MAJOR COMPONENTS

2-Stage Compressor

The 2-stage compressor contains motor windings that provide 2-pole (3500 RPM) operation.

Compressor Internal Relief

The compressor is protected by an internal pressure relief (IPR) which relieves discharge gas into compressor shell when differential between suction and discharge pressures exceeds and 550 - 625 psi. The compressor is also protected by an internal overload attached to motor windings.

Compressor Control Contactor

The contactor has a 24 volt coil and is controlled by Y1 input from the thermostat

High and Low Pressure Switches

High and low pressure switches are provided in line with the Y1 signal to the contactor for protection. The high pressure switch mounted on the liquid tube is set to open at 670 psi and higher, and the low pressure switch mounted on the suction tube opens at a pressure of 50 psi and lower.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment.

Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See Owner’s Manual for information.

127A

7

Image 7
Contents Installation Instructions Safety ConsiderationsElectrical Shock Hazard Installation Sweat Connection Install Liquid-Line Filter Drier IndoorOutdoor Unit Connected to Factory Approved Indoor Unit Refrigerant Tubing Connection OutdoorCompressor Crankcase Heater Make Electrical ConnectionsAirflow Selections ECM Furnaces System Functions and Sequence of Operation Check Charge TroubleshootingUnloader Test Procedure Do not Install a Plug Without AN Internal RectifierMajor Components Care and Maintenance01 & TP---NRH---01 Thermidistat Model TSTATBBPRH01---B Puronr R-410A Refrigerant Quick Reference Guide 127A