System and Control Options

6.5.1Specify Longest Cable Length

You may specify the length of the longest cable connected to either of the 4-20mA alarm outputs. The default value is 0-1000 ft. (0-304.8m). Valid entries range from 0-500 ft. (0-152.4m) to 0-5000 ft. (0-1524m), as shown in the Maximum Cable Length screen, below right.

Select the longer cable length installed on either zone. For example, if Zone 1 has 2000 ft. (609.6m) of cable and Zone 2 has 3500 ft. (1066.8m), select 0-4000 ft. (0-1219.2m).

The chosen setting applies to both zones and is correlated to the 4-20mA output of each zone to pro- vide the distance of the leak. Once the range is selected, the following correlation will be applied:

5mA = 0 ft. (0m)

19mA = 4000 ft. (1219.2m)

Table 10 shows the operation of the 4-20mA outputs.

Table 10 Operation of 4-20mA outputs

Signal

Operation

 

 

0mA

Indicates cable cannot be monitored

 

 

4mA

Indicates normal operation

 

 

5mA

0 ft. (0m)

 

 

19mA

Longest cable length (ft.)—for example, 4000 ft. (1219.2m)

 

 

20mA

Indicates cable fault / contamination

 

 

To specify the maximum cable length:

From the Maximum Cable Length screen, below right, use the arrows ↑↓ to choose the correct range—for example, 0-4000FT(0-1219.2M).

Press Enter .

6.5.2Define Relays as Normally Open or Normally Closed

All four digital alarm outputs may be set up as Normally Open (NO) or Normally Closed (NC). The default setting is NO (Normally Open). The chosen setting applies to all cable fault/contamination and leak relays for both zones.

To change the normal state:

From the Normally Open / Closed screen, below right, use the arrows ↑↓ to choose NO (Normally Open) or NC (Normally Closed).

For a non-supervised mode, select Normally Open. The relays energize for an alarm condition.

For a supervised mode, select Normally Closed. The relays de-energize for an alarm condition or loss of power.

Press Enter .

6.5.3Define Alarms as Latched or Unlatched

All four digital alarm outputs may be set up as Latched (Y) or Unlatched (N). When configured as Latched, alarms must be manually reset by an operator after they are cleared, as described in 6.9 - Reset Latched Alarms. The default setting is Latched (Y). The chosen set- ting applies to cable fault and leak relays for both zones.

Setup System Menu

SETUP ZN1 ZONE 1

SETUP ZN2 ZONE 2

>SETUP ALARM OUTPUTS

↑↓ =NEXT =SELECT

SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO

Maximum Cable Length

SELECT LONGEST

CABLE CONNECTED

> 0-500FT

(0-152.4 M)

↑↓ =NEXT

=SELECT

0-1000FT (0-304.8M)

0-1500FT (0-472.2M)

0-2000FT (0-609.6M)

0-2500FT (0-762.0M)

0-3000FT (0-914.4M)

0-4000FT(0-1219.2M)

0-5000FT(0-1524.0M)

Normally Open / Closed

ARE LEAK

& FAULT

RELAYS NORMAL OPEN

OR NORMAL CLOSED? NO

↑↓ =NO/NC

 

 

=END

 

 

 

 

 

 

 

 

To change this setting:

From the Latched / Unlatched screen, shown at right, use the arrows ↑↓ to choose Y (Latched) or N (Unlatched).

Press Enter .

