CONDENSING UNIT SPECIFICATIONS
ASX140181A* - ASX140361A*
| ASX140181A* | ASX140241A* | ASX140301A* | ASX140361A* | ||||
|
|
|
|
|
|
|
|
|
Cooling Capacity, BTUH | 18,000 |
| 24,000 |
| 30,000 |
| 36,000 |
|
|
|
|
|
|
|
|
|
|
Compressor |
|
|
|
|
|
|
|
|
R.L. Amps | 9.00 |
| 13.4 |
| 12.8 |
| 14.1 |
|
L.R. Amps | 48.0 |
| 58.3 |
| 64.0 |
| 77.0 |
|
Low Pressure Switch |
|
|
|
|
|
|
|
|
Open | 22 PSIG | 22 PSIG | 22 PSIG | 22 PSIG | ||||
Close | 50 PSIG | 50 PSIG | 50 PSIG | 50 PSIG | ||||
High Pressure Switch |
|
|
|
|
|
|
|
|
Open | 610 PSIG | 610 PSIG | 610 PSIG | 610 PSIG | ||||
Close | 420 PSIG | 420 PSIG | 420 PSIG | 420 PSIG | ||||
Condenser Fan Motor |
|
|
|
|
|
|
|
|
Horsepower | 1/12 |
| 1/12 |
| 1/6 |
| 1/4 |
|
F.L. Amps | 0.6 |
| 0.6 |
| 1.5 |
| 1.6 |
|
Liquid Line, Inches O.D.* | 3/8" |
| 3/8" |
| 3/8" |
| 3/8" |
|
Suction Line, Inches O.D.* | 3/4" |
| 3/4" |
| 3/4" |
| 7/8" |
|
Refrigerant Charge | 121.0 |
| 126.0 |
| 131.0 |
| 146.0 |
|
Power Supply |
|
|
|
| ||||
Minimum Circuit Ampacity(1) | 11.8 |
| 17.4 |
| 17.5 |
| 19.2 |
|
Maximum Overcurrent Device(2) | 20 |
| 30 |
| 30 |
| 30 |
|
Electrical Conduit Size |
|
|
|
|
|
|
|
|
Power Supply (Inches) | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 | ||||
Approximate Shipping Weight | 178 |
| 178 |
| 195 |
| 199 |
|
|
|
|
|
|
|
|
|
|
ASX140421A* - |
|
| ||||||
|
|
|
|
|
|
|
|
|
| ASX140421A* |
| ASX140481 |
| ASX140481 |
| ASX140601A* |
|
|
| AA/AB/AC |
| AD/B* |
| ASX140601B* |
| |
|
|
|
|
|
| |||
Cooling Capacity, BTUH | 42,000 |
| 48,000 |
| 48,000 |
| 60,000 |
|
|
|
|
|
|
|
|
|
|
Compressor |
|
|
|
|
|
|
|
|
R.L. Amps | 17.9 |
| 19.8 |
| 19.8 |
| 26.4 |
|
L.R. Amps | 112.0 |
| 109.0 |
| 109.0 |
| 134.0 |
|
Low Pressure Switch | 22 PSIG |
| 22 PSIG |
| 22 PSIG |
| 22 PSIG |
|
Open |
|
|
|
| ||||
Close | 50 PSIG |
| 50 PSIG |
| 50 PSIG |
| 50 PSIG |
|
High Pressure Switch |
|
|
|
|
|
|
|
|
Open | 610 PSIG |
| 610 PSIG |
| 610 PSIG |
| 610 PSIG |
|
Close | 420 PSIG |
| 420 PSIG |
| 420 PSIG |
| 420 PSIG |
|
Condenser Fan Motor |
|
|
|
|
|
|
|
|
Horsepower | 1/4 |
| 1/4 |
| 1/4 |
| 1/4 |
|
F.L. Amps | 1.6 |
| 1.6 |
| 1.6 |
| 1.6 |
|
Liquid Line, Inches O.D.* | 3/8" |
| 3/8" |
| 3/8" |
| 3/8" |
|
Suction Line, Inches O.D.* | 7/8" |
| 7/8" |
| 7/8" |
| 7/8" |
|
Refrigerant Charge | 180.0 |
| 186.0 |
| 189.0 |
| 271.0 |
|
Power Supply |
|
|
|
| ||||
Minimum Circuit Ampacity(1) | 24.0 |
| 26.4 |
| 26.4 |
| 34.6 |
|
Maximum Overcurrent Device(2) | 40 |
| 40 |
| 40 |
| 60 |
|
Electrical Conduit Size |
|
|
|
|
|
|
|
|
Power Supply (Inches) | 1/2 or 3/4 |
| 1/2 or 3/4 |
| 1/2 or 3/4 |
| 1/2 or 3/4 |
|
Approximate Shipping Weight | 207 |
| 242 |
| 242 |
| 280 |
|
*Up to 24' in equivalent line length
(1)Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)Maximum Overcurrent Protection Device: MUST use Time Delay Fuses or HACR type Circuit Breaker of the same size as noted.
6
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.