Carrier 50GS, 50GX Color Coding for 208/230-V Motor Leads, Color Coding for 460-V GE Motor Leads

Page 18

When evaluating the refrigerant charge, an indicated adjust- ment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.

Proceed as follows:

1.Remove caps from low- and high-pressure service fittings.

2.Using hoses with valve core depressors, attach low- and high-pressure gauge hoses to low- and high-pressure service fittings, respectively.

3.Start unit in Cooling mode and let unit run until system pressures stabilize.

4.Measure and record the following:

a.Outdoor ambient-air temperature (°F db).

b.Evaporator inlet-air temperature (°F wb).

c.Suction-tube temperature (°F) at low-side service fitting.

d.Suction (low-side) pressure (psig).

5.Using “Cooling Charging Charts” compare outdoor-air tem- perature (°F db) with the suction line pressure (psig) to determine desired system operating suction line temperature. See Fig. 15-27.

6.Compare actual suction-tube temperature with desired suction-tube temperature. Using a tolerance of ±3°F, add refrigerant if actual temperature is more than 3°F higher than proper suction-tube temperature, or remove refrigerant if actual temperature is more than 3°F lower than required suction-tube temperature.

NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section.

INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity.

Tables 8 and 9 show cooling airflows at various external static pressures. Refer to these tables to determine the airflow for the system being installed.

NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly.

Disconnect electrical power to the unit and install lockout tag before changing blower speed. Electrical shock can cause serious injury or death.

Airflow can be changed by changing the lead connections of the blower motor.

Unit 50GS two- or three-speed motors (except size 030) are factory wired for low speed operation. Unit 50GS030 is factory wired for medium speed.

All 50GX units are factory wired for low speed and may need to be wired for medium or high speed in the field.

FOR 208/230V

For color coding on the 208/230V motor leads, see Table 6.

To change the speed of the indoor fan motor (IFM), remove the fan motor speed leg lead from the time delay relay (TDR). This wire is attached to terminal–3 of TDR for single-phase and 3-phase

Table 6—Color Coding for 208/230–V Motor Leads

3-SPEED

2-SPEED

black = high speed

black = high speed

blue = medium speed

-

red = low speed

red = low speed

units. To change the speed, remove and replace with lead for desired blower motor speed. Insulate the removed lead to avoid contact with chassis parts.

FOR 460-V GE MOTORS

For color coding on the 460-v GE motor leads, see Table 7.

Table 7—Color Coding for 460-V GE Motor Leads

3-SPEED

2-SPEED

black = high

black = high

violet = jumper

blue = jumper

orange = medium

-

red = low

red = low

 

 

To change the speed of the indoor fan motor (IFM), remove fan motor speed lead from the time delay relay (TDR) and replace with the lead for the desired blower motor speed. The motor speed lead is attached to terminal–3 of TDR. For low and medium speeds black must be connected to the jumper wire. Insulate removed lead end to avoid contact with chassis parts. To select high speed on 460-v GE motors, separate the black female quick connect (QC) from the jumper lead male quick connect (QC) and connect the black lead to the BR. Insulate the jumper to avoid contact with any chassis parts.

COOLING SEQUENCE OF OPERATION

With the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO position, the cooling sequence of operation is as follows:

When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and time delay relay (TDR) (through unit wire G) across the 24-v secondary of transformer (TRAN).

The normally open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to con- denser (outdoor) fan motor (OFM). Both motors start instantly.

The set of normally open contacts of energized relay TDR close and complete the circuit through evaporator blower (indoor) fan motor (IFM).

NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.

The cooling cycle remains “on” until the room temperature drops to a point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat “breaks” the circuit between thermostat terminal R to terminals Y and G. These open circuits deenergize contactor coil C and relay coil TDR. The condenser and compressor motors stop. After a 30-second delay, the blower motor stops. The unit is in a “standby” condition, waiting for the next “call for cooling” from the room thermostat.

MAINTENANCE

To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This cooling unit should be

18

Image 18
Contents Table of Contents Safety ConsiderationsIntroduction 50GS018-042 and 50GX024-036 Unit Dimensions Installation Inspection50GS048-060 and 50GX042-060 Unit Dimensions Roof Curb Dimensions 50GS and 50GX Unit Corner Weights Suggested Rigging Configuring Units for Downflow Vertical DIS- Charge Physical Data-Unit 50GSPhysical Data-Unit 50GX Supply and Return Duct Opening HIGH-VOLTAGE Connections Control Voltage ConnectionsStandard Connection Electrical Data-50GS MocpElectrical Data-50GX MCA MocpTransformer Protection PRE-START-UPSTART-UP Start UP Cooling Section and Make ADJUST- MentsChecking and Adjusting Refrigerant Charge Checking Cooling Control OperationWiring Diagram 208/230-60-1 Wiring Diagram 208/230-60-3 Wiring Diagram Color Coding for 208/230-V Motor Leads Indoor Airflow and Airflow AdjustmentsMaintenance Color Coding for 460-V GE Motor Leads460 Volt Unit Watts 281 282 278 276 Cfm 833 776 702 638 554 Cooling Charging Chart, 50GS018 Units Cooling Charging Chart, 50GS042 Units Evaporator Blower and MotorCooling Charging Chart, 50GX030 Units Condenser COIL, Evaporator COIL, and CONDEN- Sate Drain PAN Condenser FANRefrigerant Circuit Evaporator Airflow TroubleshootingSTART-UP Checklist Liquid Line StrainerTroubleshooting-Cooling Symptom Cause RemedySTART-UP Checklist Remove and Store in JOB File Book Catalog No Form 50GS,GX-4SI Replaces 50GS,GX-3SI Tab

50GX, 50GS specifications

Carrier has long been a leader in the HVAC industry, and its latest offerings, the 50GX and 50GS series, continue this tradition. These units stand out for their robust design, advanced technology, and energy-efficient operation, making them ideal choices for commercial and light industrial applications.

The Carrier 50GX is a packaged rooftop unit known for its innovative features aimed at enhancing energy efficiency while ensuring optimal indoor air quality. It employs a variable-speed compressor, which allows for precise temperature control and reduced energy consumption. The 50GX is equipped with microprocessor controls that optimize performance and simplify maintenance, offering real-time diagnostics and monitoring.

One of the standout technologies in the 50GX is its use of R-410A refrigerant, a greener alternative that reduces environmental impact without compromising cooling performance. This refrigerant is designed to deliver superior cooling efficiency while meeting strict environmental regulations. Additionally, the system features an integrated economizer, which takes advantage of outside air to improve energy efficiency during cooler months, reducing reliance on mechanical cooling.

The 50GS series, while similar in many respects to the 50GX, is tailored for applications requiring heating solutions. These units offer gas heat as an option, providing flexibility for varying climate conditions. The 50GS also incorporates an advanced heat exchanger design that maximizes heat transfer efficiency and reduces operational costs.

Both the 50GX and 50GS units are built with durability in mind. They feature a galvanized steel cabinet with a powder-coated finish, providing resistance to rust and corrosion. The robust construction ensures a long lifespan even in challenging environments.

Maintenance is made easier with these models, thanks to their accessible design that allows for quick servicing. Both the 50GX and 50GS units come with a host of customizable options, including different airflow configurations and additional filtration systems to enhance air quality.

In conclusion, the Carrier 50GX and 50GS series represent the pinnacle of HVAC technology with their focus on energy efficiency, environmental sustainability, and robust construction. These units are ideal for customers looking to invest in reliable and efficient climate control solutions for their facilities, combining advanced technology with time-tested engineering.