Bard QH302, QH243, QH602, QH482, QH422, QH362 Vent Options, Barometric Fresh AIR Damper Standard

Page 23

VENT OPTIONS

BAROMETRIC FRESH AIR DAMPER (Standard)

Before starting, make sure the power has been turned off. The return air grille panel must be removed. The fresh air damper assembly can be seen on the back of the unit. See Figure 19.

1.The fresh air damper is attached to the back of the unit with one screw on either side of the assembly. Both of the screws must be removed.

2.Once the mounting screws are removed, tilt the assembly down and lift it out.

The mist eliminator can be seen through the opening. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit.

COMMERCIAL ROOM VENTILATOR (Option)

Before starting, make sure the power has been turned off. The return air grille panel must be removed. The commercial room ventilator (CRV) can be seen after the panel has been removed. The CRV must be removed to gain access to the mist eliminator.

1.The two mounting screws in the front of the CRV must be removed.

2.The power connectors for the CRV (located on the right side of the unit) must be disconnected. Squeeze the tabs on the sides of the connector and pull straight out. Unplug both of the connectors.

3.Slide the CRV straight out of the unit.

The mist eliminator can be seen through the opening in the back of the unit. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed.

QTEC R ENERGY RECOVERY VENTILATOR (Option)

Before starting, make sure that the power has been turned off. The return air grille panel must be removed. The energy recovery ventilator (QERV) can be seen after the panel has been removed. To gain access to the mist eliminator, the QERV must be removed. See Figure 20.

1.The front fill plate of the QERV must be removed. There is one screw on either side of the plate. Remove these screws and remove the plate.

2.On either side of the QERV there are mounting screws that hold the QERV in place. Remove both of these screws.

3.Underneath the heat recovery cassette there is a power connector for the lower blower assembly. To disconnect this plug, the tabs on both sides of the plug must be squeezed to release the plug. While squeezing the tabs, pull the plug out of the socket.

4.The QERV is plugged into the unit in the right side of the unit. Both of these plugs must be disconnected to remove the QERV. Squeeze the tabs on the sides of the connector and pull straight out.

5.Slide the QERV assembly straight out of the unit, being careful not to let the cassette slide out of the QERV.

The mist eliminator can be seen through the opening in the back of the unit. The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed.

Manual

2100-420H

Page

23 of 34

Image 23
Contents Instructions Models QH243 QH302 QH362 QH422 QH482 QH602 Qtec Series Packaged Heat Pump InstallationContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsFactory BUILT-IN Electric Heat Table Qtec Model NomenclatureElectrical Specifications on page 6 a Electrical SpecificationsModel Unit Dimensions Removal of Unit from Skid Shipping DamageUnit Removal from Skid AIR Seal Under Qtec UnitUnit on Appliance Cart Minimum Installation HeightHandling Unit After Removal from Skid GeneralInstallation with Free Blow Plenum Ducted Application Filter Location Duct WorkFilters Supply Duct ConnectionsStandard Rear Drain Optional Side Drain Side View InstallationFresh AIR Intake Condensate DrainUnit Mounting Service LightRear Drain TOP View Removing Locking Screws from Wheels Installation InstructionsMounting the Unit Operating Voltage Range Wiring Main PowerWiring LOW Voltage Wiring Component LocationLOW Voltage Connections for DDC Control LOW Voltage ConnectionsWall Thermostats Thermostat Predominant FeaturesRemote Thermostat Wiring Diagram Thermostat Option Unit Mounted Thermostat Wiring Diagram Thermostat Option Unit Mounted Thermostat Wiring Diagram Thermostat Option Start UP Mist Eliminator Service Service HintsBarometric Fresh AIR Damper Standard Vent OptionsFresh AIR Damper Removal Qerv Removal Heat Pump Control Board HPC Pressure Service PortsSequence of Operation Optional Climate Controls Sequence of OperationDefrost Cycle LOW Pressure Control Bypass TimerTroubleshooting TroubleshootingTemperature F VS Resistance R of Temperature Sensor Solid State Heat Pump Control Troubleshooting ProcedureChecking Temperature Sensor Don’t Troubleshooting GE ECM MotorsReplacing ECM Control Module Troubleshooting GE ECM Motors CONT’DIndoor Blower Performance FAN Blade Setting Dimensions Refrigerant ChargeFAN Blade Setting FAN Blade Dimensions Super Heat AT CompressorModel Temp Pressure Cooling Pressure ALL Temperatures in Degrees FReturn AIR Temperature Entering Outdoor Coil Model Pressure Heating Pressure ALL Temperatures in Degrees F

QH482, QH243, QH302, QH422, QH602 specifications

Bard has established itself as a leader in the heating, ventilation, and air conditioning (HVAC) industry with its innovative line of products, including the Bard QH series. Models such as QH362, QH602, QH422, QH302, and QH243 showcase the perfect blend of performance, efficiency, and advanced technology.

The Bard QH362 is built for both affordability and efficiency, making it ideal for smaller commercial spaces. This model offers a cooling capacity of 36,000 BTUs, providing optimal comfort with minimal energy consumption. Its robust design ensures long-lasting performance, while the air-cooled condenser enhances reliability in various climates.

The QH602 model takes it a step further with enhanced cooling capabilities, boasting a 60,000 BTU rating. This unit is particularly well-suited for larger commercial applications. Its advanced heat pump technology allows for efficient heating and cooling, ensuring indoor comfort year-round. The QH602 features a user-friendly control system that optimizes energy use and simplifies operation.

Next up, the QH422 model is designed for mid-sized commercial environments, offering 42,000 BTUs of cooling power. This model is distinguished by its energy-efficient design, significantly reducing operational costs while maintaining high-performance levels. The QH422 includes a smart thermostat that allows users to monitor and adjust settings remotely, further enhancing energy management.

The QH302 model is perfect for businesses looking for a balance between power and efficiency. With a capacity of 30,000 BTUs, this unit effectively meets the needs of medium-sized spaces. Its compact design allows for easy installation and maintenance, making it a favorite among commercial property managers.

Lastly, the QH243 model rounds out the series with a 24,000 BTU capacity, ideal for smaller commercial applications. This model showcases Bard's commitment to energy efficiency, equipped with environmentally friendly refrigerants and advanced insulation materials that minimize energy loss.

These Bard models feature innovative technologies such as variable-speed fans, which ensure consistent airflow regardless of outdoor conditions. Additionally, noise-reduction technologies provide a quieter operation, creating a more pleasant indoor environment.

In summary, the Bard QH series, including the QH362, QH602, QH422, QH302, and QH243, offers a comprehensive range of HVAC solutions tailored to diverse commercial needs. With their efficient designs, advanced technology, and focus on reliability, these models set the standard for modern heating and cooling equipment.