Amana ASX 14 SEER service manual Performance Data, Outdoor Total Sensible Latent, Btuh Watts

Page 39

PERFORMANCE DATA

ASX140421[C/D]* - ASX140481C*

MODEL: ASX140421[C*/D*] / CA*F4860*6B* W/.070 Orifice,

Conditions: 80°F IDB, 67°F IWB @ 1450 CFM

Outdoor

Total

Sensible

Latent

Total

Temp. ° F.

Btuh

Btuh

Btuh

Watts

75°

42,116

29,985

12,131

2,950

80°

41,614

30,004

11,610

3,040

85°

41,113

30,015

11,098

3,130

90°

40,611

30,127

10,485

3,205

95°

40,110

30,227

9,883

3,280

100°

39,107

30,029

9,078

3,350

 

 

 

 

 

105°

38,105

29,803

8,301

3,420

110°

36,701

28,826

7,875

3,475

 

 

 

 

 

115°

35,297

27,839

7,458

3,530

 

TVA Conditions @ 95° OD DB, 75° ID DB 63° ID WB

95°

37,200

30,132

7,068

3,160

ASX140481C* / CA*F4860*6D* W/.078 Orfice

Conditions: 80°F IDB, 67°F IWB @ 1550 CFM

Outdoor

Total

Sensible

Latent

Total

Temp. ° F.

Btuh

Btuh

Btuh

Watts

75°

48,300

34,776

13,524

3,260

80°

47,750

34,858

12,893

3,365

85°

47,200

34,928

12,272

3,470

90°

46,600

34,950

11,650

3,560

95°

46,000

34,960

11,040

3,650

100°

44,850

34,759

10,091

3,725

105°

43,700

34,523

9,177

3,800

110°

42,100

33,470

8,631

3,865

115°

40,500

32,400

8,100

3,930

TVA Conditions @ 95° OD DB, 75° ID DB, 63° ID WB

95°

43,552

35,549

8,003

3,618

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the installation instructions.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.

A properly operating unit should be within plus or minus 10 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 5 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

NOTE: Pressures are measures at the liquid and suction service valve ports.

39

Image 39
Contents Technical Manual Should be performed only by indi Product IdentificationGoodman will not be responsible For any injury or property damageDo not connect or use any device Minimum Airflow Clearance Model Type Product DesignModel Dimensions W x D x H DimensionsASX140181A ASX140241A ASX140301A ASX140361A Condensing Unit SpecificationsASX140181B* ASX140361B* / ASX140181C* ASX140361C ASX140181D* / ASX140421D 17.2 Cooling Performance DataModel ASX140181A* / CA*F3131B6A* + TXV Airflow141 ASX140181A18.0 357Model ASX140181B*/CA*F3636*6C Cooling Performance Data ASX140181B* / C* / D19.0 362147 381 Outdoor Am bient Tem peratureEntering Indoor Wet Bulb Te m perature 22.9382 ASX140241AModel ASX140241A* / CA*F3636B6A* / .057 Orifice 24.0Model ASX140241B* / CA*F3636*6C ASX140241B* / CExpanded Performance Data Model ASX140301A* / CA*F3642C6A* / .063 Orifice ASX140301A149 28.8Model ASX140301B*/CA*F3642*6C ASX140301B* / C10.0 10.2 10.5 Model ASX140361A* / CA*F3642C6A* / .067 Orifice ASX140361A11.0 34.6Model ASX140361B*/CA*F3642*6C ASX140361B* / COutdoor Am bie nt Tem pe rature 105 115 10.5145 Model ASX140421A* / CA*F4860C6A* / .074 Orifice 360 ASX140421A40.0 12.9Model ASX140421B* / CA*F4860C6A* / .074 Orifice 40.0 ASX140421B37.4 Model ASX140421C*/CA*F4860*6B11.4 11.7152 ASX140421C* / D12.2 390Model ASX140481A* / CA*F4860D6A* / .079 Orifice ASX140481A* / B148 46.014.4 370Model ASX140481C* / CA*F4860D6A / .078 Orifice ASX140481C391 15.1Model ASX140601A* / CA*F4860D6A* / .088 Orifice 394 ASX140601A* / B 56.0 19.118,000 12,758 242 573 Performance Data ASX14018-601A* /ASX14048-601B460 Performance Data ASX14024-421B* /ASX14018-361CTVA Conditions @ 95 OD DB, 75 ID DB, 63 ID WB Performance DataOutdoor Total Sensible Latent Btuh WattsASX14018-601 DiagramsIs subject to change. Always WiringASX14024 ASX140481CB