The ESI 48/120V Inverter
Description:
The ESI 48/120V inverters are single phase,
Features
•Standard 19” or 23” rack
•1KVA/800W, 2KVA/1600W
•Selectable 100V/110V/115V/120V system output
•High efficiency
•Pure sine wave output
•Compact, lightweight modular design
•Bypass function
•
•Optional SNMP Interface card
•User friendly LED and LCD display
Specification
General |
|
Product name | ESI 48 / 120 V – 1k VA |
| ESI 48 / 120 V – 2k VA |
Efficiency, at 120Vrms | 83 % |
Safety | UL 60950 |
| |
EMI, radiated compliant with | FCC Part 15 class A |
Cooling | Fan cooled |
On/Off Switch | Yes |
MTBF | 450K Hours |
DC Input |
|
Input voltage | 40 … 60 Vdc |
Rated current | 25 A (1k VA) / 50 A (2k VA) |
AC Input(Bypass) |
|
Input voltage | 100 / 110 / 115 / 120 Vrms ± 20 Vrms |
Frequency | 50 / 60 Hz ± 5 Hz |
EMI, conducted compliant with | FCC Part 15 class A |
Output |
|
Output voltage | 100 / 110 / 115 / 120 Vrms |
Voltage regulation | ± 3 % |
Frequency | 50 / 60 Hz ± 0.2 Hz |
THD | 3 %: 100% liner load |
| 5 %: 100% SPS load |
Current, nominal | 10 Arms (1kVA) |
Crest factor | 20 Arm (2kVA) |
3 : 1 | |
Mechanics |
|
Width, overall | 17.3” / 440 mm |
Depth, overall | 11.8” / 300 mm |
Height, overall | 3.5” / 88.0 mm |
Weight | 15.4 lb / 7 kg (1k VA); 17.6 lb / 8 kg (2k |
| VA) |
Environment |
|
Operating temperature | 0 ... + 45 °C |
Relative humidity | 20 ~ 90 %, non condensing |
Altitude | - 500 ~ 10000 feet |
*Specifications are subject to change.