Carrier 48SS030, 48SS036, 48SS042, 48SS024 manual Certified Dimension Print, Unit Corner Weight

Page 3

CERTIFIED DIMENSION PRINT

REQ'D CLEARANCES FOR SERVICING Ð in. (mm)

Duct Panel . . . . . . . . . . . . . . . . . . . . . . . . 0 Unit Top . . . . . . . . . . . . . . . . . . . . . 36 (914.4) Side Opposite Ducts . . . . . . . . . . . . . . 36 (914.4) Compressor Access . . . . . . . . . . . . . . 36 (914.4) (Except for NEC requirements)

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L

Ð in. (mm)

 

 

 

Maximum Extension of Overhangs . . .

. . . 48 (1219.2)

Unit Top

. . . 14 (355.6)

Duct Side of Unit

. . . . . 2 (50.8)

Side Opposite Ducts

. . . 14 (355.6)

Bottom of Unit

. . . . . . . 0.

Flue Panel

. . . 36 (914.4)

NEC (National Electrical Code) REQ'D CLEARANCES

 

 

 

Ð in. (mm)

 

 

 

 

 

Between Units, Control Box Side . . . .

. . . 42 (1066.8)

Unit and Ungrounded Surfaces,

 

 

Control Box Side

. . . 36 (914.4)

Unit and Block or Concrete Walls and Other

Grounded Surfaces, Control Box Side

. . . 42 (1066.8)

NOTE: Clearances must be maintained to prevent recircu- lation of air from outdoor fan discharge.

 

UNIT

ELECTRICAL

UNIT

 

CORNER WEIGHT

 

 

WEIGHT

 

 

(lb/kg)

 

 

 

48SS

CHARACTERISTICS

kg

A

 

B

C

 

D

OUTDOOR COIL

 

 

 

lb

 

 

018040

208/230-1-60

272

123

81/37

62/28

76/35

53/24

 

 

024040

208/230-1-60

303

138

97/44

43/20

123/56

40/18

 

024060

208/230-1-60

315

143

100/45

46/21

126/57

43/20

 

030040

208/230-1-60

320

145

100/45

47/21

126/57

47/21

 

030060/080

208/230-1-60

324

147

94/43

63/29

115/52

52/24

 

036060/080

208/230-1-60

336

153

86/39

76/35

111/50

 

63/29

 

036100/120

208/230-1-60

348

158

89/40

79/36

114/52

66/30

 

INDOOR COIL

208/230-1-60

375

170

95/43

86/39

119/54

75/34

 

042060/080

 

042100/120

208/230-1-60

387

176

98/45

89/40

122/55

78/35

 

 

UNIT

 

DIMENSION

CENTER OF GRAVITY

 

UNIT

HEIGHT

 

 

 

(in./mm)

 

 

 

(in./mm)

 

 

 

48SS

(in./mm)

 

 

 

 

 

 

 

 

 

 

 

E

F

 

G

X

 

 

Y

 

Z

 

018040

24.12/612.8 169¤16/420.7 1815¤16/481.0

25.07/637

20.59/523

10.85/276

 

024040

24.12/612.8 169¤16/420.7 1815¤16/481.0

27.07/688

23.35/693

10.85/276

 

024060

24.12/612.8 169¤16/420.7 1815¤16/481.0

26.98/685

23.27/591

10.85/276

 

030040

24.12/612.8 169¤16/420.7 1815¤16/481.0

26.71/678

23.46/596

10.85/276

 

030060/080 24.12/612.8 169¤16/420.7 1815¤16/481.0 27.15/689 22.36/568 10.85/276

 

036060/080 24.12/612.8 169¤16/420.7 1815¤16/481.0 27.50/698 22.48/571 10.85/276

 

036100/120 24.12/612.8 169¤16/420.7 1815¤16/481.0 27.40/696 22.44/570 10.85/276

 

042060/080 28.12/714.2 209¤16/522.3 2215¤16/582.6 27.01/686 22.44/570 12.65/321

 

042100/120

28.12/714.2

209¤16/522.3 2215¤16/582.6

26.94/684

22.44/570

12.65/321

INDOOR COIL ACCESS

3

Image 3
Contents 48SS018, 024, 030, 036, 042, 048 Electrical Data Unit Certified Dimension PrintUnit Corner Weight Unit Dimension Center of Gravity HeightReqd Clearances to Combustible Reqd Clearances for ServicingCharacteristics Unit ElectricalUnit Center of Gravity Unit Electrical Corner Weight CPRFCURB002A00 Flat CPRFCURB003A00 Certified Roof Curb Dimension PrintPart Number Curb CPRFCURB001A00