Electrical Requirements
Your new ceiling fan will require a grounded electrical supply line of 120 volts AC, 60 Hz, 15 amp circuit.
The outlet box must be securely anchored and capable of withstanding a load of at least 50 pounds.
! WARNING
To reduce the risk of fire, electrical shock, or personal injury, mount fan to outlet box marked “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
! WARNING
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
! WARNING
To avoid fire or shock, follow all wiring instructions carefully. Any electrical work not described in these instructions should be done or approved by a licensed electrician.
If your fan is to replace an existing ceiling light fixture, turn electricity off at the main fuse box at this time and remove the existing light fixture.
How to Put Your Ceiling Fan Together
1.Remove the hanger ball by loosening the setscrew
in the hanger ball until the ball falls freely down the | PIN | |
downrod (Figure 1). Remove the pin from the | ||
HANGER | ||
downrod, then remove the hanger ball. Retain the | BALL | |
pin and hanger ball for reinstallation in step 4. |
|
2.Separate, untwist and unkink the three 80” motor leads. Route the motor lead wires through the
downrod. Remove the upper setscrew from the | DOWNROD | SETSCREW | ||
motor coupling. Align the clevis pin holes in the |
| |||
|
| |||
downrod with the holes in the motor coupling. |
|
| ||
Install the clevis pin and secure with the hairpin clip | Figure 1 |
| ||
(Figure 2). The clevis pin must go through the |
| |||
|
| |||
holes in the motor coupling and the holes in the |
|
| ||
downrod. Be sure to push the straight leg of the |
|
| ||
hairpin clip through the hole near the end of the |
|
| ||
clevis pin until the curved portion of the hairpin clip | MOTOR |
| ||
snaps around the clevis pin. The hairpin clip must | COUPLING |
| ||
SETSCREW |
| |||
be properly installed to prevent the clevis pin from | HAIRPIN | |||
CLEVIS PIN | ||||
working loose. Pull on the downrod to make sure | CLIP | |||
|
| |||
the clevis pin is properly installed. Reinstall the |
|
| ||
upper setscrew in the motor coupling. Check that |
|
| ||
the lower setscrew is tightened securely (Figure 2). |
|
| ||
NOTE: The setscrews must be properly installed | CLEVIS | DOWNROD | ||
as described above, or fan wobble could result. |
| |||
|
| PIN | CLEVIS | |
|
|
| PIN | |
! | WARNING | UPPER |
| |
SETSCREW | HAIRPIN | |||
|
|
| CLIP | |
It is critical that the clevis pin in the motor coupling |
| SETSCREW | ||
is properly installed and the setscrews securely |
| |||
|
| |||
tightened. Failure to verify that the pin and setscrews |
|
| ||
are properly installed could result in the fan falling. |
|
| ||
|
|
| MOTOR COUPLING | |
|
| Figure 2 |
|
4 | U.L. Model No.: CF901 |