Carrier Compressor and Condensing Unit specifications Aux, Dts, Lls

Page 6

 

 

 

LEGEND

AUX

— Auxiliary

M1

— Evaporator Fan or

C

— Compressor Contactor

 

Chilled Water Pump

C1

— Compressor Contactor

M2

— Cooling Tower Pump

 

(XL start and first step of PW start)

M3

— Cooling Tower Fan

C2

— Compressor Contactor

NEC

— National Electrical Code

 

(PW second step)

OPS

— Oil-Pressure Switch

CH

— Crankcase Heater

POR

— Pumpout Relay

CHR

— Crankcase Heater Relay

PW

— Part Wind

CR

— Control Relay

SW

— Start-Stop-Reset Switch

DTS

— Discharge Temperature Sensor

TB

— Terminal Block

DX

— Direct Expansion

TDR

— Time Delay Relay

FU

— Fuse

TM

— Timer Motor

HPS

— High-Pressure Switch

TR

— Timer Relay

LLS

— Liquid Line Solenoid Valve

XL

— Across-the-Line

LPS

— Low-Pressure Switch

 

 

Terminal Block Connector

Unmarked Terminal

Marked Terminal

Factory Wiring

Field Control Wiring

To indicate common potential only; not to represent wiring.

Splice

NOTES:

1.Factory wiring is in compliance with NEC. Any field modifications or additions must be in compliance with all applicable codes. Use copper, copper-clad aluminum for field power supply only.

2.Field power supply wiring must be 75 C minimum.

3.Compressor thermally protected. Three-phase motors are pro- tected against primary single-phasing condition.

4.Pilot duty control must be field supplied. Minimum contact rating must be 25 va.

5.60 Hz units have 120 volt control circuit. 50 Hz units have 230 volt control circuit. A separate source of supply at the correct voltage must be field supplied supply at the through a fused disconnect

device with a maximum rating of 15 A to TB2 connections L1 (Hot Side) and L2 (Neutral).

6.Open control circuit disconnect switch for servicing only. Discon- nect must remain closed for crankcase heater to operate.

7.A transformer of the following rating may be field supplied for 60 Hz units: 350 va.

8.Transformer must be fused and grounded per applicable codes.

9.If any of the original wiring furnished must be replaced, it must be replaced with 90 C wire or its equivalent.

10.Wiring is shown for single pumpout control. Single pumpout control should not be used on direct-expansion (DX) cooler appli- cations (see lower diagram for wiring when applied with DX cooler).

Fig. 6 — Control Circuit Wiring for 06E/07E Units

6

Image 6
Contents Contents Safety ConsiderationsInstallation Electrical Connections 07E Water-Cooled Condensing Units Unit 07E Volts06E Hermetic Compressor Units Electrical Data Compressor Motor With Circuit Breaker AUX DTSLLS Unit 06E PRE-START-UP06E Physical Data RefrigerantSTART-UP 07E Physical DataUnit 07E Protection Devices ServiceFactory Switch Settings Capacity Control SystemNO. Removing, Inspecting and Replacing Components FigCapacity Control ContrSuction Cutoff Unloader Operation Compressor Components 06E Shown Lubrication System Torque ValuesSuction and Discharge Valve Plate Assembly Compressor Running Gear RemovalCompressor Running Gear Replacement Wear Limits 06E CompressorMotor Replacement Motor RemovalMotor Alignment Forced Circulation Page Copyright 2001 Carrier Corporation