Bryant 123A installation instructions Installation

Page 2

123A / 124A

INSTALLATION

Check Equipment and Job Site

UNPACK UNIT

Move to final location. Remove carton taking care not to damage unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location.

For hurricane tie downs, contact local distributor for details and PE (Professional Engineer) certification, if required by local authorities.

On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.

Roof mounted units exposed to winds may require wind baffles. Consult the Application Guideline and Service Manual - Residential Split System Air Conditioners and Heat Pumps for wind baffle construction.

NOTE: Unit must be level to within ±2_ (±3/8 in./ft.) per compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6-in. (152.4 mm) clearance on 1 side of unit and 12-in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.

On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.

Operating Ambient

The minimum outdoor operating ambient in cooling mode without accessory is 55 _F (12.78 _C), and the maximum outdoor operating ambient in cooling mode is 125_F (51.67 _C).

Make Piping Connections

!WARNING

PERSONAL INJURY AND ENVIRONMENTAL HAZARD

Failure to follow this warning could result in personal injury or death.

Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow-control devices, including solenoid valves.

Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

If ANY refrigerant tubing is buried, provide a 6-in. vertical rise at service valve. Refrigerant tubing lengths up to 36-in. may be buried without further special consideration. Do not bury lines more than 36-in. (914.4 mm).

3/8---in. (9.53 mm) Dia. Tiedown Knockouts in Basepan(2) Places

View From Top

UNIT BASE PAN

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

Dimension

A

B

C

26

X 26

9–1/8 (231.8)

4–7/16 (112.7)

21–1/4 (539.8)

31–1/2

X 31–1/2

9–1/8 (231.8)

6–9/16 (166.7)

24–11/16 (627.1)

35

X 35

9–1/8 (231.8)

6–9/16 (166.7)

28–7/16 (722.3)

 

 

 

 

A05177

Fig. 2 - Tiedown Knockout Locations

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. Rated tubing diameters shown in Table 1 are recommended up to 80 ft. (24.38 m). See Product Data for acceptable alternate vapor diameters and associated capacity losses. For tubing requirements beyond 80 ft. (24.38 m), substantial capacity and performance losses can occur. Following the recommendations in the Longline Guideline will reduce these losses. Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.

There are no buried-line applications greater than 36-in. (914.4 mm) allowed.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

Outdoor Unit Connected to Factory Approved Indoor Unit

Outdoor unit contains correct system refrigerant charge for operation with factory approved ARI rated indoor unit when connected by 15 ft. (4.57 m) of field-supplied or factory-accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.

Refrigerant Tubing Connection Outdoor

Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 1.) Use refrigerant grade tubing

Sweat Connection

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Service valves must be wrapped in a heat-sinking material such as a wet cloth while brazing.

2

Image 2
Contents Electrical Shock Hazard Safety ConsiderationsInstallation Instructions Installation Deep Vacuum Method Install Liquid-Line Filter Drier IndoorEvacuate Refrigerant Tubing and Indoor Coil Final Tubing CheckCompressor Crankcase Heater Install Electrical AccessoriesMake Electrical Connections Start-UpFinal Checks Care and MaintenanceCheck Charge Puronr R-410A Refrigerant Quick Reference Guide Catalog No. II123A 18---3
Related manuals
Manual 38 pages 44.17 Kb

123A specifications

Bryant 123A is a high-efficiency residential air conditioning unit that stands out for its reliable performance and advanced features. Designed with homeowners in mind, this model combines modern technology with user-friendly functionality, ensuring optimal comfort in various climates.

One of the main features of the Bryant 123A is its variable-speed compressor, which allows for precise temperature control and energy savings. Unlike traditional units that operate at a fixed speed, the variable-speed compressor adjusts its output based on the cooling needs of the home. This not only maintains a more consistent indoor temperature but also reduces energy consumption, making it an environmentally friendly choice.

The unit also boasts a SEER (Seasonal Energy Efficiency Ratio) rating of up to 19. This high rating means that the Bryant 123A operates with exceptional energy efficiency, translating into lower utility bills. Homeowners will appreciate the long-term savings that come with this energy-efficient design.

In addition to its impressive efficiency, the Bryant 123A features a robust construction designed to withstand various weather conditions. The steel cabinet is both durable and corrosion-resistant, ensuring that the unit will endure over time. Furthermore, the unit is equipped with a sound-dampening system that minimizes operational noise, providing a quieter indoor environment.

Smart technology integration is another significant characteristic of the Bryant 123A. Homeowners can benefit from the optional Ecobee Smart Thermostat compatibility, allowing remote access and control of the cooling system through smartphone apps. This feature enables users to adjust settings from anywhere, enhancing convenience and energy management.

Moreover, the Bryant 123A utilizes eco-friendly refrigerant, further solidifying its commitment to sustainable practices. The R-410A refrigerant is not only effective at cooling but also contributes to lower ozone depletion potential. This choice aligns with modern environmental standards and regulations, making the unit a responsible choice for conscious consumers.

Overall, the Bryant 123A unit is a standout option for residential air conditioning, offering advanced features, high efficiency, and durable construction. Whether for new installations or replacements, this model promises to deliver reliable cooling performance while maximizing cost savings and environmental responsibility. Homeowners seeking comfort without compromise will find the Bryant 123A an ideal solution for their cooling needs.