Bard QH422, QH243, QH602, QH482, QH362, QH302 installation instructions Start UP

Page 21

START UP

DESCRIPTION OF STANDARD

EQUIPMENT

Solid State Electronic Heat Pump Control

Provides efficient 30-minute defrost cycle. A thermistor sensor and speed up terminal for service along with a 10- minute defrost override are standard on the electronic heat pump control.

High / Low Pressure Switch

Provides refrigerant circuit high pressure and loss of charge protection. Includes lockout circuit that is resettable from room thermostat.

Five Minute Compressor Time Delay

Provides short cycle protection for the compressor which extends compressor life. Built into the electronic heat pump control as standard.

Service Lights

One service light indicates when service is required.

Check System – detects high or low pressure switch operation for compressor protection.

OPTIONAL CFM (QH362, QH422, QH482 AND QH602 ONLY)

These units are shipped from the factory set to operate at the optional CFM level shown in Table 9. This provides lower operating sound levels for non-ducted, free discharge applications. This CFM level will reduce the system capacity performance by approximately 2% at the same energy efficiency.

Rated CFM is required for ducted applications for maximum performance rating. To obtain full CFM on these models, connect jumper wire as follows:

1.Disconnect all power to the unit. Failure to do so may result in damage to the motor.

2.Open return air service panel

3.Open inner control panel cover

4.Locate low voltage terminal strip. There is a pink jumper wire with both ends attached to terminal marked “G2”. Move one end of this jumper to terminal “Y”.

5.Reverse steps to reassemble.

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil with a dishwasher detergent.

PHASE MONITOR

All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contactor is allowed to energize.

If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.

THREE PHASE SCROLL COMPRESSOR START UP INFORMATION

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.

However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as, substantially reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for even one hour may have a negative impact on the bearing due to oil pump out.

All three phase scroll compressors used in the QTEC series are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction. The direction of rotation of the motor may be changed by reversing any two line connections to the unit.

Manual

2100-420H

Page

21 of 34

Image 21
Contents Instructions Models QH243 QH302 QH362 QH422 QH482 QH602 Qtec Series Packaged Heat Pump InstallationContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsFactory BUILT-IN Electric Heat Table Qtec Model NomenclatureElectrical Specifications on page 6 a Electrical SpecificationsModel Unit Dimensions Unit Removal from Skid Shipping DamageAIR Seal Under Qtec Unit Removal of Unit from SkidHandling Unit After Removal from Skid Minimum Installation HeightGeneral Unit on Appliance CartInstallation with Free Blow Plenum Ducted Application Filters Duct WorkSupply Duct Connections Filter LocationFresh AIR Intake Optional Side Drain Side View InstallationCondensate Drain Standard Rear DrainService Light Rear Drain TOP ViewUnit Mounting Installation Instructions Mounting the UnitRemoving Locking Screws from Wheels Wiring LOW Voltage Wiring Wiring Main PowerComponent Location Operating Voltage RangeLOW Voltage Connections for DDC Control LOW Voltage ConnectionsWall Thermostats Thermostat Predominant FeaturesRemote Thermostat Wiring Diagram Thermostat Option Unit Mounted Thermostat Wiring Diagram Thermostat Option Unit Mounted Thermostat Wiring Diagram Thermostat Option Start UP Mist Eliminator Service Service HintsBarometric Fresh AIR Damper Standard Vent OptionsFresh AIR Damper Removal Qerv Removal Sequence of Operation Pressure Service PortsOptional Climate Controls Sequence of Operation Heat Pump Control Board HPCDefrost Cycle LOW Pressure Control Bypass TimerTroubleshooting TroubleshootingSolid State Heat Pump Control Troubleshooting Procedure Checking Temperature SensorTemperature F VS Resistance R of Temperature Sensor Don’t Troubleshooting GE ECM MotorsReplacing ECM Control Module Troubleshooting GE ECM Motors CONT’DFAN Blade Setting FAN Blade Dimensions FAN Blade Setting Dimensions Refrigerant ChargeSuper Heat AT Compressor Indoor Blower PerformanceModel Temp Pressure Cooling Pressure ALL Temperatures in Degrees FReturn AIR Temperature Entering Outdoor Coil Model Pressure Heating Pressure ALL Temperatures in Degrees F

QH482, QH243, QH302, QH422, QH602 specifications

Bard has established itself as a leader in the heating, ventilation, and air conditioning (HVAC) industry with its innovative line of products, including the Bard QH series. Models such as QH362, QH602, QH422, QH302, and QH243 showcase the perfect blend of performance, efficiency, and advanced technology.

The Bard QH362 is built for both affordability and efficiency, making it ideal for smaller commercial spaces. This model offers a cooling capacity of 36,000 BTUs, providing optimal comfort with minimal energy consumption. Its robust design ensures long-lasting performance, while the air-cooled condenser enhances reliability in various climates.

The QH602 model takes it a step further with enhanced cooling capabilities, boasting a 60,000 BTU rating. This unit is particularly well-suited for larger commercial applications. Its advanced heat pump technology allows for efficient heating and cooling, ensuring indoor comfort year-round. The QH602 features a user-friendly control system that optimizes energy use and simplifies operation.

Next up, the QH422 model is designed for mid-sized commercial environments, offering 42,000 BTUs of cooling power. This model is distinguished by its energy-efficient design, significantly reducing operational costs while maintaining high-performance levels. The QH422 includes a smart thermostat that allows users to monitor and adjust settings remotely, further enhancing energy management.

The QH302 model is perfect for businesses looking for a balance between power and efficiency. With a capacity of 30,000 BTUs, this unit effectively meets the needs of medium-sized spaces. Its compact design allows for easy installation and maintenance, making it a favorite among commercial property managers.

Lastly, the QH243 model rounds out the series with a 24,000 BTU capacity, ideal for smaller commercial applications. This model showcases Bard's commitment to energy efficiency, equipped with environmentally friendly refrigerants and advanced insulation materials that minimize energy loss.

These Bard models feature innovative technologies such as variable-speed fans, which ensure consistent airflow regardless of outdoor conditions. Additionally, noise-reduction technologies provide a quieter operation, creating a more pleasant indoor environment.

In summary, the Bard QH series, including the QH362, QH602, QH422, QH302, and QH243, offers a comprehensive range of HVAC solutions tailored to diverse commercial needs. With their efficient designs, advanced technology, and focus on reliability, these models set the standard for modern heating and cooling equipment.