Omega LV800 manual F E T Y, E C I F I C At I O N S

Page 10

S A F E T Y

General Safety

CAUTION: It is essential that all instructions in this manual be followed to ensure proper operation of the equipment and safety of operating person- nel. Use of equipment not specified herein, may impair protection provid- ed by equipment. The use of this symbol is used throughout manual to highlight important safety issues. Please pay particular attention to these items.

Electrical Shock Caution

Certain LV800 models are powered with HIGH VOLTAGE. No operator serviceable parts are inside. All servicing is to be performed by qualified personnel. Each MK-2e is provided with a "protective conductor terminal" which shall be terminated to earth ground potential (See Electrical Installation). This product's design complies with EN61010-1 installation category II and pollution degree 2.

Electromagnetic Compatibility (EMC)

The LV800 was tested and found to comply with the standards listed below. The LV800 should not be used in residential or commercial envi- ronments. Compliance to EMC standards was demonstrated by means of a test setup using the following installation methods.

1)LV800 enclosure was connected to earth ground (protective earth).

2)No specific wiring convention was used to supply power or to retrieve output signal from the LV800.

EMC Emissions:

Meets EN 61326-1 Electrical Equipment for Control Use, EMC

EN 55011 Radiated and conducted emissions

(Class A- industrial) EN 61000-3 Fluctuations/Flicker

Meets FCC Part 15B: RF Devices, Unintentional Radiators

CISPR 11 Radiated and conducted emissions (Class A- industrial)

EMC Immunity:

Meets EN 61326-1 Electrical Equipment for Control Use,

EMC

IEC 1000-4-2 Electrostatic discharge (industrial)

IEC 1000-4-3 RF radiated EM fields (industrial)

IEC 1000-4-4 Electrical fast transients (industrial)

IEC 1000-4-5 Electrical surges (industrial)

IEC 1000-4-6 RF conducted EM energy (industrial)

IEC 1000-4-8 Power frequency magnetic fields (industrial)

IEC 1000-4-11 Source voltage deviation

 

S P E C I F I C AT I O N S

Power:

115VAC (±15%); 2.5VA; 50/60Hz / 230VAC (±15%); 2.5VA; 50/60Hz

Altitude:

6562 ft (2000 m) max

Installation Category:

II

Pollution Degree:

4 (Reduced to 2 by enclosure) Suitable for indoor/outdoor use

Ambient Op Temp:

-40˚ F (-40˚ C) to +150˚ F (+65˚ C)

*Internal Bin Temp:

To +176˚ F (+80˚ C) w/alum. mount (<104˚ F (40˚ C) ambient)

Output Relay:

To +400˚ F (+204˚ C) w/SS mount (<122˚ F (50˚ C) ambient)

SPDT, 5A @ 250VAC, 30VDC maximum

External Indicators:

Red and green LEDs indicating power and operating mode

Sensitivity:

Multi-turn potentiometer adjustment 0.5pf to 150 pf

Stability:

±0.015pf per degree F (±0.027pf per degree C) @ 0.5pf setting

Time Delay:

0.25 to 15 sec delay-to-activate, adjustable

Fail-Safe:

0.25 sec delay-to-deactivate, fixed

Switch selectable - HI/LO

Build-up Immunity:

Protected via driven shield to 150 ohm load

Enclosure:

Cast alum screw-on cover, beige polyester pwdr coat, NEMA 4, IP66

Conduit Connection:

Two (2) 3/4” NPT connections

**Approvals:

CSAUS CSAC Ordinary Locations, CE Mark(Ordinary location only)

Standard/Food Grade Probe

Mounting:

1-1/4” NPT alum or combo 3/4” NPT 316SS and 1-1/4” NPT alum

Probe Material:

3/8in(9.5mm) dia. 316SS probe & guard, PPS insulators

Probe Length:

16in(406mm) from alum mounting

Temp (Probe Only): PPS+450˚ F (+232˚ C) max;

Pressure:

50 psi(3.5 bar) max (alum connection);150 psi(10 bar) max (3/4” NPT SS)

Stub Probe

 

Mounting:

1-1/4” NPT alum, or combo

 

3/4” NPT 316SS and 1-1/4” NPT alum

Probe Material:

3/8in(9.5mm) dia. 316SS probe & guard, PPS insulators

Probe Length:

Cut to customer specification; application dependent

Temp (Probe Only): PPS +450˚ F (+232˚ C) max

Pressure:

50 psi(3.5 bar) max (aluminum); 150 psi(10 bar) max (3/4 NPT SS)

*Influenced by mounting, material thermal conductivity and ambient temperature.

9

Image 10
Contents User’s Guide Servicing North America LV 8 0 0 S E R I E S Choosing a Location See Figure E I N S TA L L AT I O N C O N S I D E R AT I O N SCover Removal See Figure E C T R I C a L I N S TA L L AT I O N Output Relay Contacts See Figure Power Input SeeL I B R AT I O N Step Calibration- probe exposed to materialDelay Troubleshooting I N T E N a N C EC H a N I C a L S F E T Y E C I F I C AT I O N SWARRANTY/DISCLAIMER Shop online at omega.com