Operating Indicators
Operation
Operating Indicators
•
Indicators at the Output End of the unit show the unit’s power status and alarms for conditions that could cause it to shut down.
Output Watts
Power on – The Voltage Input and Power Output indicators automatically toggle between input and output values at
Over Current | Current Overload Protection – |
| If the inverter is overloaded, |
| it will shut down to protect itself. |
| The meter will flash as shown to |
| indicate Overload Protect. |
| To restore normal operation, |
| disconnect the excessive load |
| and turn the unit Off and On |
| again using the Power Button. |
Short Circuit | Short Circuit Protection – If the |
| AC output of the inverter is short- |
| circuited for one second or more, |
| it will shut down to protect itself. |
| The meter will flash as shown to |
| indicate Short Circuit Protect and |
| an alarm will sound. |
| To restore normal operation, |
| disconnect the short circuit and |
| turn the unit Off and On again |
| using the Power Button. |
Operating Indicators
Operation
Low Voltage | Low Voltage Protection – If the |
| DC input voltage drops below |
| the alarm threshold of 10.5V the |
| meter will flash as shown to |
| indicate Low Voltage Protection, |
| but the unit will continue to |
| operate. If the input voltage drops |
| to 10.0V or less, the inverter will |
| shut down to protect itself, the |
| meter will continue to flash as |
| shown, and an alarm will sound. |
| To restore normal operation, return |
| the DC input voltage to at least |
| 12V. The inverter will automatically |
| return to normal operation. |
High Voltage | High Voltage Protection – If the |
| DC input voltage rises above 15.0V, |
| the inverter will shut down to protect |
| itself, the meter will flash as shown |
| to indicate Over Voltage Protection, |
| and an alarm will sound. |
| To restore normal operation, return |
| the DC input voltage to less than |
| 15V. The inverter will automatically |
| return to normal operation. |
|
|
|
|