Allied Air Enterprises 4AC18LT Start-Up, Refrigerant Charging, Refrigerant Charge Adjustment

Page 13

START-UP

CAUTION

If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.

1.Rotate fan to check for frozen bearings or binding.

2.Inspect all factory and field-installed wiring for loose connections.

3.After evacuation is complete, open liquid line and suction line service valves to release refrigerant charge (contained in outdoor unit) into system.

4.Replace the stem caps and secure finger tight, then tighten an additional 1/6 of a turn.

5.Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit nameplate. If not, do not start equipment until the power company has been consulted and the voltage condition corrected.

6.Set thermostat for cooling demand, turn on power to indoor blower, and close the outdoor unit disconnect switch to start the unit.

7.Recheck unit voltage with unit running. Power must be within range shown on unit nameplate.

Refrigerant Charging

This system is charged with R410A refrigerant which operates at much higher pressures than R-22. The liquid line drier provided with the unit is approved for use with R410A. Do not replace it with one designed for use with R-

22.This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device.

R410A refrigerant cylinders are rose colored. Refrigerant should be added through the suction valve in the liquid state.

Certain R410A cylinders are identified as being equipped with a dip tube. These allow liquid refrigerant to be drawn from the bottom of the cylinder without inverting the cylinder. Do not turn this type of cylinder upside down to draw refrigerant.

Units are factory charged with the amount of R410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15’ line set. For varying lengths of line set, refer to Table 5 for refrigerant charge adjustment. A blank space is provided on the unit rating plate to list the actual field charge.

Refrigerant Charge Adjustment

Liquid Line Set

Oz. per 5 ft. adjust

Diameter

from 15 ft. line set*

 

 

3/8 in.

3 oz. Per 5 ft.

 

 

*If line length is greater than 15 ft., add this amount. If line length is less than 15 ft., remove this amount.

Table 5

IMPORTANT

Mineral oils are not compatible with R410A. If oil must be added, it must be a polyolester oil.

If the system is void of refrigerant, clean the system using the procedure described below.

1.Use dry nitrogen to pressurized the system and check for leaks. Repair leaks, if possible.

2.Evacuate the system to remove as much of the moisture as possible.

3.Use dry nitrogen to break the vacuum.

4.Evacuate the system again.

5.Weigh the appropriate amount of R410A refrigerant (listed on unit nameplate) into the system.

6.Monitor the system to determine the amount of moisture remaining in the oil. Use a test kit to verify that the moisture content is withing the kit’s dry color range. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future.

The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is determined by the unit’s refrigerant metering device and the outdoor ambient temperature.

Measure the liquid line temperature and the outdoor ambient temperature as outlined below:

506469-01

Issue 1008

Page 13 of 24

Image 13
Contents Lennox International Inc. Company 4AC18LT SeriesInstallation Clearances InstallationTorque Table GeneralSlab Mounting Electrical WiringSlab Mounting Roof MountingOutside Unit Placement & Installation PlacementLine Set Isolation Refrigerant Line Set DiametersThermostat Designations Installing Refrigerant LineRefrigerant Piping Refrigerant Line Sets Installing Horizontal Runs Refrigerant Line Sets Transition from Vertical to Horizontal Required Euipment Flushing ProcedureExpansion Valve Systems Refrigerant Metering DeviceTXV Data To Close Liquid or Suction Line Service Valve To Access the Schrader PortEvacuation Using an Electronic Leak DetectorIssue START-UP Refrigerant Charge AdjustmentRefrigerant Charging Blocking Outdoor Coil Check Charge Using Normal Operating Pressures R410A Temperature/Pressure ChartSubcooling Values Approach Values for TXV SystemsIssue Operation Flash Codes Flash Codes Miswired Module Troubleshooting Indoor Coil MaintenanceIndoor Unit Start-Up and Performance Checklist Wire Diagram Issue

4AC18LT specifications

Allied Air Enterprises has made significant strides in the HVAC industry with the introduction of its 4AC18LT air conditioner. This model is part of a premium line of products that emphasizes efficiency, reliability, and advanced cooling technology. The 4AC18LT is specifically designed to meet the diverse needs of both residential and light commercial applications, making it a versatile choice for many consumers.

One of the standout features of the 4AC18LT is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating of up to 18, this unit is engineered to provide excellent energy efficiency, significantly reducing electricity consumption while delivering consistent cooling performance. As energy costs continue to rise, homeowners and businesses can benefit greatly from this efficiency, leading to lower monthly utility bills and a reduced carbon footprint.

The 4AC18LT employs advanced R-410A refrigerant, which is known for its environmentally friendly properties. Unlike older refrigerants that contribute to ozone depletion, R-410A is more stable and offers better heat transfer capabilities, which enhances the overall performance of the unit. This focus on eco-friendliness aligns with contemporary environmental standards and regulations, ensuring that users are making a responsible choice for their cooling needs.

In terms of design, the 4AC18LT features a robust and compact frame that is built to withstand the rigors of outdoor installation. The unit's durability is further enhanced by its corrosion-resistant finish, which protects the coil and cabinet from harsh weather conditions, extending the life span of the system.

Noise reduction technology is another highlight of the 4AC18LT. This model is designed with a quieter operation in mind, utilizing a sound blanket and insulated compressor compartment. These features work together to minimize noise levels, allowing users to enjoy a comfortable indoor environment without disruptive sound.

The 4AC18LT also supports advanced controls and compatibility with smart thermostats, providing users with greater flexibility and convenience. Homeowners can take advantage of programmable features, enabling them to optimize cooling schedules for energy savings and increased comfort.

Overall, Allied Air Enterprises’ 4AC18LT air conditioner combines efficiency, environmental responsibility, durability, and user-friendly features, making it an excellent choice for those in need of reliable cooling solutions. Whether installed in a residential or light commercial setting, the 4AC18LT promises to deliver exceptional performance and peace of mind.