Latched / Unlatched

IS LEAK & FAULT ALARM LATCHED? Y

↑↓ =Y/N

=END

31

Image 35
Contents LIQUI-TECT Monitoring System Page Table of Contents Figures Introduction Equipment InspectionKey lock Outside Enclosure OverviewLCD stops flashing Entry in Alarm History LogTypical Sequence LCD flashesController board components Controller Board Overview24VAC connector RS232 connectorRS485 connector Power receptacleLED indicators summary LED IndicatorsUnpacking and Preliminary Inspection Installation ConsiderationsPacking Contents Mounting the Panel Surface-Mounting the Liqui-tect PanelRequired tools Flush-Mounting the Liqui-tect Panel 24VAC input connector Connect Power to the Liqui-tect PanelInput Power Connections Small Enclosure Terminal 24VAC wiring red & whiteTroubleshooting Transformer Module Input and Output Power Connections Large EnclosureInput Power Connections VAC Output Power ConnectionsWiring specifications Attaching Leak Detection Connection Cable to the Panel Connecting Leak Detection Cable InputsLeak detection cable LT500Y Connecting Leak Detection Cable to the Connection CableSections Hold-down clips At beginning End of arc PatternsAlarm outputs Connecting Alarm OutputsDIP switch Audible horn RS422 SiteScan Web ConnectorDisable the Audible Horn RS422 SiteScan Web connectorView Status Menu View Status OverviewSystem and Control Overview Main MenuView Zone Trend View Alarm HistoryView Status View Cable StatusOverall Condition View Cable StatusCable Status Screens Viewing Additional ScreensAlarm History Log conditions View Alarm HistoryAlarm History Log Alarm History LogZone Trend Log View Zone TrendZone Trend Log Alphanumeric Special characters LoginLogin Valid characters for data entryReset Latched Alarms Login ScreenSetup System Reset Latched AlarmSetup System Setup ZN1 Zone Setup System OverviewChange Units Label Identify the Zone as ConnectedChange Zone Label Auto Calibration Progress Set Up Sensitivity for Water DetectionAuto Calibration Change Maximum LengthContamination Detection Sensitivity Set Up Sensitivity for Contamination DetectionSetup Zone 2 Menu Setup System Setup ZN2 ZoneSetup System Setup Alarm Outputs Define Relays as Normally Open or Normally Closed Define Alarms as Latched or UnlatchedSignal Operation Specify Longest Cable LengthSelect Setup Re-Alarm Delay Setup System Setup Re-Alarm DelayLatched Alarms Only Unlatched Alarms OnlyDefault mapping values Setup System Setup MapmodeSelect Setup Mapmode Select Zone to Map Set Up Mapping for Zone 1 or ZoneMessage if No Mapping View Last MapSelect Zone to Map Mapping for Last MapReset Password to the Factory Default Aaaa Setup System Setup System InfoChange Password Change Date & Time/Automatic Daylight Saving Time Factory DefaultsFactory default settings Factory DefaultsReset Latched Alarms Reset Latched AlarmsLog In and Choose Reset Latched Alarm Choose Y to Reset AlarmsClear Alarm History Clear Zone Trend Clear Zone TrendLog In and Choose Clear Zone Trend Liqui-tect Panel Specifications Specifications Specifications Page Asia 23F, Allied Kajima Bldg Technical Support/ServiceCompany Behind the Products Locations

MC68HC16Z1 specifications

The Emerson MC68HC16Z1 is a versatile microcontroller that combines power and efficiency, making it an ideal choice for various embedded applications. As part of the Motorola 68HC16 series, the MC68HC16Z1 is designed to deliver robust performance while offering extensive support for both simple and complex tasks. With its 16-bit architecture, this microcontroller is well-equipped to handle a range of functionalities, from industrial control systems to automation processes.

One of the main features of the MC68HC16Z1 is its high-performance 16-bit CPU, which operates at speeds up to 20 MHz. This allows for efficient data processing and execution of instructions, which is critical in time-sensitive applications. The microcontroller boasts a rich instruction set, including various addressing modes that enhance programming flexibility. This versatility enables developers to implement efficient algorithms tailored to their specific application needs.

Power management is another noteworthy characteristic of the MC68HC16Z1. The device supports low-power operation modes, which is essential for battery-powered applications or scenarios where energy consumption is a concern. With its capability to switch between different operational states, the microcontroller can significantly extend battery life while ensuring that performance is not compromised.

The MC68HC16Z1 also includes an integrated analog-to-digital converter (ADC) that allows for direct interaction with analog signals. This feature is particularly beneficial in applications that require sensor data acquisition. Additionally, the microcontroller provides various communication interfaces, including serial communication options like UART and SPI, facilitating seamless data transfer between devices.

In terms of memory, the MC68HC16Z1 supports a wide range of options, including both RAM and ROM, allowing for flexible storage solutions depending on the application requirements. The built-in programmability further allows for updates and modifications to the firmware, ensuring that the system can adapt to evolving project specifications.

Moreover, the microcontroller features an extensive array of I/O ports, making it capable of interfacing with various peripheral devices such as sensors, actuators, and displays. This extensive connectivity enhances its usability in a range of applications, from robotics to automotive systems.

In summary, the Emerson MC68HC16Z1 microcontroller stands out for its balanced blend of performance, low power consumption, and feature-rich design. Its 16-bit architecture, integrated ADC, versatile communication interfaces, and extensive memory options make it a go-to choice for developers looking to create effective and reliable embedded systems. Whether for industrial automation or consumer electronics, the MC68HC16Z1 continues to be a dependable and powerful component in the realm of microcontroller technology.