stage 1 | W/W1 | W1 |
Compressor Low | Y1 | Y1 |
Compressor High | Y/Y2 | Y/Y2 |
Fan | G | G |
24VAC Hot Heating | Rh | R |
24VAC Hot Cooling | Rc |
|
Dry Contact 1 | D1 |
|
Dry Contact 2 | D2 | DHUM |
24VAC Common | C | COM |
Humidify | HUM | Humidifier Solenoid |
|
| |
Outdoor Air Temp | OAT | Valve |
Remote Room Sensor | RRS | Outdoor Sensor |
|
| |
OAT/RRS Return | SRTN | Remote Room |
SRTN |
| |
| Sensor | |
|
|
AIR CONDITIONER
Y1 |
Y2 |
R |
C |
A08057
Thermidistat Models
w/ Furnace &
LEGEND
| 24 VOLT FACTORY WIRING |
| 24 VOLT FIELD WIRING |
| FIELD SPLICE CONNECTION |
| RELAY SPDT, PILOT DUTY |
| |
| OR EQUIVALENT |
R1 |
|
H | HUMIDISTAT, OPENS ON |
| HUMIDITY RISE (HL38MG026) |
AFS | AIRFLOW SELECTOR |
A02005
Fig. 10 - Thermidistat Wiring with 2-Stage Puron refrigerant Air Conditioner
14