Bryant 123A Install Liquid-Line Filter Drier Indoor, Evacuate Refrigerant Tubing and Indoor Coil

Page 3

Use refrigeration grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

Table 1 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

 

LIQUID

RATED VAPOR

 

up to 80 ft. (24.38 m)*

 

 

UNIT SIZE (SERIES)

Connection

Connection

Tube

 

& Tube

 

Diameter

Diameter

 

Diameter

 

 

 

018, 024

3/8

5/8

5/8

030, 036

3/8

3/4

3/4

042, 048

3/8

7/8

7/8

060 (all series)

3/8

7/8

1---1/8

Notes:

1.Tube diameters are for total equivalent lengths up to 80 ft. (24.38 m)

2.Do not apply capillary tube or fixed orifice indoor coils to these units.

*For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (250 ft. (76.2 m)Total Equivalent Length), refer to the Longline Guideline --- Air Conditioners and Heat Pumps using Puronr Refrigerant.

Install Liquid-Line Filter Drier Indoor

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

1.Installation of filter drier in liquid line is required.

2.Filter drier must be wrapped in a heat-sinking material such as a wet cloth while brazing.

Refer to Fig. 3 and install filter drier as follows:

1.Braze 5-in. liquid tube to the indoor coil.

2.Wrap filter drier with damp cloth.

3.Braze filter drier to above 5-in. (127 mm) liquid tube. Flow arrow must point towards indoor coil.

4.Connect and braze liquid refrigerant tube to the filter drier.

A05178

Fig. 3 - Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 4.

5000

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

4000

 

 

 

 

 

LEAK IN

3500

 

 

 

 

 

 

 

 

 

 

SYSTEM

3000

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

MICRONS2000

 

 

 

 

 

VACUUM TIGHT

1500

 

 

 

 

 

 

 

 

 

 

TOO WET

1000

 

 

 

 

 

 

 

 

 

 

TIGHT

500

 

 

 

 

 

 

 

 

 

 

DRY SYSTEM

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

MINUTES

 

 

 

 

 

 

 

 

 

 

A95424

Fig. 4 - Deep Vacuum Graph

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal or wires. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

123A / 124A

3

Image 3
Contents Safety Considerations Installation InstructionsElectrical Shock Hazard Installation Final Tubing Check Install Liquid-Line Filter Drier IndoorEvacuate Refrigerant Tubing and Indoor Coil Deep Vacuum MethodStart-Up Install Electrical AccessoriesMake Electrical Connections Compressor Crankcase HeaterCare and Maintenance Check ChargeFinal Checks Catalog No. II123A 18---3 Puronr R-410A Refrigerant Quick Reference Guide
Related manuals
Manual 38 pages 44.17 Kb

123A specifications

Bryant 123A is a high-efficiency residential air conditioning unit that stands out for its reliable performance and advanced features. Designed with homeowners in mind, this model combines modern technology with user-friendly functionality, ensuring optimal comfort in various climates.

One of the main features of the Bryant 123A is its variable-speed compressor, which allows for precise temperature control and energy savings. Unlike traditional units that operate at a fixed speed, the variable-speed compressor adjusts its output based on the cooling needs of the home. This not only maintains a more consistent indoor temperature but also reduces energy consumption, making it an environmentally friendly choice.

The unit also boasts a SEER (Seasonal Energy Efficiency Ratio) rating of up to 19. This high rating means that the Bryant 123A operates with exceptional energy efficiency, translating into lower utility bills. Homeowners will appreciate the long-term savings that come with this energy-efficient design.

In addition to its impressive efficiency, the Bryant 123A features a robust construction designed to withstand various weather conditions. The steel cabinet is both durable and corrosion-resistant, ensuring that the unit will endure over time. Furthermore, the unit is equipped with a sound-dampening system that minimizes operational noise, providing a quieter indoor environment.

Smart technology integration is another significant characteristic of the Bryant 123A. Homeowners can benefit from the optional Ecobee Smart Thermostat compatibility, allowing remote access and control of the cooling system through smartphone apps. This feature enables users to adjust settings from anywhere, enhancing convenience and energy management.

Moreover, the Bryant 123A utilizes eco-friendly refrigerant, further solidifying its commitment to sustainable practices. The R-410A refrigerant is not only effective at cooling but also contributes to lower ozone depletion potential. This choice aligns with modern environmental standards and regulations, making the unit a responsible choice for conscious consumers.

Overall, the Bryant 123A unit is a standout option for residential air conditioning, offering advanced features, high efficiency, and durable construction. Whether for new installations or replacements, this model promises to deliver reliable cooling performance while maximizing cost savings and environmental responsibility. Homeowners seeking comfort without compromise will find the Bryant 123A an ideal solution for their cooling needs.