Omega Engineering LVRD500, LVU40 For LVU and Lvrd Series Ultrasonic and Radar Sensors

Page 2

Instruction Manual

For LVU and LVRD Series

Ultrasonic and Radar Sensors

Inter-Connection Diagram

Top View of Sensor (Access Cover Removed)

+ 8

 

 

 

12– 30 VDC -- 7

 

 

- F1/8 A 250V

6

 

 

 

L1

8

 

 

DC Power Input

AC IN

L2/N

7

 

 

 

6

Note - TB #7 is

 

 

 

 

+ 5

Connected to TB #4

4-20 mA

 

— 4

 

 

Control Panel

!

SHIELD

3

 

 

Fastening Screw

RS232/485 A/TX

2

 

 

B/RX 1

Terminal Block

 

STATUS

 

 

Status LED

 

CALIBRATION

Calibration Pushbutton

 

SWITCH

 

 

 

NOTE — Use only 1/2” NPT Conduit

Typical Installation

1)DIRECT MOUNTING ULTRASONIC SENSOR -SIMPLY THREAD SENSOR DIRECTLY INTO METAL OR PLASTIC NOZZLE.

2)RADAR UNIT MUST BE INSTALLED INTO METAL FITTING WITH THE ANTENNA POINTING DOWNWARD.

FCC INFORMATION TO RADAR USERS

NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provided reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio fre- quency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interfer- ence to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the inter- ference at his own expense.

WARNING-Changes or Modifications not expressly approved by the Manufacturer could void the user’s

authority to operate the equipment.

Wiring Information

- Ground shield at one end only.

- All terminal block wiring must be rated for 250V.

- Power input wiring must be protected by a 15A double

pole circuit breaker .

- Terminal is for use only with equipment which has no live

parts which are accessible .

- Terminal is for use with equipment which maintains basic

insulation from hazardous voltage under normal and sin-

gle fault conditions .

- Connection used at the remote end of external circuit .

Recommended Wiring

 

12

- 30 Vdc

˜

115

/ 230 Vac

60

/ 50 Hz

 

1/2” NPT Conduit Hole 1”, 1 1/2”, 2” , 3”NPT

Ultrasonic Sensor

Radar Rod Antenna

CALIBRATION PUSHBUTTON

/ Led Indicator For 4 - 20 mA (750 ohm Max.) output

OPTIONAL Programmable Calibration & Diagnostics, Data Logging, RS232 or RS485 Com. Temperature Compensation for the speed of sound .

For AC Sensor —

Power

 

3

Wire unshielded 22 AWG , 300 V

Current

Output

1 Pair

shielded

24 AWG , 300 V

Communication

1

Pair

shielded

24 AWG , 300 V

For DC Sensor—

 

 

 

 

Power &

Current output 3 Wire shielded 24 AWG , 300 V

Calibration — 4 -20 or 20 - 4 mA Output

FULL — Calibrate 20 mA or 4mA (Set Near Target)

 

 

 

 

 

 

 

 

Deadzone

 

FULL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Process Temperature

 

 

 

 

 

 

 

 

20 or 4 mA

 

 

 

 

 

Radar ;190° F/90°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

— 40° F/°C

 

 

 

 

 

 

 

 

 

 

LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ultrasonic ;

 

 

 

 

 

 

 

 

Yellow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

R

 

Red

 

 

 

 

 

140° F/60 °C

 

 

 

 

 

 

 

 

 

 

 

 

 

— 40° F/° C

 

C

 

 

S

E

 

 

 

 

 

 

 

 

 

 

 

C

 

 

S

 

 

 

 

 

 

 

 

 

 

 

U

 

 

P

O

 

 

 

 

 

 

 

 

 

 

 

R

 

 

L

 

 

 

 

 

 

 

 

 

 

 

A

 

 

A

U

 

 

 

 

 

 

 

 

 

 

 

C

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

I

 

 

 

 

 

 

 

 

 

 

+/—0.25%

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Per

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Level

 

 

 

 

EMPTY

4 or 20mA

Operation - An ultrasonic/electromagnetic pulse is transmitted from the sensor . The pulse travels to the surface being monitored and is re- flected off this surface back to the sensor . The time of flight is divided by 2 and converted to an output signal directly proportional to the material level .

1.Calibration mode LED color is Green.

(for Radar Low Dielectric Materials has to be off)

2.Push button and hold until LED turns Yellow (20 mA) or push button and hold until LED turns Red (4 mA)

3.Release button, observe LED flashes to acknowledge

the calibration.

EMPTY— Calibrate 4 mA or 20 mA (Set Far Target) 1. Calibration mode LED color is Green

(for Radar Low Dielectric Materials has to be off)

2. Push button and hold until LED turns Red (4 mA)

or push button and hold until LED turns Yellow (20 mA)

3. Release button, observe LED flashes to acknowledge the calibration.

For Radar to turn the Low Dielectric Materials operation mode ON and OFF (this mode is recommended for materials with dielectric constant lower than 4.)

1)To turn the Low Dielectric Materials ON. Push button and hold until LED goes OFF after the sequence of Yellow , Red and turns Off. The Low Dielectric Material operation is On when the LED’S Green light blinks constantly.

2)To turn the Low Dielectric Materials OFF. Push button and hold until LED goes OFF after the sequence of Yellow , Red and Turns OFF. The Low Dielectric Material operation is OFF when LED is continuously Green.

Image 2
Contents Instruction Sheet For LVU and Lvrd Series Ultrasonic and Radar Sensors Shield 4214/0605