Philips SKSGPK254 Ordering Information, Page 2 of, Job Information Type, Skyway SKS2GPK228 or

Page 2
Page 2 of 2

Skyway SKS2GPK228 or 254

Page 2 of 2

2' x 4' Recessed Fluorescent, Tri-Lens Frame Static or Air Supply/Return, 2 or 3 Lamp T5 or T5HO

Model No. SKS2GPK228120WA

LER = FP - 64.1 IW - 54.5 BF - 0.92 Comparative yearly lighting energy cost per

1000 lumens = $3.74

Report Number: G2008274

Catalog Number: SKS2GPK228120WA

Lamps: (2) F28T5/835/ALTO

Luminaire: Skyway Recessed 2' x 4' fixture prismatic acrylic lens assembly.

Ballast: ST232120E

Report is based on 2600 Lumens per lamp. Efficiency: 73.0%

CIE Type-Direct-Indirect

 

 

 

 

Plane:

 

 

 

 

0-Deg

 

90-Deg

Spacing Criteria:

 

 

1.2

 

 

1.2

Shielding Angles:

 

 

90

 

 

90

Plane:

 

 

 

 

0-Deg

 

90-Deg

Luminous Length:

 

45.600

 

21.600

COEFFICIENTS OF UTILIZATION –

 

 

ZONAL CAVITY METHOD. EFFECTIVE

 

FLOOR CAVITY REFLECTANCE 0.200

 

RC

 

80

 

 

50

 

 

30

 

RW

70

50

30

50

30

10

50

30

10

01

81

78

75

73

70

69

70

69

67

02

74

69

65

65

62

59

63

60

58

03

68

62

56

58

54

51

57

53

50

04

63

55

50

53

48

44

51

47

44

05

59

50

44

48

43

39

46

42

39

06

54

46

40

44

39

35

42

38

35

07

51

42

36

40

35

31

39

34

31

08

47

38

32

37

32

28

36

31

28

09

44

35

30

34

29

26

33

29

26

10

42

33

27

32

27

23

31

26

23

CANDELA DISTRIBUTION

 

0.0

45.0

90.0

FLUX

0

1814

1814

1814

 

5

1789

1784

1784

169

15

1690

1687

1716

479

25

1521

1542

1608

715

35

1271

1316

1341

810

45

859

867

853

673

55

505

559

511

486

65

282

298

280

299

75

143

128

112

140

85

13

10

6

24

90

10

9

5

 

 

 

 

 

 

ZONAL LUMEN SUMMARY

ZONE

LUMENS

% LAMP

% FIXT

00-030

1363

26.2

35.9

00-040

2173

41.8

57.3

00-060

3333

64.1

87.8

00-090

3796

73.0

100.0

90-180

0000

0.0

000.0

00-180

3796

73.0

100.0

LUMINANCE DATA IN CANDELA/SQ. METER

AVERAGE AVERAGE AVERAGE AVERAGE

IN DEG.

0-DEG. 45-DEG. 90-DEG.

45

1911.

1929.

1898.

55

1385.

1533.

1401.

65

1050.

1109.

1042.

75

869.

778.

681.

85

235.

180.

108.

Model No. SKS2GPK254UNVPG

LER = FP - 56.9 IW - 114.9 BF - 1.0 Comparative yearly lighting energy cost per

1000 lumens = $4.21

Report Number: G2008317

Catalog Number: SKS2GPK254UNVPG

Lamps: (2) F54T5/835/HO/ALTO

Luminaire: Skyway Recessed 2' x 4' fixture prismatic acrylic lens assembly.

Ballast: ICN-2S25-90C

Report is based on 4500 Lumens per lamp. Efficiency: 72.7%

CIE Type-Direct-Indirect

 

 

 

 

Plane:

 

 

 

 

0-Deg

 

90-Deg

Spacing Criteria:

 

 

1.2

 

 

1.3

Shielding Angles:

 

 

90

 

 

90

Plane:

 

 

 

 

0-Deg

 

90-Deg

Luminous Length:

 

45.600

 

21.600

COEFFICIENTS OF UTILIZATION –

 

 

ZONAL CAVITY METHOD. EFFECTIVE

 

FLOOR CAVITY REFLECTANCE 0.200

 

RC

 

80

 

 

50

 

 

30

 

RW

70

50

30

50

30

10

50

30

10

01

80

77

74

72

70

68

69

68

66

02

73

68

62

64

61

58

62

59

56

03

67

60

55

57

53

49

55

52

48

04

62

54

48

51

47

43

50

46

42

05

57

49

43

46

41

38

45

41

37

06

53

44

38

42

37

33

41

36

33

07

50

40

34

39

33

30

38

33

29

08

46

37

31

35

30

27

35

30

27

09

43

34

28

33

28

24

32

27

24

10

41

31

26

30

25

22

30

25

22

CANDELA DISTRIBUTION

 

0.0

45.0

90.0

FLUX

0

2812

2812

2812

 

5

2790

2790

2790

265

15

2668

2666

2690

755

25

2446

2470

2551

1145

35

2107

2174

2281

1356

45

1576

1541

1527

1200

55

938

1009

935

880

65

524

581

525

568

75

291

263

252

299

85

86

63

58

77

90

13

12

7

 

 

 

 

 

 

ZONAL LUMEN SUMMARY

ZONE

LUMENS

% LAMP

% FIXT

00-030

2165

24.1

33.1

00-040

3521

39.1

53.8

00-060

5601

62.2

85.6

00-090

6545

72.7

100.0

90-180

0000

0.0

000.0

00-180

6545

72.7

100.0

LUMINANCE DATA IN CANDELA/SQ. METER

AVERAGE AVERAGE AVERAGE AVERAGE

IN DEG.

0-DEG. 45-DEG. 90-DEG.

45

3506.

3428.

3397.

55

2573.

2767.

2564.

65

1950.

2163.

1954.

75

1769.

1599.

1532.

85

1552.

1137.

1047.

Ordering Information

Explanation of Catalog Number. Example: SKS2GPK254UNVPG

2

P

K

Skyway

Recessed

Fluorescent

SK

SY

Body Style:

Fixture

Ceiling Type:

Side Lens:

Center Lens:

Lamp

Lamp:

Voltage:

 

 

 

 

 

 

 

 

 

Options:

S = Static

Width

G = Standard

P= Frost White

K= Pattern 19

Quantity

(By Others)

120, 277 or

 

 

 

Add appropriate

A = Air

 

Grid

Acrylic Lens

.156 Virgin

2=2 Lamp

28=T5 28W

UNV=120-277

 

 

 

suffix to catalog

 

 

T = Slot Grid

 

Acyrlic Lens

3=3 Lamps

54=T5HO 54W

 

 

 

 

 

no., ie: (A)

 

 

 

 

 

 

(Nominal 48")

 

Ballast Type:

 

 

 

 

 

 

 

 

 

 

 

 

Standard Skyway

 

 

 

 

 

 

 

 

<20THD <10THD

 

 

 

 

 

 

1 or 2 Lamp 28W Elec. T5

PI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 or 2 Lamp 28W Elec. T5

PG ††

For NYC Code – I.B.E.W. Manufactured

 

 

 

 

 

1 or 2 Lamp 54W Elec. T5HO

PG ††

 

 

 

 

 

 

 

1-3 Lamp 54W Elec. T5HO

PU ††

NK

For NYC Code – Local 3 Manufactured

 

Options/AccessoriesFusing: Internal fast blow fusing: SUFFIX: A.Internal slow blow fusing: SUFFIX: C.Drywall Kit: Order Catalog Number: FK92X4.Electrical Wiring Options: Consult factory.For motion or light sensor: See Folio OA20-10 and OA20-30.Specifications

Performance: In an installation of 2 lamp 28W luminaires in a room cavity ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .78. To reduce glare the average brightness at 65° shall not exceed 1109 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 64.1%.

Air Handling: (SKA only) side air passages for air supply or air return. Supply air is discharged vertically. Optional side closure strips. Air return is also provid- ed through the lamp compartment through fixture body ends.

Materials: Chassis parts are die-formed code gauge cold rolled steel. Housing has side rails hemmed over and housing ends turned-in for safe handling.

Finish: Chassis exterior–black baked polyester enamel. Cavity–white baked polyester enamel minimum 86% reflectance. Rust preventative undercoating. Reflectors- 95% reflective white powder coated.

†Instant Start (120, 277 or UNV) ††Program Rapid Start (UNV only)

Specifications (continuned)

Lens: Proprietary high quailty frost white acrylic and clear conical prism lens assembly.

Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°.

UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed.

This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See: www.lamprecycle.org

Job Information Type:

For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish.

www.lightolier.com © 2009 a Philips Group

Section 5/Folio MA12-16

Lightolier is a Philips group brand

Image 2